Daikin FXSQ32MVE [288/458] Indoor unit malfunction of thermistor r2t for heat exchanger

Daikin RXYQ14P9W1B [288/458] Indoor unit malfunction of thermistor r2t for heat exchanger
Si34-803 Troubleshooting by Indication on the Remote Controller
Troubleshooting 277
3.11
C4
Indoor Unit: Malfunction of Thermistor (R2T) for
Heat Exchanger
Remote
Controller
Display
C4
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by heat exchanger thermistor.
Malfunction
Decision
Conditions
When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Defect of thermistor (R2T) for liquid pipe
Defect of indoor unit PC board
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P.427.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Remove the thermistor from
the indoor unit PC board, and
then insert it again.
Remove the thermistor from
the indoor unit PC board, and
then make resistance
measurement of the thermistor
using a multiple meter.
Normal (The malfunction is
caused by faulty contact.)
YES
NO
Replace the indoor unit PC board.
YES
Is the
thermistor normal?
Replace the thermistor (R2T).
NO
5 k to 90 k