Daikin FXSQ32MVE [420/458] Rxyq5 8payl ptl
![Daikin FXDQ50NBVET [420/458] Rxyq5 8payl ptl](/views2/1697648/page420/bg1a4.png)
Si34-803 List of Electrical and Functional Parts
Appendix 409
3.2 Outdoor Unit - 60Hz
3.2.1 RXYQ5 / 8PAYL, PTL
Item Name Symbol
Model
RXYQ5PAYL RXYQ8PAYL
Compressor
Inverter
Type
M1C
JT1GCVDKYR@SB
OC protection
device
14.7A
STD 1
Type
M2C —
OC protection
device
STD 2
Type
M3C —
OC protection
device
Fan motor
OC protection
device
M1F 1.15A 3A
Item Name Symbol
Model
RXYQ5PTL RXYQ8PTL
Compressor
Inverter
Type
M1C
JT100GCVDK@SB
OC protection
device
26.5A
STD 1
Type
M2C —
OC protection
device
STD 2
Type
M3C —
OC protection
device
Fan motor
OC protection
device
M1F 2.3A 5.5A
Electronic expansion valve (Main) Y1E Fully closed: 0pls Fully open: 480pls
Electronic expansion valve (Subcool) Y2E —
Fully closed: 0pls
Fully open: 480pls
Pressure
protection
High pressure
switch
For M1C S1PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M2C S2PH —
For M3C S3PH —
Low pressure sensor SLNPL OFF: 0.07MPa
Temperature
protection
Discharge gas temperature
protection
(Discharge pipe thermistor)
R3T OFF: 135°C
Inverter fin temperature
protection
(Radiator fin thermistor)
R1T OFF: 93°C
Others Fuse
For main PC
board
A1P 250V, 15A
A2P 250V, 3A (PTL : 250V, 15A)
For Noise filter
PC board
F1U
250V AC 6.3A Class B
(No fuse for TL model)
+0
−0.12
Содержание
- Basic control 12 p.2
- Function general 10 p.2
- Introduction vi p.2
- Functional parts layout 7 p.2
- Combination of outdoor units 4 model selection p.2
- Refrigerant circuit 8 p.2
- Part 4 function 09 p.2
- Part 2 specifications 1 p.2
- Part 1 general information p.2
- Model names of indoor outdoor units 2 external appearance p.2
- Table of contents p.2
- Specifications 2 p.2
- Refrigerant flow for each operation mode 2 p.2
- Part 3 refrigerant circuit 7 p.2
- R 410a heat pump 50hz 60hz p.2
- Part 6 troubleshooting 39 p.3
- Symptom based troubleshooting 42 2 troubleshooting by remote controller 45 p.3
- Test operation 80 p.3
- Outdoor unit pc board layout 96 3 field setting 97 p.3
- Protection control 52 p.3
- Part 5 test operation 79 p.3
- Other control 57 p.3
- Special control 43 p.3
- Outline of control indoor unit 65 p.3
- Troubleshooting by indication on the remote controller 60 p.4
- Wiring diagrams for reference 75 p.5
- Troubleshooting op unified on off controller 53 p.5
- Troubleshooting op central remote controller 45 p.5
- Piping diagrams 64 p.5
- Part 7 appendix 63 p.5
- Drawings flow charts iii p.6
- Example of connection r 410a type 25 7 thermistor resistance temperature characteristics 27 8 pressure sensor 29 9 method of checking the inverter s power transistors and diode modules 30 p.6
- Precautions for new refrigerant r 410a 34 p.6
- Piping installation point 23 p.6
- Part 8 precautions for new refrigerant r 410a 33 p.6
- Option list 19 p.6
- List of electrical and functional parts 06 p.6
- Index i p.6
- Caution in repair p.7
- Warning p.7
- Safety cautions p.7
- Introduction p.7
- Warning p.8
- Cautions regarding products after repair p.8
- Caution p.8
- Inspection after repair p.9
- Warning p.9
- Caution p.9
- Using icons list p.10
- Using icons p.10
- Icons are used to attract the attention of the reader to specific information the meaning of each icon is described in the table below p.10
- Caution p.10
- Preface p.11
- Part 1 general information p.12
- Note fxdq has following 2 series as show below fxdq pb nbvet without drain pump fxdq pb nbve with drain pump bev unit is required for each indoor unit ma rohs directive models specifications dimensions and other functions are not changed compared with m type p.13
- Model names of indoor outdoor units p.13
- Indoor units p.13
- E the unit with anti corrosion treatment p.13
- Outdoor units normal series p.13
- Model names of indoor outdoor units si34 803 p.13
- High cop series energy saving series p.13
- Heat pump rxyq 5p a 8p a 10p a 12p a 14p a 16p a 18p a 20p a 22p a y1 e yl e tl e 24p a 26p a 28p a 30p a 32p a 34p a 36p a 38p a 40p a 42p a 44p a 46p a 48p a 50p a 52p a 54p a p.13
- Heat pump rxyq p.13
- General information p.13
- Y1 e yl e tl e p.13
- Series model name power supply p.13
- Power supply ve 1 phase 220 240v 50hz v1 1 phase 220 240v 50hz y1 3 phase 380 415v 50hz yl 3 phase 380v 60hz tl 3 phase 220v 60hz p.13
- Indoor units p.14
- General information 3 p.14
- Floor standing type p.14
- External appearance p.14
- Concealed floor standing type p.14
- Ceiling suspended type p.14
- Ceiling suspended cassette type connection unit series p.14
- Ceiling mounted duct type middle and high static pressure p.14
- Ceiling mounted duct type p.14
- Ceiling mounted cassette type round flow p.14
- Ceiling mounted cassette type double flow p.14
- Ceiling mounted cassette corner type p.14
- Ceiling mounted built in type p.14
- Wall mounted type p.14
- Slim ceiling mounted duct type p.14
- Si34 803 external appearance p.14
- Rxyq12p a 14p a 16p a 18p a p.15
- Rxyq5p a rxyq8p a 10p a p.15
- Rxyq38p a 40p a 42p a 44p a 46p a rxyq48p a 50p a 52p a 54p a p.15
- Rxyq20p a 22p a 24p a 26p a 28p a rxyq30p a 32p a 34p a 36p a p.15
- Outdoor units p.15
- Normal series space saving series p.15
- High cop series energy saving series p.16
- Combination of outdoor units p.17
- Model selection si34 803 p.19
- Outdoor units normal type space saving type p.19
- Model selection p.19
- High cop type energy saving type p.19
- General information p.19
- Vrv iii heat pump series p.19
- Use the above tables to determine the capacities of indoor units to be connected make sure the total capacity of indoor units connected to each outdoor unit is within the specified value kw the total capacity of connected indoor units must be within a range of 50 to 130 of the rated capacity of the outdoor unit in some models it is not possible to connect the maximum number of connectable indoor units select models so the total capacity of connected indoor units conforms to the specification p.20
- Si34 803 model selection p.20
- Note fxdq has following 2 series as show below fxdq pb nbvet without drain pump fxdq pb nbve with drain pump bev unit is required for each indoor unit p.20
- New refrigerant model code p20 type p25 type p32 type p40 type p50 type p63 type p80 type p100 type p125 type p200 type p250 type selecting model capacity 2 kw 2 kw 3 kw 4 kw 5 kw 7 kw 9 kw 11 kw 14 kw 22 kw 28 kw equivalent output 0 hp 1hp p.20
- Indoor unit capacity p.20
- Hp 2 hp 2 hp 3 hp 4hp 5hp 8hp 10hp p.20
- General information 9 p.20
- Connectable indoor unit p.20
- Differences from conventional models p.21
- Part 2 specifications p.22
- Specifications 2 p.22
- Outdoor unit s p.23
- Specifications si34 803 p.23
- Specifications p.23
- Si34 803 specifications p.24
- Specifications 13 p.24
- Specifications si34 803 p.25
- Specifications p.25
- Specifications 15 p.26
- Si34 803 specifications p.26
- Specifications p.27
- Specifications si34 803 p.27
- Specifications 17 p.28
- Si34 803 specifications p.28
- Specifications si34 803 p.29
- Specifications p.29
- Specifications 19 p.30
- Si34 803 specifications p.30
- Specifications si34 803 p.31
- Specifications p.31
- Si34 803 specifications p.32
- Specifications 21 p.32
- Specifications si34 803 p.33
- Specifications p.33
- Specifications 23 p.34
- Si34 803 specifications p.34
- Specifications si34 803 p.35
- Specifications p.35
- Specifications 25 p.36
- Si34 803 specifications p.36
- Specifications si34 803 p.37
- Specifications p.37
- Specifications 27 p.38
- Si34 803 specifications p.38
- Specifications si34 803 p.39
- Specifications p.39
- Si34 803 specifications p.40
- Specifications 29 p.40
- Specifications si34 803 p.41
- Specifications p.41
- Specifications 31 p.42
- Si34 803 specifications p.42
- Specifications si34 803 p.43
- Specifications p.43
