H6: Pulse Train Input/Output
No.
(Addr.
Hex)
Name Description Values Page
H6-01
(42C)
Pulse Train Input Terminal
RP Function Selection
0: Frequency reference
1: PID feedback value
2: PID setpoint value
Default: 0
Range: 0 to 2
223
H6-02
(42D)
Pulse Train Input Scaling
Sets the terminal RP input signal frequency that is equal to 100% of the value
selected in H6-01.
Default: 1440 Hz
Min.: 100
Max.: 32000
223
H6-03
(42E)
Pulse Train Input Gain
Sets the level of the value selected in H6-01 when a frequency with the value
set in H6-02 is input.
Default: 100.0%
Min.: 0.0
Max.: 1000.0
223
H6-04
(42F)
Pulse Train Input Bias
Sets the level of the value selected in H6-01 when 0 Hz is input.
Default: 0.0%
Min.: -100.0
Max.: 100.0
224
H6-05
(430)
Pulse Train Input Filter Time
Sets the pulse train input filter time constant.
Default: 0.10 s
Min.: 0.00
Max.: 2.00
224
H6-08
(43F)
Pulse Train Input Minimum
Frequency
Sets the minimum frequency for the pulse train input to be detected. Enabled
when H6-01 = 0, 1, or 2.
Default: 0.5 Hz
Min.: 0.1
Max.: 1000.0
224
B.7 H Parameters: Multi-Function Terminals
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual