Daikin FXSQ32MVE [418/458] Rxyq10pay1 12pay1

Daikin FXSQ32MVE [418/458] Rxyq10pay1 12pay1
Si34-803 List of Electrical and Functional Parts
Appendix 407
3.1.2 RXYQ10PAY1~12PAY1
Item Name Symbol
Model
RXYQ10PAY1 RXYQ12PAY1
Compressor
Inverter
Type
M1C
JT1GCVDKYR@SB
OC protection
device
14.7A
STD 1
Type
M2C
JT170G-KYE@T
OC protection
device
15.0A
STD 2
Type
M3C
OC protection
device
Fan motor
OC protection
device
M1F 3A 1.15A
Electronic expansion valve (Main) Y1E Fully closed: 0pls Fully open: 480pls
Electronic expansion valve (Subcool) Y2E Fully closed: 0pls Fully open: 480pls
Pressure
protection
High pressure
switch
For M1C S1PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M2C S2PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M3C S3PH
Low pressure sensor SLNPL OFF: 0.07MPa
Temperature
protection
Discharge gas temperature
protection
(Discharge pipe thermistor)
R3T OFF: 135°C
Inverter fin temperature
protection
(Radiator fin thermistor)
R1T OFF: 93°C
Others Fuse
For main PC
board
A1P 250V, 15A
A2P 250V, 3A
For Noise filter
PC board
F1U 250V AC 5A Class B
+0
0.12
+0
0.12