- Specifications 33 p.44
- Si34 803 specifications p.44
- Heating capacity p.44
- Cooling capacity 19 cwb p.44
- Specifications si34 803 p.45
- Specifications p.45
- Heating capacity p.45
- Cooling capacity 19 cwb p.45
- Cooling capacity 19 cwb p.46
- Specifications 35 p.46
- Si34 803 specifications p.46
- Heating capacity p.46
- Specifications si34 803 p.47
- Specifications p.47
- Heating capacity p.47
- Cooling capacity 19 cwb p.47
- Specifications 37 p.48
- Si34 803 specifications p.48
- Heating capacity p.48
- Cooling capacity 19 cwb p.48
- Specifications si34 803 p.49
- Specifications p.49
- Heating capacity p.49
- Cooling capacity 19 cwb p.49
- Cooling capacity 19 cwb p.50
- Specifications 39 p.50
- Si34 803 specifications p.50
- Heating capacity p.50
- Specifications si34 803 p.51
- Specifications p.51
- Heating capacity p.51
- Cooling capacity 19 cwb p.51
- Specifications 41 p.52
- Si34 803 specifications p.52
- Heating capacity p.52
- Cooling capacity 19 cwb p.52
- Specifications si34 803 p.53
- Specifications p.53
- Heating capacity p.53
- Cooling capacity 19 cwb p.53
- Cooling capacity 19 cwb p.54
- Specifications 43 p.54
- Si34 803 specifications p.54
- Heating capacity p.54
- Specifications si34 803 p.55
- Specifications p.55
- Heating capacity p.55
- Cooling capacity 19 cwb p.55
- Specifications 45 p.56
- Si34 803 specifications p.56
- Heating capacity p.56
- Cooling capacity 19 cwb p.56
- Specifications si34 803 p.57
- Specifications p.57
- Specifications 47 p.58
- Si34 803 specifications p.58
- Specifications p.59
- Specifications si34 803 p.59
- Specifications 49 p.60
- Si34 803 specifications p.60
- Specifications si34 803 p.61
- Specifications p.61
- Specifications 51 p.62
- Si34 803 specifications p.62
- Specifications si34 803 p.63
- Specifications p.63
- Specifications 53 p.64
- Si34 803 specifications p.64
- Indoor units p.65
- Ceiling mounted cassette round flow type p.65
- Si34 803 specifications p.66
- Ceiling mounted cassette round flow type p.66
- Bycp125k w1 bycp125k w1 bycp125k w1 bycp125k w1 p.66
- Specifications 55 p.66
- Specifications si34 803 p.67
- Specifications p.67
- Ceiling mounted cassette type double flow p.67
- Bybc32g w1 bybc32g w1 bybc32g w1 bybc50g w1 p.67
- Specifications 57 p.68
- Si34 803 specifications p.68
- Ceiling mounted cassette type double flow p.68
- Bybc50g w1 bybc63g w1 bybc125g w1 bybc125g w1 p.68
- Specifications si34 803 p.69
- Specifications p.69
- Ceiling mounted cassette corner type p.69
- Byk45fjw1 byk45fjw1 byk45fjw1 byk71fjw1 p.69
- Specifications 59 p.70
- Slim ceiling mounted duct type ve with drain pump vet without drain pump p.70
- Si34 803 specifications p.70
- Specifications si34 803 p.71
- Specifications p.71
- Slim ceiling mounted duct type ve with drain pump vet without drain pump p.71
- Specifications 61 p.72
- Si34 803 specifications p.72
- Ceiling mounted built in type p.72
- Bybs32djw1 bybs32djw1 bybs32djw1 p.72
- Specifications si34 803 p.73
- Specifications p.73
- Ceiling mounted built in type p.73
- Bybs45djw1 bybs45djw1 bybs71djw1 p.73
- Specifications 63 p.74
- Si34 803 specifications p.74
- Ceiling mounted built in type p.74
- Bybs125djw1 bybs125djw1 bybs125djw1 p.74
- Ceiling mounted duct type p.75
- Specifications si34 803 p.75
- Specifications p.75
- Specifications 65 p.76
- Si34 803 specifications p.76
- Ceiling mounted duct type p.76
- Specifications si34 803 p.77
- Specifications p.77
- Ceiling mounted duct type p.77
- Specifications 67 p.78
- Si34 803 specifications p.78
- Ceiling suspended type p.78
- Wall mounted type p.79
- Specifications si34 803 p.79
- Specifications p.79
- Specifications 69 p.80
- Si34 803 specifications p.80
- Wall mounted type p.80
- Specifications si34 803 p.81
- Specifications p.81
- Floor standing type p.81
- Specifications 71 p.82
- Si34 803 specifications p.82
- Floor standing type p.82
- Specifications si34 803 p.83
- Specifications p.83
- Concealed floor standing type p.83
- Specifications 73 p.84
- Si34 803 specifications p.84
- Concealed floor standing type p.84
- Connection unit p.85
- Ceiling suspended cassette type p.85
- Bev units p.85
- Suction gas pipes p.85
- Specifications si34 803 p.85
- Specifications p.85
- Liquid pipes p.85
- Indoor unit p.85
- Outdoor air processing unit p.86
- Specifications 75 p.86
- Si34 803 specifications p.86
- Refrigerant flow for each operation mode 2 p.88
- Refrigerant circuit 8 p.88
- Part 3 refrigerant circuit p.88
- Functional parts layout 7 p.88
- Rxyq5p a p.89
- Refrigerant circuit si34 803 p.89
- Refrigerant circuit p.89
- Refirgerant circuit p.89
- Si34 803 refrigerant circuit p.90
- Rxyq5p a p.90
- Refirgerant circuit 79 p.90
- Rxyq8p a p.91
- Refrigerant circuit si34 803 p.91
- Refirgerant circuit p.91
- Si34 803 refrigerant circuit p.92
- Rxyq8p a p.92
- Refirgerant circuit 81 p.92
- Rxyq10p a 12p a p.93
- Refrigerant circuit si34 803 p.93
- Refirgerant circuit p.93
- Si34 803 refrigerant circuit p.94
- Rxyq10p a 12p a p.94
- Refirgerant circuit 83 p.94
- Refirgerant circuit p.95
- Rxyq14p a 16p a 18p a p.95
- Refrigerant circuit si34 803 p.95
- Si34 803 refrigerant circuit p.96
- Rxyq14p a 16p a 18p a p.96
- Refirgerant circuit 85 p.96
- Thermistor p.97
- Refrigerant system p.97
- Outdoor air processing unit fxmq125mfv1 250mfv1 p.97
- Main control equipment p.97
- Si34 803 functional parts layout p.98
- Rxyq5p a p.98
- Refirgerant circuit 87 p.98
- Functional parts layout p.98
- Front view p.98
- Functional parts layout si34 803 p.99
- Front view p.99
- Rxyq8p a p.99
- Refirgerant circuit p.99
- Si34 803 functional parts layout p.100
- Rxyq10p a p.100
- Refirgerant circuit 89 p.100
- Heat exchanger p.100
- Front view p.100
- Accumulator p.100
- Rxyq12p a p.101
- Refirgerant circuit p.101
- Heat exchanger p.101
- Functional parts layout si34 803 p.101
- Front view p.101
- Accumulator p.101
- Front view p.102
- Accumulator p.102
- Si34 803 functional parts layout p.102
- Rxyq14p a 16p a 18p a p.102
- Refirgerant circuit 91 p.102
- Heat exchanger p.102
- Rxyq5p a cooling operation p.103
- Refrigerant flow for each operation mode si34 803 p.103
- Refrigerant flow for each operation mode p.103
- Refirgerant circuit p.103
- Si34 803 refrigerant flow for each operation mode p.104
- Refirgerant circuit 93 p.104
- Cooling oil return operation p.104
- Refrigerant flow for each operation mode si34 803 p.105
- Refirgerant circuit p.105
- Heating oil return defrost operation p.105
- Refirgerant circuit 95 p.106
- Heating operation p.106
- Si34 803 refrigerant flow for each operation mode p.106
- Rxyq8p a cooling operation p.107
- Refrigerant flow for each operation mode si34 803 p.107
- Refirgerant circuit p.107
- Si34 803 refrigerant flow for each operation mode p.108
- Refirgerant circuit 97 p.108
- Cooling oil return operation p.108
- Refrigerant flow for each operation mode si34 803 p.109
- Refirgerant circuit p.109
- Heating oil return defrost operation p.109
- Si34 803 refrigerant flow for each operation mode p.110
- Refirgerant circuit 99 p.110
- Heating operation p.110
- Rxyq10p a 12p a cooling operation p.111
- Refrigerant flow for each operation mode si34 803 p.111
- Refirgerant circuit p.111
- Si34 803 refrigerant flow for each operation mode p.112
- Refirgerant circuit 101 p.112
- Cooling oil return operation p.112
- Refrigerant flow for each operation mode si34 803 p.113
- Refirgerant circuit p.113
- Heating oil return defrost operation p.113
- Si34 803 refrigerant flow for each operation mode p.114
- Refirgerant circuit 103 p.114
- Heating operation p.114
- Rxyq14p a 16p a 18p a cooling operation p.115
- Refrigerant flow for each operation mode si34 803 p.115
- Refirgerant circuit p.115
- Si34 803 refrigerant flow for each operation mode p.116
- Refirgerant circuit 105 p.116
- Cooling oil return operation p.116
