Function 143
3. Special Control
3.1 Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made
and the position of the four way valve is also determined. To position the four way valve, the master and slave units
simultaneously start up.
3.1.1 Startup Control in Cooling Operation
3.1.2 Startup Control in Heating Operation
Thermostat ON
Pressure equalization
control prior to startup
Startup control
STEP1 STEP2
Compressor 0 Hz
52 Hz
+ OFF + OFF
124 Hz + OFF + OFF
+2 steps/20 sec.
(until Pc - Pe>0.39MPa is achieved)
Outdoor unit fan STEP4
Ta<20°C: OFF
Ta20°C: STEP4
+1 step/15 sec. (when Pc>2.16MPa)
-1 step/15 sec. (when Pc<1.77MPa)
Four way valve (20S1) Holds OFF OFF
Main motorized valve (EV1) 0 pls 480 pls 480 pls
Subcooling motorized valve
(EV2) (RXYQ8~)
0 pls 0 pls 0 pls
Hot gas bypass valve
(SVP)
OFF
OFF OFF
Accumulator oil return valve
(SVO)
OFF OFF OFF
Injection (SVT) (RXYQ5P
model)
OFF OFF OFF
Ending conditions A lapse of one minute A lapse of 10 sec.
A lapse of 130 sec.
Pc - Pe>0.39MPa
OR
Thermostat ON
Pressure equalization
control prior to startup
Startup control
STEP1 STEP2
Compressor 0 Hz
52 Hz
+ OFF + OFF
124 Hz + OFF + OFF
+2 steps/20 sec.
(until Pc - Pe>0.39MPa is achieved)
Outdoor unit fan STEP4 STEP8 STEP8
Four way valve Holds ON ON
Main motorized valve (EV1) 0 pls 0 pls 0 pls
Subcooling motorized valve
(EV2) (RXYQ8~)
0 pls 0 pls 0 pls
Hot gas bypass valve
(SVP)
OFF OFF OFF
Accumulator oil return valve
(SVO)
OFF OFF OFF
Injection (SVT) (RXYQ5P
model)
OFF OFF OFF
Ending conditions A lapse of one minute A lapse of 10 sec.
A lapse of 130 sec.
Pc>2.70MPa
Pc-Pe>0.39MPa
OR