Yaskawa CIMR-PU2A0211 [186/548] Provides motor control protects the motor and calculates torque limits set e2 01 to the full load amps fla stamped on the motor nameplate if auto tuning completes successfully the value entered to t1 04 will automatically be saved to e2 01
No. Parameter Name Setting Range Default
E1-11 Middle Output Frequency 2 0.0 to [E1-04]
0.0 Hz
<6>
E1-12 Middle Output Frequency Voltage 2
0.0 to 255.0 V
<4>
0.0 V
<5>
<6>
E1-13 Base Voltage
0.0 to 255.0 V
<4>
0.0 V
<5>
<7>
<4> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<5> The drive changes these settings when Auto-Tuning is performed (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).
<6> Parameter ignored when E1-11 and E1-12 are set to 0.0.
<7> E1-13 and E1-05 are set to the same value when Auto-Tuning is performed.
Output Voltage (V)
Frequency (Hz)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09 E1-07 E1-06 E1-11 E1-04
Figure 5.35 V/f Pattern
Note: 1. The following condition must be true when setting up the V/f pattern: E1-09
≤ E1-07 < E1-06 ≤ E1-11 ≤
E1-04
2. To make the V/f pattern a straight line below E1-06, set E1-09 equal to E1-07. In this case the E1-08 setting is disregarded.
3. E1-03 is unaffected when the drive is initialized, but E1-04 through E1-13 return to their default values.
4. Only
use
E1-11,
E1-12,
and
E1-13 to fine-tune the V/f pattern in the constant output range. These parameters rarely need to be changed.
u
E2: Motor 1 Parameters
These parameters contain the motor data needed for motor 1. Performing Auto-Tuning (including Rotational Auto-Tuning
and Stationary Auto-Tuning 1 and 2) automatically sets these parameters. Refer to Auto-Tuning Fault Detection on page
307 for details if Auto-Tuning cannot be performed.
n
E2-01: Motor Rated Current
Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on
the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.
No. Parameter Name Setting Range Default
E2-01 Motor Rated Current
10% to 200% of the drive
rated current
Determined by
o2-04
Note: 1. The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the
drive is set for a maximum applicable
motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable
motor capacity is higher than 11 kW. Refer to Power Ratings on page 374 for details.
2. An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly
to prevent this error.
n
E2-02: Motor Rated Slip
Sets the motor rated slip in Hz to provide motor control, protect the motor, and calculate torque limits. This value is
automatically set during Auto-Tuning (Rotational Auto-Tuning, Stationary Auto-Tuning 1 and 2).
No. Parameter Name Setting Range Default
E2-02 Motor Rated Slip 0.00 to 20.00 Hz
Determined by
o2-04
If Auto-Tuning cannot be performed, calculate the motor rated slip using the information written on the motor nameplate and
the formula below:
E2-02 = f - (n × p)/120
(f: rated frequency (Hz), n: rated motor speed (r/min), p: number of motor poles)
5.5 E: Motor Parameters
186
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual