Yaskawa CIMR-PU2A0250 [222/548] View the value set to h4 02 terminal fm monitor gain on the digital operator a voltage equal to 100 of the parameter being set in h4 01 will be output from terminal fm
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc, or 4 to 20 mA using parameter H4-07 and
H4-08. Figure 5.63 illustrates how gain and bias settings work.
No. Name Setting Range Default
H4-02 Multi-Function Analog Output Terminal FM Gain -999.9 to 999.9% 100.0%
H4-03 Multi-Function Analog Output Terminal FM Bias -999.9 to 999.9% 0.0%
H4-05 Multi-Function Analog Output Terminal AM Gain -999.9 to 999.9% 50.0%
H4-06 Multi-Function Analog Output Terminal AM Bias -999.9 to 999.9% 0.0%
Using Gain and Bias to Adjust Output Signal Level
The output signal is adjustable while the drive is stopped.
Terminal FM
1.
View the value set to H4-02 (Terminal FM Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in H4-01 will be output from terminal FM.
2.
Adjust H4-02 viewing the monitor connected to the terminal FM.
3.
View the value set to H4-03 on the digital operator; terminal FM will output a voltage equal to 0% of the parameter
being set in H4-01.
4.
Adjust H4-03 viewing the output signal on the terminal FM.
Terminal AM
1.
View the value set to H4-05 (Terminal AM Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in H4-04 will be output from terminal AM.
2.
Adjust H4-05 viewing the monitor connected to the terminal AM.
3.
View the value set to H4-06 on the digital operator; terminal AM will output a voltage equal to 0% of the parameter
being set in H4-04.
4.
Adjust H4-06 viewing the output signal on the terminal AM.
Output Voltage
Output Voltage
0 V
5 V
10 V
Gain 150%
Bias 0%
Gain = 150%
Bias = 0%
Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
100%
Monitor Value
Monitor Value
0%
H4-07, 08 = 0 H4-07, 08 = 1
10 V
-10 V
100%
5 V
15 V
-5 V
-15 V
-100%
Figure 5.63 Analog Output Gain and Bias Setting Example 1 and 2
Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.
Gain = 100%
Bias = 30%
Gain = 100%
Bias = 0%
Gain 100%
Bias 30%
Gain 100%
Bias 0%
Monitor Value
Monitor Value
0 V
3 V
10 V
100%
0%
Output Voltage
Output Voltage
H4-07, 08 = 0 H4-07, 08 = 1
10V
-10 V
100%
3 V
-4 V
-100%
Figure 5.64 Analog Output Gain and Bias Setting Example 3