- Heating oil return defrost operation p.117
- Refrigerant flow for each operation mode si34 803 p.117
- Refirgerant circuit p.117
- Si34 803 refrigerant flow for each operation mode p.118
- Refirgerant circuit 107 p.118
- Heating operation p.118
- Special control 43 p.120
- Protection control 52 p.120
- Part 4 function p.120
- Outline of control indoor unit 65 p.120
- Other control 57 p.120
- Function general 10 p.120
- Basic control 12 p.120
- Symbol p.121
- Function general p.121
- In the event indoor unit stops or the thermostat turns off while in oil return operation or defrosting operation pump down residual operation is performed on completion of the oil return operation or defrosting operation p.122
- Function 111 p.122
- Si34 803 function general p.122
- Operation mode p.122
- Malfunction standby retry p.122
- Normal operation p.123
- List of functions in normal operation p.123
- Basic control p.123
- 1 pi control evaporator outlet superheated degree sh constant 2 pi control condenser outlet subcooled degree sc constant 1 and 2 refer 6 electronic expansion valve control on page 171 p.123
- Heating operation p.124
- Cooling operation p.124
- Compressor pi control p.124
- Carries out the compressor capacity pi control to maintain te at constant during cooling operation and tc at constant during heating operation to ensure stable unit performance p.124
- Operating priority and rotation of compressors for multi standard connection system p.125
- Function p.125
- Basic control si34 803 p.125
- In the case of combination of 3 outdoor units the above diagram shows master unit slave unit 1 and slave unit 2 from left to right compressors may operate in any pattern other than those mentioned above according to the operating status p.126
- Function 115 p.126
- Si34 803 basic control p.126
- Rxyq46p a 48p a 10hp 1fan 12hp 2fan p.126
- No 3 no 6 no 9 p.126
- No 2 no 5 no 8 p.126
- No 1 no 4 no 7 p.126
- Inv std1 std2 p.126
- Rxyq8pay1 p.127
- Rxyq5pay1 p.127
- Rxyq18pay1 p.127
- Rxyq14pay1 16pay1 p.127
- Rxyq10pay1 12pay1 p.127
- Notes 1 inv inverter compressor std1 standard compressor 1 std2 standard compressor 2 2 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.127
- Hz stand alone installation p.127
- Function p.127
- Compressor step control multi outdoor unit connection is available on the standard connection system compressor operations vary with the following steps according to information in 2 compressor pi control furthermore the operating priority of compressors is subject to information in operating priority and rotation of compressors p.127
- Basic control si34 803 p.127
- Two unit multi system p.128
- Si34 803 basic control p.128
- Rxyq22pay1 10 12hp p.128
- Rxyq20pay1 8 12hp p.128
- Represents the range in which hz is not stepped up p.128
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.128
- Function 117 p.128
- Rxyq26pay1 8 18hp p.129
- Rxyq24pay1 8 16hp p.129
- Represents the range in which hz is not stepped up p.129
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.129
- Function p.129
- Basic control si34 803 p.129
- Represents the range in which hz is not stepped up p.130
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.130
- Function 119 p.130
- Si34 803 basic control p.130
- Rxyq28pay1 30pay1 10 12 18hp p.130
- Rxyq 32pay1 16 16hp p.130
- Rxyq36pay1 18 18hp p.131
- Rxyq 34pay1 16 18hp p.131
- Represents the range in which hz is not stepped up p.131
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.131
- Function p.131
- Basic control si34 803 p.131
- Three unit multi system p.132
- Si34 803 basic control p.132
- Rxyq38pay1 8 12 18hp p.132
- Rxyq 40pay1 8 16 16hp p.132
- Represents the range in which hz is not stepped up p.132
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.132
- Function 121 p.132
- Rxyq44pay1 8 18 18hp p.133
- Rxyq 42pay1 8 16 18hp p.133
- Represents the range in which hz is not stepped up p.133
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.133
- Function p.133
- Basic control si34 803 p.133
- Si34 803 basic control p.134
- Rxyq50pay1 52pay1 14 16 18 18hp p.134
- Rxyq46pay1 48pay1 10 12 18 18hp p.134
- Represents the range in which hz is not stepped up p.134
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.134
- Function 123 p.134
- Rxyq54pay1 18 18 18hp p.135
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.135
- Function p.135
- Basic control si34 803 p.135
- Si34 803 basic control p.136
- Rxyq18payl ptl p.136
- Rxyq14 16payl ptl p.136
- Rxyq10 12payl ptl p.136
- Notes 1 inv inverter compressor std1 standard compressor 1 std2 standard compressor 2 2 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.136
- Hz stand alone installation p.136
- Function 125 p.136
- Two unit multi system p.137
- Rxyq22payl ptl 10 12hp p.137
- Represents the range in which hz is not stepped up rxyq20payl ptl 8 12hp p.137
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.137
- Function p.137
- Basic control si34 803 p.137
- Represents the range in which hz is not stepped up p.138
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.138
- Function 127 p.138
- Si34 803 basic control p.138
- Rxyq26payl ptl 8 18hp p.138
- Rxyq24payl ptl 8 16hp p.138
- Rxyq32payl ptl 16 16hp p.139
- Rxyq28 30payl ptl 10 12 18hp p.139
- Represents the range in which hz is not stepped up p.139
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.139
- Function p.139
- Basic control si34 803 p.139
- Si34 803 basic control p.140
- Rxyq36payl ptl 18 18hp p.140
- Rxyq34payl ptl 16 18hp p.140
- Represents the range in which hz is not stepped up p.140
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.140
- Function 129 p.140
- Basic control si34 803 p.141
- Rxyq40payl ptl 8 16 16hp p.141
- Rxyq38payl ptl 8 12 18hp p.141
- Represents the range in which hz is not stepped up p.141
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.141
- Function p.141
- Si34 803 basic control p.142
- Rxyq44payl ptl 8 18 18hp p.142
- Rxyq42payl ptl 8 16 18hp p.142
- Represents the range in which hz is not stepped up p.142
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.142
- Function 131 p.142
- Rxyq50 52payl ptl 14 16 18 18hp p.143
- Rxyq46 48payl ptl 10 12 18 18hp p.143
- Represents the range in which hz is not stepped up p.143
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.143
- Function p.143
- Basic control si34 803 p.143
- Si34 803 basic control p.144
- Rxyq54payl ptl 18 18 18hp p.144
- Notes 1 inv inverter compressor std standard compressor figures after on represent the number of std compressors in operation 2 master unit and slave unit in this section are the names for control and they will be transferred according to the priority of rotation system 3 depending on the operating conditions of compressors the compressors may run in patterns other than those aforementioned p.144
- Function 133 p.144
- Hz 60hz high cop type p.145
- Used to control the revolutions of outdoor unit fans in the steps listed in table below according to condition changes p.152
- The optimum initial value of the evaporator outlet superheated degree is 5 c but varies depending on the discharge pipe superheated degree of inverter compressor p.152
- Subcooling motorized valve ev2 control p.152
- Step control of outdoor unit fans p.152
- Makes pi control of the motorized valve y2e to keep the superheated degree of the outlet gas pipe on the evaporator side for the full use of the subcooling heat exchanger p.152
- Main motorized valve ev1 control p.152
- Figures listed above are all those controlled while in standard mode which vary when the system is set to high static pressure or capacity precedence mode p.152
- Electronic expansion valve pi control p.152
