4.6 Application Selection
Application Presets are available to facilitate drive setup
for commonly used applications. Selecting one of these Application
Presets automatically assigns functions to the input and output terminals and sets a predefined group of parameters to values
appropriate for the selected application.
In addition, the parameters most likely to be changed are assigned to the group of User Parameters, A2-01 through A2-16.
User Parameters are part of the Setup Group, which provides quicker access by eliminating the need to scroll through multiple
menus.
Note: 1. Application Presets can only be selected if all drive parameters are at their original default settings.
2. Entering a value to A1-03 to enable an Application Preset will fix that value to the parameter. The value cannot be changed without first
setting A1-03 to 2220 or 3330 to initialize the drive.
WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter
A1-03 may automatically change the I/O terminal function from the default setting. Failure to comply may result in death or serious injury.
No. Parameter Name Settings Default
A1-03 Initialize Parameters
0: No initialization (default)
1110: User Initialize (parameter values
must be stored using parameter o2-03)
2220: 2-Wire Initialize
3330: 3-Wire Initialize
5550: Terminal/Control Initialize
8008: Pump
8009: Pump w/ PI
8010: Fan
8011: Fan w/ PI
0
A1-06 Application Presets (monitor only)
0: Disabled
8: Pump
9: Pump w/ PI
10: Fan
11: Fan w/ PI
0
u
A1-03 = 8008: Pump
Table 4.7 Pump Application Parameters
Parameter Name Page
A1-06 Application Preset Selection (monitor only) 118
b1-01 Frequency Reference Selection 139
b1-02 Run Command Selection 140
b1-03 Stopping Method Selection 141
b1-04 Reverse Operation Selection 143
C1-01 Acceleration Time 1 168
C1-02 Deceleration Time 1 168
d1-01 Frequency Reference 1 173
E2-01 Motor Rated Current 186
L2-01 Momentary Power Loss Operation Selection 229
L5-01 Number of Auto Restart Attempts 243
L5-04 Fault Reset Interval Time 243
o1-06 User Monitor Selection Mode 254
o1-07 Second Line Monitor Selection 255
o1-08 Third Line Monitor Selection 255
u
A1-03 = 8009: Pump w/ PI
Table 4.8 Pump w/ PI Application Parameters
Parameter Name Page
A1-06 Application Preset Selection (monitor only) 118
b1-02 Run Command Selection 140
4.6 Application Selection
118
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual