Yaskawa CIMR-PU2A0081 [399/548] B6 dwell function
No.
(Addr.
Hex)
Name Description Values Page
b5-94
(B94)
<1>
EZ Wake-up Level
EZ Wake-up Lvl
When b5-95 is set to 0 (Absolute), the drive wakes-up when the PID Feedback
(H3-oo = 20) drops below this level for the time set in b5-96.
For reverse-acting, the PID Feedback must be
above this level for the time set
in b5-96.
When b5-95 is set to 1 (Setpoint Delta), the drive wakes-up when the PID
Feedback (H3-oo = 20) drops below the PID Setpoint minus this level (for
normal acting PID) for the time set in b5-96.
For reverse-acting, Wake-up level is PID Setpoint plus this level. The PID
Feedback must be above the wake-up level for the time set in b5-96.
Default: 0.00%
Min.: 0.00
Max.: 600.00
162
b5-95
(B95)
<1>
EZ Wake-up Mode
EZ Wake-up Mode
Sets how the wake-up level is determined.
0: Absolute
1: Setpoint Delta
Default: 0
Range: 0, 1
162
b5-96
(B96)
<1>
EZ Wake-up Time
EZ Wake-up Time
The drive will wake up when the PID Feedback drops below the b5-94, EZ
Wake-up Level for the time set in this parameter.
Default: 1.0 s
Min.: 0.0
Max.: 1000.0
163
<1> Unit and resolution are determined by b5-20, b5-39 and b5-46. Internally limited to b5-38. Changing b5-20, b5-38 and b5-39 will not automatically
update the value of this parameter.
<2> Parameter is only effective when EZ Sleep is enabled by setting b5-89 to 1.
<3> Unit, range and resolution is determined by b5-90. Changing b5-90 will not automatically update the value of this parameter.
u
b6: Dwell Function
No.
(Addr.
Hex)
Name Description Values Page
b6-01
(1B6)
Dwell Reference at Start
Parameters b6-01 and b6-02 set the frequency to hold and the time to maintain
that frequency at start.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
166
b6-02
(1B7)
Dwell Time at Start
Default: 0.0 s
Min.: 0.0
Max.: 10.0
166
b6-03
(1B8)
Dwell Reference at Stop
Parameters b6-03 and b6-04 set the frequency to hold and the time to maintain
that frequency at stop.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
166
b6-04
(1B9)
Dwell Time at Stop
Default: 0.0 s
Min.: 0.0
Max.: 10.0
166
u
b8: Energy Saving
No.
(Addr.
Hex)
Name Description Values Page
b8-01
(1CC)
Energy Saving Control
Selection
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
166
b8-04
(1CF)
Energy Saving Coefficient
Value
Determines the level of maximum motor efficiency. Setting range is 0.0 to
2000.0 for drives 3.7 kW and smaller. The display resolution depends on the
rated output power of the drive.
Default:
<1> <2>
Min.: 0.00
Max.: 655.00
166
b8-05
(1D0)
Power Detection Filter Time
Sets a time constant filter for output power detection. Default: 20 ms
Min.: 0
Max.: 2000
166
b8-06
(1D1)
Search Operation Voltage
Limit
Sets the limit for the voltage search operation as a percentage of the motor
rated voltage.
Default: 0%
Min.: 0
Max.: 100
167
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter value changes automatically if E2-11 is manually changed or changed by Auto-Tuning.
B.3 b: Application
YASKAWA SIEP YAIP1U 01A AC Drive - P1000 Technical Manual
399
B
Parameter List

Содержание

2656

Изучите параметры пробуждения и энергосбережения для приводов. Узнайте, как настроить уровни и время пробуждения, а также коэффициенты эффективности.