- Carries out the motorized valve y1e pi control to maintain the evaporator outlet superheated degree sh at constant during heating operation to make maximum use of the outdoor unit heat exchanger evaporator p.152
- Outdoor unit fan control in cooling operation p.153
- While in cooling operation if the outdoor temperature is low this mode provides high pressure control using the outdoor unit fan to retain appropriate liquid pressure thus ensuring refrigerant circulation rate to be supplied to indoor units p.153
- This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the compressor thus reducing startup loads furthermore the inverter is turned on to charge the capacitor in addition to avoid stresses to the compressor due to oil return or else after the startup the following control is made and the position of the four way valve is also determined to position the four way valve the master and slave units simultaneously start up p.154
- Startup control in heating operation p.154
- Startup control in cooling operation p.154
- Startup control p.154
- Special control p.154
- Start up std compressors at intervals of 15 seconds p.155
- Large capacity start up control heating p.155
- Start conditions referring to the set conditions for the following items start the oil return operation in cooling cumulative oil feed rate timer setting make this setting so as to start the oil return operation when the initial cumulative operating time reaches two hours after power supply is turned on and then every eight hours furthermore the cumulative oil feed rate is computed from tc te and compressor loads p.156
- Oil return operation in cooling operation p.156
- Oil return operation p.156
- In the case of multi outdoor unit system master unit performs the operations listed in the table above slave units operating units perform the operations listed in the table above non operating units perform the operations listed in the table above from the oil return operation non operating unit stops during oil return preparation operation actuators are based on rxyq14 18p a p.156
- In order to prevent the compressor from running out of oil the oil return operation is conducted to recover oil flown out from the compressor to the system side p.156
- Oil return operation in heating operation p.157
- In the case of multi outdoor unit system master unit performs the operations listed in the table above slave units operating units perform the operations listed in the table above non operating units perform the operations listed in the table above from the oil return operation non operating unit stops during oil return preparation operation actuators are based on rxyq1 p.157
- Defrosting operation p.158
- To defrost the outdoor unit heat exchanger while in evaporator the defrost operation is conducted to recover the heating capacity start conditions referring to the set conditions for the following items start the defrosting operation heat transfer coefficient of the outdoor unit heat exchanger heat exchange temperature tb timer set to two hours at minimum furthermore the heat transfer coefficient of the outdoor unit evaporator is computed from tc te and compressor loads p.158
- In the case of multi outdoor unit system master unit performs the operations listed in the table above slave units operating units perform the operations listed in the table above non operating units perform the operations listed in the table above from the defrost operation non operating unit stops during defrost preparation operation actuators are based on rxyq14 18p a p.158
- Pump down residual operation in heating operation p.159
- Pump down residual operation in cooling operation p.159
- Pump down residual operation p.159
- If the liquid refrigerant stays in the evaporator at the startup of a compressor this liquid refrigerant enters the compressor thus resulting in diluted oil in the compressor and then degraded lubrication performance consequently in order to recover the refrigerant in the evaporator while the compressor stops the pump down residual operation is conducted p.159
- Actuators are based on rxyq14 18p a p.159
- Used to forcedly stop the compressor for a period of 3 minutes in order to prevent the frequent on off of the compressor and equalize the pressure within the refrigerant system p.160
- Standby p.160
- Restart standby p.160
- In order to prevent the refrigerant from melting in the compressor oil in the stopped mode this mode is used to control the crankcase heater p.160
- Crankcase heater control p.160
- Actuators are based on rxyq14 18p a p.160
- Stop due to malfunction p.161
- In order to protect compressors if any of the following items has an abnormal value the system will make stop with thermostat off and the malfunction will be determined according to the number of retry times p.161
- Actuators are based on rxyq14 18p a p.161
- When system is in stop mode normal operation stop p.161
- This mode is used to define actuator operations when the system stops p.161
- Stopping operation p.161
- While the master unit is in operation this mode is used to set the refrigerant flow rate to a required level using a slave unit in the stopped mode in cooling operation same as that of normal operation stop p.162
- Stopping operation of slave units during master unit is in operation with multi outdoor unit system p.162
- In heating operation the system operates with following mode p.162
- This high pressure protection control is used to prevent the activation of protection devices due to abnormal increase of high pressure and to protect compressors against the transient increase of high pressure p.163
- Protection control si34 803 p.163
- Protection control p.163
- In heating operation in the case of multi outdoor unit system the entire system performs this control in the following sequence p.163
- In cooling operation in the case of multi outdoor unit system each outdoor unit performs this control individually in the following sequence p.163
- High pressure protection control p.163
- Function p.163
- In cooling operation in the case of multi outdoor unit system the entire system performs this control in the following sequence p.164
- Hot gas svp on p.164
- Hot gas svp off p.164
- This low pressure protection control is used to protect compressors against the transient decrease of low pressure p.164
- Master unit 52 hz off off p.164
- Low pressure protection control p.164
- In heating operation in the case of multi outdoor unit system each outdoor unit performs this control individually in the following sequence p.164
- After 10 min p.165
- This discharge pipe protection control is used to protect the compressor internal temperature against a malfunction or transient increase of discharge pipe temperature p.165
- Te and suction superheated degree p.165
- Std compressor p.165
- Protection control not limited p.165
- Inv compressor p.165
- Htds value of std compressor discharge pipe temperature tds compensated with outdoor air temperature tp value of compressor port temperature calculated by t p.165
- Each compressor performs the discharge pipe temperature protection control individually in the following sequence p.165
- Discharge pipe temp p.165
- Discharge pipe protection control p.165
- Applicable std compressor stops p.165
- Inverter fin temperature control p.166
- A y1 yl 26 a tl p.166
- Y1 yl 26 a tl p.166
- When occurring 4 times within 60 min the malfunction code l4 is output p.166
- Under fin temperature protection control p.166
- Tfin 81 c inv upper limit rps max p.166
- Nomal operation p.166
- Inverter protection control p.166
- Inverter overcurrent protection control p.166
- Inverter fin temp 81 c continues for 3 min or more p.166
- Inverter current protection control and inverter fin temperature control are performed to prevent tripping due to a malfunction or transient inverter overcurrent and fin temperature increase p.166
