Daikin FXSQ32MVE [331/458] Outdoor unit malfunction of inverter radiating fin temperature rise sensor

Daikin FXSQ20MVE [331/458] Outdoor unit malfunction of inverter radiating fin temperature rise sensor
Troubleshooting by Indication on the Remote Controller Si34-803
320 Troubleshooting
3.42
P4
Outdoor Unit: Malfunction of Inverter Radiating Fin
Temperature Rise Sensor
Remote
Controller
Display
P4
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Resistance of radiation fin thermistor is detected when the compressor is not operating.
Malfunction
Decision
Conditions
When the resistance value of thermistor becomes a value equivalent to open or short circuited
status.
Malfunction is not decided while the unit operation is continued.
"P4" will be displayed by pressing the inspection button.
Supposed
Causes
Defect of radiator fin temperature sensor
Defect of inverter PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Power OFF
Power ON
Replace the
compressor.
Replace the fan motor
Replace the fan driver
PC board.
Replace the inverter
PC board.
End
YES
YES
YES
NO
NO
NO
Disconnect the cable from the
compressor, and then check
the compressor for the
insulation resistance.
Disconnect the cable from the
fan, and then check the fan
motor for the insulation
resistance.
Remove and insert the fin
thermistor connector [X111A].
The insulation
resistance is low (i.e., not more than
100k.)
The insulation
resistance is low (i.e., not more than
1M.)
Turn ON the
power supply, and then check
whether or not the malfunction
recurs.