H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function Description Page
16 Frequency detection 4 Closed: When the output frequency is greater than or equal to the value in L4-03 ±L4-04. 212
17 Torque detection 1 (N.C.) Open: Overtorque or undertorque has been detected.
210
18 Torque detection 2 (N.O.) Closed: Overtorque or undertorque has been detected.
19 Torque detection 2 (N.C.) Open: Overtorque or undertorque has been detected. 210
1A During reverse Closed: Drive is running in the reverse direction. 213
1B During baseblock (N.C.) Open: Drive has entered the baseblock state (no output voltage). 213
1E Restart enabled Closed: An automatic restart is performed 213
1F Motor overload alarm (oL1) Closed: oL1 is at 90% of its trip point or greater. An oH3 situation also triggers this alarm. 213
20 Drive overheat pre-alarm (oH) Closed: Heatsink temperature exceeds the parameter L8-02 value. 213
22
Mechanical weakening
detection
Closed: Mechanical weakening detected.
214
2F Maintenance period
Closed: Cooling fan, electrolytic capacitors, IGBTs, or the soft charge bypass relay may require
maintenance.
214
37 During frequency output
Open: Either the drive has stopped or baseblock, DC Injection Braking, or Initial Excitation is
being performed.
Closed: Drive is running the motor (not in a baseblock state and DC Injection is not being
performed).
214
38 Drive enabled
Closed: Multi-function input set for “Drive enable” is closed (H1-oo = 6A)
214
39 Watt hour pulse output Output units are determined by H2-06. Outputs a pulse every 200 ms to indicate the kWh count. 214
3C LOCAL/REMOTE status
Open: REMOTE
Closed: LOCAL
214
3D During speed search Closed: Speed Search is being executed. 214
3E PID feedback low Closed: PID feedback level is too low. 214
3F PID feedback high Closed: The PID feedback level is too high. 214
4A During KEB Ride-Thru Closed: KEB Ride-Thru is being performed. 214
4C During fast stop Closed: A Fast Stop command has been entered from the operator or input terminals. 214
4D oH Pre-alarm time limit Closed: oH pre-alarm time limit has passed. 215
4E Braking transistor fault (rr) Closed: The built-in dynamic braking transistor failed. 215
4F Braking resistor overheat (oH) Closed: The dynamic braking resistor has overheated. 215
50 Waiting to Run Closed: b1-11 Timer is active. 215
51
Sequence timer 1
SeqTimer Disable
Closed: Sequence timer 1 is active.
215
52
Sequence timer 2
SeqTimer Cancel
Closed: Sequence timer 2 is active.
215
53
Sequence timer 3
Sequence timer 3
Closed: Sequence timer 3 is active.
215
54
Sequence timer 4
Sequence Timer 4
Closed: Sequence timer 4 is active.
215
58
Underload detection
UL6
Closed: Underload is detected.
215
60 Internal cooling fan alarm Closed: Internal cooling fan alarm 215
71
Secondary PI Feedback Low
PI2 Feedback Low
Closed: PI2 feedback level is too low.
215
72
Secondary PI Feedback High
PI2 FeedbackHigh
Closed: The PI2 feedback level is too high.
215
100 to 192
Function 0 to 92 with inverse
output
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
215
B.7 H Parameters: Multi-Function Terminals
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
415