Setting 22: Mechanical Weakening Detection
The output closes when a mechanical weakening situation is detected.
Setting 2F: Maintenance Period
The output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as determined
by the estimated performance life span of those components. Components performance life is displayed as a percentage on
the digital operator screen. Refer to Periodic Maintenance on page 329.
Setting 37: During Frequency Output
The output closes when the drive is outputting a frequency.
Status Description
Open Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking, Short Circuit Braking.
Closed Drive is outputting frequency.
ON
ON
OFF
OFF
ONOFF
ON
run command
baseblock
command
output
frequency
during run
during frequency
output
OFF
Figure 5.56 During Frequency Output Time Chart
Setting 38: Drive Enable
Reflects
the status of a digital input configured
as a “Drive enable” input (H1-oo = 6A). If that digital input closes, then the
digital output set for “Drive enable” will also close.
Setting 39: Watt Hour Pulse Output
Outputs a pulse to indicate the watt hours. Refer to H2-06: Watt Hour Output Unit Selection on page 215 for details.
Setting 3C: LOCAL/REMOTE Status
The output terminal closes while the drive is set for LOCAL and opens when in REMOTE.
Status Description
Open
REMOTE: The external reference that has been selected (either b1-01 and b1-02 or b1-15 and b1-16) is used as frequency reference
and Run command source.
Closed LOCAL: The digital operator is used as frequency reference and Run command source.
Setting 3D: During Speed Search
The output terminal closes while Speed Search is being performed. Refer to b3: Speed Search on page 145 for details.
Setting 3E: PID Feedback Low
Output terminal closes when a PID feedback loss
(FbL) is detected. The feedback is considered to be lost if it falls below the
level set to b5-13 for longer than the time set to b5-14. Refer to PID Feedback Loss Detection on page 156 for details.
Setting 3F: PID Feedback High
Output terminal closes when a PID feedback loss (FbH) is detected. The feedback is considered to be lost if it rises beyond
the level set to b5-36 for longer than the time set to b5-37. Refer to PID Feedback Loss Detection on page 156 for details.
Setting 4A: During KEB Operation
The output terminal closes while KEB is being performed. Refer to KEB Ride-Thru Function on page 229 for a KEB function
description.
Setting 4C: During Fast Stop
The output terminal closes when a Fast Stop is being executed. Refer to Setting 15, 17: Fast Stop (N.O., N.C.) on page 200.