Yaskawa CIMR-PU2A0081 [267/548] S2 02 s2 07 s2 12 s2 17 sequence timers 1 to 4 stop time

Превью страниц Страница 267 / 548
Yaskawa CIMR-PU2A0021 [267/548] S2 02 s2 07 s2 12 s2 17 sequence timers 1 to 4 stop time
No. Name Setting Range Default
S2-01 Sequence Timer 1 Start Time 00:00 to 24:00 00:00
S2-06 Sequence Timer 2 Start Time 00:00 to 24:00 00:00
S2-11 Sequence Timer 3 Start Time 00:00 to 24:00 00:00
S2-16 Sequence Timer 4 Start Time 00:00 to 24:00 00:00
n
S2-02/S2-07/S2-12/S2-17: Sequence Timers 1 to 4 Stop Time
Sets the stop times for timers 1 to 4. The values must be set greater than or equal to S2-01/S2-06/S2-11/S2-16.
No. Name Setting Range Default
S2-02 Sequence Timer 1 Stop Time 00:00 to 24:00 00:00
S2-07 Sequence Timer 2 Stop Time 00:00 to 24:00 00:00
S2-12 Sequence Timer 3 Stop Time 00:00 to 24:00 00:00
S2-17 Sequence Timer 4 Stop Time 00:00 to 24:00 00:00
n
S2-03/S2-08/S2-13/S2-18: Sequence Timers 1 to 4 Day Selection
Sets the days for which sequence timers 1 to 4 are active.
No. Name Setting Range Default
S2-03 Sequence Timer 1 Day Selection 0 to 10 0
S2-08 Sequence Timer 2 Day Selection 0 to 10 0
S2-13 Sequence Timer 3 Day Selection 0 to 10 0
S2-18 Sequence Timer 4 Day Selection 0 to 10 0
Setting 0: Timer Disabled
Setting 1: Daily
Setting 2: Mon - Fri
Setting 3: Sat - Sun
Setting 4: Monday
Setting 5: Tuesday
Setting 6: Wednesday
Setting 7: Thursday
Setting 8: Friday
Setting 9: Saturday
Setting 10: Sunday
n
S2-04/S2-09/S2-14/S2-19: Sequence Timers 1/2/3/4 Selection
Sets the action that occurs when sequence timers 1 to 4 are active.
No. Name Setting Range Default
S2-04 Sequence Timer 1 Selection 0 to 2 0
S2-09 Sequence Timer 2 Selection 0 to 2 0
S2-14 Sequence Timer 3 Selection 0 to 2 0
S2-19 Sequence Timer 4 Selection 0 to 2 0
Setting 0: Digital Output Only
Setting 1: Run
Setting 2: Run - PI Disable
n
S2-05/S2-10/S2-15/S2-20: Sequence Timers 1/2/3/4 Reference Source
Selects
the frequency reference source used for running the drive when sequence timers 1 to 4 are active (only applicable when
S2-04/S2-09/S2-14/S2-19 are set to 1 or 2).
5.11 S: Special Application
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
267
5
Parameter Details
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Содержание

2656