Outline of Control (Indoor Unit) Si34-803
176 Function
(2) Heating operations
T1: Temperature detected by suction air thermistor Th1
T2: Temperature detected by liquid pipe temp. thermistor Th2
T3: Temperature detected by gas pipe temp. thermistor Th3
T4: Temperature detected by discharge air thermistor Th4
Tc : Outdoor unit condensing temperature
EV: Electronic expansion valve opening
Discharge
air
Refrigerant
Refrigerant
CPU
(From Outdoor unit)
T2
T1
T4
EV
Tc
Ts
Temp.
Setting
T4 < Ts?
Is EV possible
to open?
Is
EV possible to
close?
Calculate superheat degree.
If the discharge temperature
T4 is lower than the discharge
setting temperature Ts
Judge if the superheat degree
is not too small when the EV is
opened.
If yes,
EV is opened
If yes,
EV is closed.
Ye s
Ye s Ye s
No
NoNo
If the discharge temperature T4
is higher than the discharge
setting temperature Ts
Judge if the superheat degree
is not too large when the EV is
closed.
SC=Tc–T2
EV=EV+EV EV=EV–EV