Si34-803 Troubleshooting by Remote Controller
Troubleshooting 255
Outdoor Unit L9 9 Inverter start up error 314
LA 9 Malfunction of power unit
LC 9 Malfunction of transmission between inverter and control PC board 316
P1 9 Inverter over-ripple protection 319
P4 9 Malfunction of inverter radiating fin temperature rise sensor 320
PJ 9 Faulty field setting after replacing main PC board or faulty combination of PC
board
322
System U0 8 Low pressure drop due to refrigerant shortage or electronic expansion valve
failure
323
U1 9 Reverse phase / open phase 324
U2 9 Power supply insufficient or instantaneous failure 325
U3 9 Check operation is not executed 328
U4 9 Malfunction of transmission between indoor units 329
U5 9 Malfunction of transmission between remote controller and indoor unit 331
U5 7 Failure of remote controller PC board or setting during control by remote
controller
331
U7 9 Malfunction of transmission between outdoor units 332
U8 9 Malfunction of transmission between main and sub remote controllers
(malfunction of sub remote controller)
334
U9 9 Malfunction of transmission between indoor and outdoor units in the same
system
335
UA 9 Improper combination of indoor and outdoor units, indoor units and remote
controller
336
UC 8 Address duplication of centralized controller 338
UE 9 Malfunction of transmission between centralized controller and indoor unit 339
UF 9 System is not set yet 342
UH 9 Malfunction of system, refrigerant system address undefined 343
Central
Remote
Controller
and
Schedule
Timer
M1 8 or 7 PC board defect 345
M8 8 or 7 Malfunction of transmission between optional controllers for centralized
control
346
MA 8 or 7 Improper combination of optional controllers for centralized control 348
MC 8 or 7 Address duplication, improper setting 350
Heat
Reclaim
Ventilation
64 8 Indoor unit’s air thermistor error
65 8 Outside air thermistor error
6A 8 Damper system alarm
6A 9 Damper system + thermistor error
6F 8 Malfunction of simple remote controller
6H 8 Malfunction of door switch or connector
94 9 Internal transmission error
8: ON 7: OFF 9: Blink
Malfunction
code
Operation
lamp
Malfunction contents Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.