- Inverter current 14 a y1 yl 26 a tl inv upper limit frequency max p.166
- In the case of multi outdoor unit system each inv compressor performs these controls in the following sequence p.166
- Fin temp standby p.166
- Std compressor overload protection p.167
- Injection control only for rxyq5p a p.167
- For transitional rise in discharge pipe temperature have the liquid refrigerant flow into the suction side to reduce the discharge pipe temperature for the compressor protection p.167
- This control is used to prevent abnormal heating due to overcurrent to the compressor resulting from failures of std compressor such as locking p.167
- Timing of outdoor unit rotation p.168
- Outdoor unit rotation p.168
- Other control p.168
- In the case of multi outdoor unit system this outdoor unit rotation is used to prevent the compressor from burning out due to unbalanced oil level between outdoor units p.168
- Example the following diagram shows outdoor unit rotation in combination of 3 outdoor units in heating in cooling p.168
- Details of outdoor unit rotation in the case of multi outdoor unit system each outdoor unit is given an operating priority for the control outdoor unit rotation makes it possible to change the operating priority of outdoor units thus the system becomes free of compressors that stop over an extended period of time at the time of partial loading preventing unbalanced oil level p.168
- After oil return operation after defrosting operation at the beginning of the starting control when any of outdoor unit stops for a period of 20 minutes or more in heating there are outdoor units that stop operation in cooling low pressure of all outdoor units in operation is less than 0 5 mpa in cooling p.168
- Restrictions for emergency operation p.169
- Emergency operation p.169
- Caution in order to disable the compressor operation due to a failure or else be sure to do so in emergency operation mode never attempt to disconnect power supply wires from magnetic contactors or else doing so will operate compressors in combination that disables oil equalization between the compressors thus resulting in malfunctions of other normal compressors p.169
- In the case of multi outdoor unit system rxyq20p a to 54p a p.170
- In the case of 1 outdoor unit system rxyq8p a to 18p a p.170
- Note in order to forcedly clear the automatic backup operation reset the power supply with the outdoor unit in the stopped state p.171
- 777777 77 p.173
- 777777 p.173
- 7777777 7777 p.173
- In order to save the power consumption the capacity of outdoor unit is saved with control forcibly by using demand 1 setting or demand 2 setting to operate the unit with this mode additional setting of continuous demand setting or external input by external control adapter is required p.175
- Heating operation prohibition p.175
- Heating operation is prohibited above 24 c ambient temperature p.175
- Demand operation p.175
- Outline of control indoor unit p.176
- Drain pump control p.176
- Louver control for preventing ceiling dirt p.178
- Thermostat sensor in remote controller p.179
- Cooling p.179
- Heating p.180
- Thermostat control in dry operation p.181
- Outline of control indoor unit si34 803 p.181
- Furthermore while in dry operation mode fans operate at l flow rate stops for a period of six minutes while the thermostat is off and then return to operation at l flow rate this control is used to prevent a rise in indoor humidity while in thermostat off mode p.181
- Function p.181
- Assuming that the suction air temperature at the time of starting the dry operation is tro and the suction air temperature in operation is tr p.181
- While in dry operation the thermostat control is conducted according to a suction temperature at the time of starting the dry operation p.181
- While in a single remote controller group control the body thermostat is only used fro this control furthermore while in heating operation cassette mounted indoor units conduct the thermostat control by a value compensated by 2 c for the value detected with the body thermostat through field settings the thermostat differential setting can be changed from 1 c to 0 c for details on the changing procedure refer to information on page onward p.181
- Vrv multi systems are set at factory to thermostat control mode using the remote controller while in normal thermostat differential control mode i e factory set mode the thermostat turns off when the system reaches a temperature of 1 c from the set temperature while in cooling operation or of 1 c from that while in heating operation p.181
- Thermostat control while in normal operation p.181
- Remote controller setting p.182
- Po horizontal p.182
- Normal control p.182
- Lapse of 3 minutes p.182
- Hot start ending conditions p.182
- Hot start control in heating operation only p.182
- Hot start control hot start in progress p.182
- H l remote controller setting p.182
- Fan louver p.182
- Electronic expansion valve control p.182
- Defrost ending or oil return ending or thermostat on p.182
- Freeze prevention p.183
- Heater control p.183
- Freeze prevention by off cycle indoor unit p.183
- Swing flaps operate as shown in table below p.184
- Residual operation time 100 seconds on ceiling suspended type or 60 seconds on other types p.184
- List of swing flap operations p.184
- Fan residual operation while the heater turns off in order to prevent the activation of the thermal protector the fan conducts residual operation for a given period of time after the heater turns off this operation is conducted regardless of with or without heater equipped p.184
- 2 the heater control on off is conducted by converting the heater temperature into the condensing pressure equivalent saturated temperature tc according to the temperature detection through the high pressure sensor sinph of the outdoor unit p.184
- 1 l or ll only on fxfq models p.184
- To select cooling heating or fan operation mode according to the suction air outdoor air temperature p.185
- Selection of operation mode by suction air thermostat p.185
- Outdoor air processing unit p.185
- Objective p.185
- Details p.185
- Control of outdoor air processing unit unique control for outdoor air processing unit p.185
- Sh t3 t2 p.186
- Discharge air temperature control p.186
- Discharge air p.186
- Temp setting p.186
- Refrigerant p.186
- Is ev possible to open p.186
- Is ev possible to close p.186
- Ev ev ev ev ev ev p.186
- Yes yes p.187
- Temp setting p.187
- Sc tc t2 p.187
- Refrigerant p.187
- Is ev possible to open p.187
- Is ev possible to close p.187
- Ev ev ev ev ev ev p.187
- Discharge air p.187
- Low outdoor air temperature protection control p.188
- Details p.188
- Objective p.188
- Test operation 80 p.190
- Part 5 test operation p.190
- Outdoor unit pc board layout 96 3 field setting 97 p.190
- Test operation p.191
- Installation process p.191
- Procedure and outline p.192
- Check work prior to turn power supply on p.192
- Make field settings with outdoor unit pc board p.193
- Make field settings if needed for the setting procedure refer to information in 3 field setting from outdoor unit on page 214 onward for the outdoor multi system make field settings with the master unit field settings made with the slave unit will be all invalid p.193
- Conduct check operations p.193
- Check to be sure the transmission is normal the transmission is normal if the leds display conditions as shown in table below p.193
- Check the led display of the outdoor unit pc board p.193
- Check for normal operation p.193
- Before starting the normal operation after the completion of check operations make sure indoor and outdoor units normally operate p.193
- Be sure to turn the power on 6 hours before starting operation to protect compressors to power on clankcase heater p.193
