Yaskawa CIMR-PU2A0081 [452/548] Phone 800 94 412 fax 888 23 773 web www clrwtr com email info clrwtr com

Превью страниц Страница 452 / 548
Yaskawa CIMR-PU2A0360 [452/548] Phone 800 94 412 fax 888 23 773 web www clrwtr com email info clrwtr com
No. Name Unit Default Settings
Model CIMR-Po
4A0009 4A0011 4A0018 4A0023
o2-04 Drive Model Selection Hex. 96 97 9A
E2-11 Motor Rated Power kW (HP)
3.7
(5)
5.5
(7.5)
7.5
(10)
11
(15)
b3-04 V/f Gain during Speed Search % 100 100 100 100
b3-06 Output Current 1 during Speed Search 0.5 0.5 0.5 0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
b3-26 Start Speed Search Select
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value 245.8 189.5 145.38 140.88
C5-17 Motor Inertia
kgm
2
0.0158 0.0255 0.037 0.053
C6-02 Carrier Frequency Selection 7 7 7 7
E2-01 Motor Rated Current A 7 9.8 13.3 19.9
E2-02 Motor Rated Slip Hz 2.7 1.5 1.3 1.7
E2-03 Motor No-Load Current A 2.3 2.6 4 5.6
E2-05 Motor Line-to-Line Resistance Ω 3.333 1.595 1.152 0.922
E2-06 Motor Leakage Inductance % 19.3 18.2 15.5 19.6
E2-10 Motor Iron Loss for Torque Compensation W 130 193 263 385
L2-02 Momentary Power Loss Ride-Thru Time s 0.5 0.5 0.8 1
L2-03 Momentary Power Loss Min. Baseblock Time s 0.6 0.7 0.8 0.9
L2-04 Momentary Power Loss Voltage Recovery Time s 0.3 0.3 0.3 0.3
L3-24 Motor Acceleration Time for Inertia Calculations s 0.154 0.168 0.175 0.265
L8-02 Overheat Alarm Level °C 110 110 110 115
L8-35 Installation Method Selection 2 2 2 2
L8-38 Carrier Frequency Reduction Selection 2 2 2 2
n1-03 Hunting Prevention Time Constant ms 10 10 10 10
B.15 Defaults by Drive Model
452
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Содержание

2656