Si34-803 Wiring Diagrams for Reference
Appendix 387
RXYQ20PA / 22PA / 24PA / 26PA / 28PA / 30PA / 32PAY1
RXYQ20PA / 22PA / 24PA / 26PA / 28PA / 30PA / 32PAYL
POWER SUPPLY
MAIN
SWITCH
POWER SUPPLY
L
[UNIT 2]
N
MAIN
SWITCH
[UNIT 2]
[UNIT 1]
POWER SUPPLY
L2L3L1 N L2L3L1 N
MAIN
SWITCH
[UNIT 1]
SWITCH
FUSE
2 WIRES CABLE
(POWER LINE)
INDOOR UNITS
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(TRANSMISSION LINE)
OUTDOOR UNITS
INDOOR UNITS
2 WIRES CABLE
(TRANSMISSION LINE)
SWITCH
N
FUSE
L
SWITCH
N
FUSE
L
SWITCH
N
FUSE
L
SWITCH
N
FUSE
L
SWITCH
N
FUSE
L
SWITCH
N
FUSE
L
SWITCH
N
FUSE
L
SWITCH
FUSE
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
(TRANSMISSION LINE)
FUSE
SWITCH
N
L1 L2 L3
N
L1 L2 L3
2 WIRES CABLE
(TRANSMISSION LINE)
POWER SUPPLY
LN
MAIN
SWITCH
2 WIRES CABLE
(POWER LINE)
2 WIRES CABLE
(TRANSMISSION LINE)
SWITCH
N
FUSE
L
2 WIRES CABLE
(TRANSMISSION LINE)
OUTDOOR UNITS
2 WIRES CABLE
(TRANSMISSION LINE)
When the power source is connected in
series between the units.
When the power source is supplied to each
outdoor unit individually.
Notes 1) All wiring, components and materials to be procured on the site must comply with the
applicable local and national codes.
2) Use copper conductors only.
3) As for details, see wiring diagram.
4) Install circuit breaker for safety.
5) All field wiring and components must be provided by licensed electrician.
6) Unit shall be grounded in compliance with the applicable local and national codes.
7) Wiring shown are general points-of-connection guides only and are not intended for or to
include all details for a specific installation.
8) Be sure to install the switch and the fuse to the power line of each equipment.
9) Install the main switch that can interrupt all the power souces in an integrated manner because
this system consists of the equipment utilizing the multiple power sources.
10) The capacity of UNIT1 must be larger than UNIT2 when the power source is connected in
series between the units.
11) If there exists the possibility of reversed phase, lose phase, momentary blackout or the power
goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
2 WIRES CABLE
(TRANSMISSION LINE)
2 WIRES CABLE
(TRANSMISSION LINE)
N
L1 L2 L3
3D052261D