Daikin FXSQ32MVE [326/458] Troubleshooting 315

Daikin FXDQ40NAVE [326/458] Troubleshooting 315
Si34-803 Troubleshooting by Indication on the Remote Controller
Troubleshooting 315
Troubleshooting
Power ON
YES
YES
NO
NO
Is a difference
between high pressure
and low pressure prior
to startup
0.2MPa?
Does the malfunction
L9 recur?
It can take a maximum of 60 minutes
to determine the malfunction.
Faulty pressure
equalization:
Check the refrigerant
system.
End of measures:
Check the refrigerant
system.
Check of compressor:
Check the compressor
for abnormal sounds,
vibration, operating
conditions, and others
according to the
Compressor Diagnosis
Procedure.