- Turn power on p.193
- Turn outdoor unit and indoor unit power on p.193
- The master unit is the outdoor unit to which the transmission wiring for the indoor units is conncted the other outdoor units are slave units p.193
- The check operations shown below will be automatically initiated check for erroneous wirings check for failure to open stop valves check for excessive refrigerant refilling automatic judgment of piping length p.193
- Test operation si34 803 p.193
- Test operation p.193
- Preparations p.194
- Air tight test and vacuum drying p.194
- Note total amount of refrigerant should be 100 kg or less p.195
- Before working p.195
- Air tight test and vacuum drying method p.195
- Additional refrigerant charge and check operation p.195
- When operating the shutoff valve follow the procedure instructed below p.196
- Shutoff valve operation procedure p.196
- Note do not open the shutoff valve until 1 check work prior to turn power supply on in page 181 are completed if the shutoff valve is left open without turning on the power it may cause refrigerant to buildup in the compressor leading insulation degradation be sure to use the correct tools the shutoff valve is not a back seat type if forced it to open it might break the valve body when using a service port use the charge hose after tightening the cap make sure no refrigerant gas is leaking p.196
- 3 3 3 3 3 p.197
- Note press the mode button bs1 if you get confused while operating this returns to setting mode 1 default p.197
- It is possible to find out how many indoor or outdoor unit in the system are turned on by operating the push button on the pc board a1p of outdoor unit in case of multi system master unit follow the procedure below to check how many indoor or outdoor units are turned on p.197
- How to check how many units are connected p.197
- 5 3 5 5 3 p.197
- 4 3 3 3 3 p.197
- 3 4 3 3 3 p.197
- 3 3 4 3 4 p.197
- Procedure of adding refrigerant charging and check operation p.198
- Test operation si34 803 p.199
- Test operation p.199
- Perform the refrigerant charging operation following refrigerant charging operation procedure as shown in page 189 and charge the remaining refrigerant of the additional charging amount for performing the refrigerant charging operation the push button on the pc board a1p of outdoor unit incase of multi system master unit are use see the figure 32 in addition the refrigerant are charged from the refrigerant charge port via the valve a see the figure 33 for operating the push button and opening and closing the valve follow the work procedure p.199
- Open the valve c see the figure 31 the valve a b and the liquid and gas side shutout valve must be left closed and charge the refrigerant of the additional charging amount from the liquid side shutout valve service port if the additional charging amount was charged fully close the valve c and go to step 5 if the additional charging amount was not charged fully go to step 4 p.199
- Note the refrigerant will be charged about 22kg in one hour at outdoor temp 30 c db 6kg at 0 c db if you need to speed up in case of multi system connect the refrigerant cylinders to each outdoor unit as shown in the figure 33 p.199
- Fig 33 p.199
- Fig 32 p.199
- Fig 31 p.199
- Refrigerant charging operation procedure p.200
- 2 if necessary set the field setting by using the dip switch on the outdoor unit pc board a1p for how to set see 1 onsite settings with the power off 3 close the el compo box lid and all front panel except on the side of the el compo box 1 and turn the power to the outdoor unit and all connected indoor units 2 after h2p stop blinking about 12 minutes after turning on the power check led displays as shown in the table display of normal system and the system is normal state if h2p is blinking check the malfunction code in the remote controller and correct the malfunction in accordance with remote controller display malfunction code in page 191 1 lead the refrigerant charge hose etc from the pipe intake all front panels must be closed at the procedure 9 2 if you perform the refrigerant charging operation within the refrigerant system that have the power off unit the operation cannot finish properly for confirming the number of the outdoor and indoor units with the power on see how to chec p.200
- 1 open the liquid and gas side shutoff valves the valve a c must be closed the valve a c means the valves in the figure 33 display of normal system p.200
- Note for check operation the following work will be performed check of shutoff valve opening check of miswiring judgment of piping length check of refrigerant overcharge it takes about 40 minutes to complete the check operation p.201
- How to distinguish the master unit sub unit 1 and sub unit 2 in the multi system p.201
- Check operation procedure p.201
- 4 make the onsite settings as needed using the push button bs1 bs5 on the outdoor unit pc board a1p with the power on see 1 onsite settings with the power on 5 perform the check operation following the check operation method of the service precautions label on the el compo box lid the system operation for about 40 minutes and automatically stops the check operation if the malfunction code is not displayed in the remote controller after the system stop check operation is completed normal operation will be possible after 5 minutes if the malfunction code is displayed in the remote controller correct the malfunction following remote controller displays malfunction code and perform the check operation again p.201
- 1 make the onsite setting as needed using the dip switches on the outdoor unit pc board a1p with the power off see 1 onsite settings with the power off 2 close the el compo box lid and all front panels except as the side of the el compo box and turn on the power to the outdoor unit and all connected indoor units be sure to turn the power on at least 6 hours before operation in order to have power running to the crank case heater 3 check the led display on the outdoor unit pc board a1p is as shown in the table below and transmission is normal p.201
- Remote controller displays malfunction code p.202
- If any malfunction codes other than the above are displayed check the service manual for how to respond p.202
- Onsite settings with the power on p.203
- Onsite settings with the power off p.203
- Onsite settings p.203
- Test run p.204
- Before test run p.204
- Checks after test run p.205
- When turning on power the second time and subsequent p.206
- When turning on power first time p.206
- When an indoor unit or outdoor unit has been added or indoor or outdoor unit pc board has been changed p.206
- The unit cannot be run for up to 12 minutes to automatically set the master power and address indoor outdoor address etc status p.206
- Tap the reset button on the outdoor unit pc board operation becomes possible for about 2 minutes if you do not push the reset button the unit cannot be run for up to 10 minutes to automatically set master power status p.206
- Operation when power is turned on p.206
- Caution when the 400 volt power supply is applyed to n phase by mistake replace inverter pc board a2p and control transformer t1r t2r in switch box together p.206
- Be sure to push and hold the reset button for 5 seconds if not the addition cannot be recognized in this case the unit cannot be run for up to 12 minutes to automatically set the address indoor outdoor address etc status p.206
- Outdoor unit pc board layout p.207
- Outdoor unit pc board p.207
- 4 local setting switch used to make field settings p.207
- 3 mode setting switch used to change mode p.207
- 2 set mode display led leds display mode according to the setting p.207
- 1 microcomputer normal monitor this monitor blinks while in normal operation and turns on or off when a malfunction occurs p.207
