Daikin FXSQ32MVE [160/458] Standby

Daikin FXDQ63NBVES [160/458] Standby
Si34-803 Special Control
Function 149
3.6 Standby
3.6.1 Restart Standby
Used to forcedly stop the compressor for a period of 3 minutes, in order to prevent the frequent ON/OFF of the
compressor and equalize the pressure within the refrigerant system.
* Actuators are based on RXYQ14~18P(A).
3.6.2 Crankcase Heater Control
In order to prevent the refrigerant from melting in the compressor oil in the stopped mode, this mode is used to control
the crankcase heater.
Actuator Operation
Compressor OFF
Outdoor unit fan
Ta>30°C: STEP4
Ta30°C: OFF
Four way valve Holds
Main motorized valve (EV1) 0 pls
Subcooling motorized (EV2) 0 pls
Hot gas bypass valve (SVP) OFF
Accumulator oil return valve (SVO) OFF
Injection (SVT) (RXYQ5P(A) model) OFF
Ending conditions 2 min.
Crankcase heater
OFF
Crankcase heater
ON
Discharge pipe
temperature < 70
˚C
Discharge pipe
temperature > 75
˚C