Yaskawa CIMR-PU2A0211 [433/548] B 1 s special application
No.
(Addr.
Hex)
Name Description Values Page
S2-14
(3213)
Sequence Timer 3 Selection
Tmr 3 Seq Sel
Sets the action that occurs when sequence timer 3 is active.
0: Digital output only
0: Digital out only
1: Run
1: Run
2: Run - PI disable
2: Run - PI Disable
Default: 0
Range: 0 to 2
267
S2-15
(3214)
Sequence Timer 3 Reference
Source
Tmr 3 Ref Source
Selects the frequency reference source used for running the drive when
sequence timer 3 is active (only applicable when S2-14 is set to 1 or 2).
0: Operator (d1-01)
0: Operator (d1-01)
1: Operator (d1-02)
1: Operator (d1-02)
2: Operator (d1-03)
2: Operator (d1-03)
3: Operator (d1-04)
3: Operator (d1-04)
4: Terminals
4: Terminals
5: Serial communication
5: Serial com
6: Option card
6: Option PCB
7: Pulse input
Default: 0
Range: 0 to 7
267
S2-16
(3215)
Sequence Timer 4 Start
Time
Tmr 4 Start Time
Sets the start time for timer 4. The value must be set less than or equal to S2-17. Default: 00:00
Min.: 00:00
Max.: 24:00
<1>
266
S2-17
(3216)
Sequence Timer 4 Stop Time
Tmr 4 Stop Time
Sets the stop time for timer 4. The value must be set greater than or equal to
S2-16.
Default: 00:00
Min.: 00:00
Max.: 24:00
<1>
267
S2-18
(3217)
Sequence Timer 4 Day
Selection
Tmr 4 Day Sel
Sets the days for which sequence timer 4 is active.
0: Timer disabled
0: Timer disabled
1: Daily
1: Daily
2: Mon - Fri
2: Mon - Fri
3: Sat - Sun
3: Sat - Sun
4: Monday
4: Monday
5: Tuesday
5: Tuesday
6: Wednesday
6: Wednesday
7: Thursday
7: Thursday
8: Friday
8: Friday
9: Saturday
9: Saturday
10: Sunday
10: Sunday
Default: 0
Range: 0 to 10
267
S2-19
(3218)
Sequence Timer 4 Selection
Tmr 4 Seq Sel
Sets the action that occurs when sequence timer 4 is active.
0: Digital output only
0: Digital out only
1: Run
1: Run
2: Run - PI disable
2: Run - PI Disable
Default: 0
Range: 0 to 2
267
S2-20
(3219)
Sequence Timer 4 Reference
Source
Tmr 4 Ref Source
Selects the frequency reference source used for running the drive when
sequence timer 4 is active (only applicable when S2-19 is set to 1 or 2).
0: Operator (d1-01)
0: Operator (d1-01)
1: Operator (d1-02)
1: Operator (d1-02)
2: Operator (d1-03)
2: Operator (d1-03)
3: Operator (d1-04)
3: Operator (d1-04)
4: Terminals
4: Terminals
5: Serial communication
5: Serial com
6: Option card
6: Option PCB
7: Pulse input
Default: 0
Range: 0 to 7
267
<1> Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer.
B.11 S: Special Application
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
433