Daikin FXSQ32MVE [281/458] Abnormal power supply voltage

Daikin FXDQ25PBNVT [281/458] Abnormal power supply voltage
Troubleshooting by Indication on the Remote Controller Si34-803
270 Troubleshooting
3.6 Abnormal Power Supply Voltage
Remote
Controller
Display
A8
Applicable
Models
FXMQ40~125P
Method of
Malfunction
Detection
Detect malfunction checking the input voltage of fan motor.
Malfunction
Decision
Conditions
When the input voltage of fan motor is 150V and below, or 386V and above.
Supposed
Causes
The possible causes are:
Power-supply voltage malfunction.
Connection defect on signal line.
Wiring defect.
Instantaneous blackout, others.
Troubleshooting
Check the condition of
the power source.
Check if power-supply
voltage is 220V - 240V
± 10%.
Check if there is power
open phase or faulty
wiring.
Check if power-supply
voltage side unbalance
is within 6V.
YES
There
are problems on
the condition of power
source described
above.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Correct any fault.
NO
NO
YES
"A8"
Reoccurrence
of malfunction.
Check and correct each wiring.
It is possible to have external
factor, such as brownout and
instantaneous blackout.