Yaskawa CIMR-PU2A0081 [509/548] Screw size

Превью страниц Страница 509 / 548
Yaskawa CIMR-PU2A0021 [509/548] Screw size
Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
2A0211
<2>
R/L1, S/L2, T/L3 1/0 × 2P 1/0 to 2/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 1/0 × 2P 1/0 to 2/0
–, +1 1 to 4/0
+3 1/0 to 4/0
4 4 to 1/0
2A0250
<2>
R/L1, S/L2, T/L3 3/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300
–, +1 3/0 to 300
+3 2 to 300 M10
18 to 23
(159 to 204)
3 3 to 300 M12
32 to 40
(283 to 354)
2A0312
<2>
R/L1, S/L2, T/L3 4/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300
–, +1 3/0 to 300
+3 3/0 to 300 M10
18 to 23
(159 to 204)
2 2 to 300 M12
32 to 40
(283 to 354)
2A0360
<2>
R/L1, S/L2, T/L3 250 × 2P 4/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 4/0 × 2P 4/0 to 600
–, +1 250 to 600
+3 3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
2A0415
<2>
R/L1, S/L2, T/L3 350 × 2P 250 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 2P 300 to 600
–, +1 300 to 600
+3 3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
<1> When installing an EMC filter, additional measures must be taken to comply with IEC61800-5-1. Refer to EMC Filter Installation on page 502
for details.
<2> Drive models 2A0110 to 2A0415 require the
use of UL-Listed closed-loop crimp terminals for UL/cUL compliance. Use only the tools recommended
by the terminal manufacturer for crimping.
D.3 UL and CSA Standards
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
509
D
Standards Compliance

Содержание