- Field setting p.208
- Field set mode p.208
- Unit no p.208
- Second code no p.208
- Mode no p.208
- First code no p.208
- Field setting from remote controller p.208
- Wireless remote controller indoor unit p.209
- Simplified remote controller p.210
- Test operation p.211
- Setting contents and code no vrv indoor unit p.211
- Notes 1 settings are made simultaneously for the entire group however if you select the mode no inside parentheses you can also set by each individual unit setting changes however cannot be checked except in the individual mode for those in parentheses 2 the mode numbers inside parentheses cannot be used by wireless remote controllers so they cannot be set individually setting changes also cannot be checked 3 marked are factory set 4 do not make settings other than those described above nothing is displayed for functions the indoor unit is not equipped with 5 88 may be displayed to indicate the remote controller is resetting when returning to the normal mode 6 if the setting mode to equipped heat reclaim ventilation fan conducts the fan residual operation by linking to indoor unit 7 the fxmq50 63 80 100 125pve cannot be set to 30pa the fxmq40pve cannot be set to 180 or 200pa p.211
- Field setting si34 803 p.211
- Test operation 201 p.212
- Si34 803 field setting p.212
- Applicable range of field setting p.212
- 1 static pressure selection 2 refer to 3 outdoor air processing unit field setting remote controller on p 09 p.212
- 1 filter sign setting p.213
- Whether or not to display filter cleaning after operation of certain duration can be selected p.213
- When a ultra long life filter is installed the filter sign timer setting must be changed p.213
- The factory setting for the second code no is 01 and room temperature is controlled by the indoor unit suction air thermistor and remote controller thermistor when the second code no is set to 02 room temperature is controlled by the suction air thermistor when the second code no is set to 03 room temperature is controlled by the remote controller thermistor p.213
- Setting table p.213
- Select the thermistor to control room temperature p.213
- If switching the filter sign on time set as given in the table below set time p.213
- Detailed explanation of setting modes p.213
- 4 filter cleaning displayed or not displayed p.213
- 3 selection of thermistor p.213
- 2 ultra long life filter sign setting p.213
- This input is used for on off operation and protection device input from the outside the input is performed from the t1 t1 terminal of the operation terminal block x1a in the electric component box p.214
- Setting table p.214
- External static pressure settings make settings in either method a or method b as explained below a use the airflow auto adjustment function to make settings airflow auto adjustment the volume of blow off air is automatically adjusted to the rated quantity b select external static pressure with remote controller check that 01 off is set for the second code no in mode no 21 for airflow adjustment on an indoor unit basis in table 4 the second code no is set to 01 off at factory set change the second code no as shown in table according to the external static pressure of the duct to be connected p.214
- 7 external on off input p.214
- 6 optional output switching p.214
- 5 airflow adjustment auto p.214
- Using this setting operation output signal and abnormal output signal can be provided output signal is output between terminals k1 and k2 of customized wiring adapter an optional accessory p.214
- This setting makes it possible to change differential values for mode selection while in automatic operation mode p.215
- This setting is used to set air flow when heating thermostat is off when thermostat off air flow volume up mode is used careful consideration is required before deciding installation location during heating operation this setting takes precedence over 7 fan stop when thermostat is off p.215
- This is used to set air flow to ll air flow when cooling thermostat is off p.215
- The automatic operation mode setting is made by the use of the operation mode selector button p.215
- For the air conditioners with no setting for the function same as factory setting the units will be left in the stop condition when the power supply is reset automatically after power failure reset or the main power supply is turned on again after once turned off however for the air conditioners with the setting the units may start automatically after power failure reset or the main power supply turned on again return to the same operation condition as that of before power failure p.215
- For the above reasons when the unit is set enabling to utilize auto restart function after power failure reset utmost care should be paid for the occurrence of the following situation p.215
- Differential value during thermostat on off control can be changed for details refer to 6 thermostat control while in normal operation on page 170 p.215
- Caution 1 the air conditioner starts operation suddenly after power failure reset or the main power supply turned on again consequently the user might be surprised with question for the reason why 2 in the service work for example turning off the main power switch during the unit is in operation and turning on the switch again after the work is completed start the unit operation the fan rotates p.215
- 9 air flow setting when heating thermostat is off p.215
- 8 thermostat switching p.215
- 12 air flow when cooling thermostat is off p.215
- 11 auto restart after power failure reset p.215
- 10 setting of operation mode to auto p.215
- 13 setting of normal air flow p.216
- 1 mode no setting is done in a batch for the group to make or confirm settings for an individual unit set the internal mode number in parentheses 2 the figure of the ceiling height is for the all round outlet for the settings for four direction part of corner closed off three direction and two direction outlets see the installation manual and technical guide supplied with the separately sold closure material kit p.216
- Way 3 way 2 way outlets p.216
- Make the following setting according to the ceiling height the setting position no is set to 01 at the factory in the case of fxaq p.216
- In the case of fxhq p.216
- In the case of fxfq25 80 all round outlet p.216
- In the case of fxfq25 80 p.216
- In the case of fxfq100 125 all round outlet p.216
- In the case of fxfq100 125 p.216
- Set the air flow direction of indoor units as given in the table below set when optional air outlet blocking pad has been installed the second code no is factory set to 01 p.217
- Only the model fxkq has the function when only the front flow is used sets yes no of the swing flap operation of down flow p.217
- Make the following air flow direction setting according to the respective purpose p.217
- In the case of fxuq71 125 p.217
- In the case of fxdq20 32pb fxdq40 63nb p.217
- 17 setting of the static pressure selection p.217
- 16 setting of air flow direction adjustment range p.217
- 15 operation of downward flow flap yes no p.217
- 14 air flow direction setting p.217
- Some indoor unit models are not equipped with draft prevention upward function p.217
- Setting table p.217
- This is used when fresh air intake kit equipped with fan is connected the indoor fan carries out residual operation for one minute after the thermostat is stopped for the purpose of preventing dust on the air filter from falling off p.218
- This is used to interlock the humidifier with the drain pump when water is drained out of the unit this setting is unnecessary p.218
- The second code no is set to 07 an external static pressure of 100 pa at factory set 1 the fxmq50 63 80 100 125pve cannot be set to 30 pa 2 the fxmq40pve cannot be set to 180 or 200 pa p.218
