Yaskawa CIMR-PU2A0081 [185/548] V f pattern settings e1 04 to e1 13

Превью страниц Страница 185 / 548
Yaskawa CIMR-PU2A0081 [185/548] V f pattern settings e1 04 to e1 13
Table 5.25 Rated Torque Characteristics, Settings 0 to 3
Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3 72 Hz
0
6
200
1.3 2.5 50
12
Voltage (V)
Frequency (Hz)
0
6
200
1.5 3 60
12
Voltage (V)
Frequency (Hz)
0
6
12
200
1.5 3 6050
Voltage (V)
Frequency (Hz)
0
6
12
200
1.5 3 7260
Voltage (V)
Frequency (Hz)
Table 5.26 Derated Torque Characteristics, Settings 4 to 7
Setting = 4 50 Hz Setting = 5 50 Hz Setting = 6 60 Hz Setting = 7 60 Hz
0
5
200
1.3 25 50
35
Voltage (V)
Frequency (Hz)
0
6
200
1.3 25 50
50
Voltage (V)
Frequency (Hz)
0
5
200
1.5 30 60
35
Voltage (V)
Frequency (Hz)
0
6
200
1.5 30 60
50
Voltage (V)
Frequency (Hz)
Table 5.27 High Starting Torque, Settings 8 to B
Setting = 8 50 Hz Setting = 9 50 Hz Setting = A 60 Hz Setting = B 60 Hz
0
7
200
1.3 2.5 50
15
Voltage (V)
Frequency (Hz)
0
9
200
1.3 2.5 50
20
Voltage (V)
Frequency (Hz)
0
7
200
1.5 3 60
15
Voltage (V)
Frequency (Hz)
0
11
200
1.5 3 60
20
Voltage (V)
Frequency (Hz)
Table 5.28 Constant Output, Settings C to F
Setting = C 90 Hz Setting = D 120 Hz Setting = E 180 Hz Setting = F 60 Hz
0
6
12
200
1.5 3 9060
Voltage (V)
Frequency (Hz)
0
6
12
200
1.5 3 12060
Voltage (V)
Frequency (Hz)
0
6
12
200
1.5 3 18060
Voltage (V)
Frequency (Hz)
0
6.9
230
1.5 3 60
13.8
Voltage (V)
Frequency (Hz)
Setting a Custom V/f Pattern (Setting F: Default)
Setting parameter E1-03 to F allows the user to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When initialized, the default values for parameters E1-04 to E1-13 will be equal to Predefined V/f pattern 1.
n
V/f Pattern Settings E1-04 to E1-13
If E1-03 is set to a preset V/f pattern (i.e., a value other than F), the user can monitor the V/f pattern in parameters E1-04
through E1-13. To create a new V/f pattern, set E1-03 to F. Refer to V/f Pattern on page 186 for an example custom V/f
pattern.
No. Parameter Name Setting Range Default
E1-04 Maximum Output Frequency 40.0 to 400.0 Hz 60.0 Hz
E1-05 Maximum Voltage
0.0 to 255.0 V
<4>
575.0 V
E1-06 Base Frequency 0.0 to [E1-04] 60.0 Hz
E1-07 Middle Output Frequency 0.0 to [E1-04] 3.0 Hz
E1-08 Middle Output Frequency Voltage
0.0 to 255.0 V
<4>
15.0 V
E1-09 Minimum Output Frequency 0.0 to [E1-04] 1.5 Hz
E1-10 Minimum Output Frequency Voltage
0.0 to 255.0 V
<4>
9.0 V
5.5 E: Motor Parameters
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
185