Daikin FXSQ32MVE [340/458] Malfunction of transmission between indoor units

Daikin RXYQ18P9W1B [340/458] Malfunction of transmission between indoor units
Si34-803 Troubleshooting by Indication on the Remote Controller
Troubleshooting 329
3.48
U4
Malfunction of Transmission Between Indoor Units
Remote
Controller
Display
U4
Applicable
Models
All model of indoor unit
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor and outdoor units is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
Outdoor unit power supply is OFF
System address doesn’t match
Defect of indoor unit PC board
Defect of outdoor unit PC board

Содержание

Скачать