- Setting to humidification setting turns on the humidifier if suction temperature is 20ºc or above and turns off the humidifier if suction temperature is 18ºc or below when the heating thermostat is off p.218
- 21 interlocked operation between humidifier and drain pump p.218
- 20 setting of direct duct connection p.218
- 19 humidification when heating thermostat is off p.218
- 18 external static pressure settings for fxmq p model p.218
- This is set to perform individual operation of heat reclaim ventilation using the remote controller central unit when heat reclaim ventilation is built in switch only when heat reclaim ventilation is built in p.219
- 22 individual setting of ventilation p.219
- Outdoor air processing unit field setting remote controller p.220
- Note bold face in indicates the default setting p.220
- Centralized control group no setting p.221
- Group no setting example p.222
- Brc7c type brc7e type brc4c type p.222
- Test operation 211 p.222
- Si34 803 field setting p.222
- Group no setting by wireless remote controller for centralized control 1 when in the normal mode push button for 4 seconds or more and operation then enters the field set mode 2 set mode no 00 with button 3 set the group no for each group with button advance backward p.222
- Enter the selected group numbers by pushing button 5 push button and return to the normal mode p.222
- Caution when turning the power supply on the unit may often not accept any operation while 88 is displaying after all indications were displayed once for about 1 minute on the liquid crystal display this is not an operative fault p.222
- Setting of operation control mode from remote controller local setting p.223
- Contents of control modes p.223
- Whether operation by remote controller will be possible or not for turning on off controlling temperature or setting operation mode is selected and decided by the operation mode given on the right edge of the table below p.224
- How to select operation mode p.224
- Do not select timer operation possible by remote controller if not using a remote controller operation by timer is impossible in this case 1 factory setting p.224
- List of field setting items this following section indicates the list of field setting items for the lists of dip switch contents setting mode 1 and setting mode 2 refer to information in tables shown on the following page onward for setting items of 1 refer to detailed information provided on page 226 onward p.225
- Field setting from outdoor unit p.225
- For setting items of 1 refer to detailed information provided on page 226 onward p.226
- Dip switch detail p.227
- Caution p.227
- Setting by dip switches using dip switches on the pc board enables field setting shown below however make no changes of factory settings except for ds1 1 p.227
- Refer ds1 1 4 ds2 1 4 setting detail on next page p.227
- Make the following settings according to models of outdoor units all models are set to off at factory p.227
- Initial conditions of dip switches p.227
- If the ds1 1 1 4 ds2 2 2 4 setting has not been carried out error code ua are displayed and unit can not be operated p.227
- Dip switch setting after changing the main pc board a1p to spare parts pc board after the replacement by the spare pc board be sure to make settings shown below when you change the main pc board a1p to spare parts pc board please carry out the following setting p.227
- Detail of ds1 1 4 ds2 1 4 setting for overseas general p.228
- This mode is used to set and check the following items 1 set items in order to make cool heat selection in a batch of outdoor unit group change the setting cool heat selection ind used to select cool or heat by individual outdoor unit factory set cool heat selection master used to select cool or heat by outdoor unit group with the master unit cool heat selection slave used to select cool or heat by outdoor unit group with the slave unit 2 check items the following items can be checked 1 current operating conditions normal abnormal in check operation 2 setting conditions of cool heat selection individual batch master batch slave 3 low noise operating conditions in normal operation in low noise operation 4 demand operating conditions in normal operation in demand operation p.230
- Test operation 219 p.230
- Si34 803 field setting p.230
- Procedure for changing cool heat selection setting p.230
- A setting mode 1 p.230
- 7 8 7 7 7 7 p.230
- B setting mode 2 p.231
- 8 7 7 7 7 p.235
- 7 7 7 7 7 p.235
- 1 number of connected indoor units used to make setting of the number of indoor units connected to an outdoor unit 2 number of connected bs units used to make setting of the number of bs units connected to an outdoor unit 3 number of outdoor units used to make setting of the number of outdoor units connected to diii net that is one of the communication lines 4 number of bs units used to make setting of the number of bs units connected to diii net that is one of the communication lines 5 number of terminal units used to make setting of the number of indoor units connected to diii net that is one of the communication lines only available for vrv indoor units p.235
- 7 8 8 8 8 p.235
- 7 8 8 8 7 p.235
- 7 8 8 7 8 p.235
- 7 8 8 7 7 p.235
- 7 8 7 8 8 p.235
- 7 8 7 8 7 p.235
- 7 8 7 7 8 p.235
- The numbers in the no column represent the number of times to press the set bs2 button p.235
- 7 8 7 7 7 p.235
- Test operation p.235
- 7 7 8 8 8 p.235
- Field setting si34 803 p.235
- 7 7 8 8 7 p.235
- C monitor mode p.235
- 7 7 8 7 8 p.235
- 8 8 7 7 8 p.235
- 7 7 8 7 7 p.235
- 8 7 8 8 7 p.235
- 7 7 7 8 8 p.235
- 8 7 8 7 8 p.235
- 7 7 7 8 7 p.235
- 8 7 8 7 7 p.235
- 7 7 7 7 8 p.235
- 7 7 8 7 7 p.236
- 7 7 7 9 7 p.236
- 7 7 7 8 7 p.236
- 7 7 7 7 9 p.236
- 7 7 7 7 8 p.236
- 7 7 7 7 7 p.236
- 4 1 32 8 2 p.236
- The number of terminal blocks for no 12 and 13 is expressed as an 8 digit binary number which is the combination of four upper and four lower digits for no 12 and 13 respectively 0 128 in the address for no 12 is 0101 the address for no 13 is 0110 and the combination of the two is 01010110 binary number which translates to 64 16 4 2 86 base 10 number in other words the number of terminal block is 86 p.236
- 16 128 32 no 2 p.236
- The no 1 cool heat unified address is expressed as a binary number consisting of the lower 6 digits 0 63 p.236
- Setting item 0 display contents of number of units for various settings p.236
- See the preceding page for a list of data etc for no 0 25 p.236
- No 3 8 2 p.236
- In the address is 010110 binary number which translates to 16 4 2 22 base 10 number in other words the address is 22 p.236
- Data such as addresses and number of units is expressed as binary numbers the two ways of expressing are as follows p.236
- 7 8 7 7 7 p.236
- 7 7 9 7 7 p.236
- There are the following 4 cool heat switching modes set cool heat separately for each outdoor unit system by indoor unit remote controller set cool heat separately for each outdoor unit system by cool heat selector set cool heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by indoor unit remote controller set cool heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by cool heat switching remote controller p.237
- Set cool heat separately for each outdoor unit system by indoor unit remote controller p.237
- It does not matter whether or not there is outdoor outdoor unit wiring set outdoor unit pc board ds1 1 to in factory set set cool heat switching to ind individual for setting mode 1 factory set set the master unit indoor unit having the right to select the cooling heating operation mode p.237
- In the case of wireless remote controllers p.237
- In the case of wired remote controllers p.237
- For the details refer to the installation manual supplied together with the indoor unit p.237
- Cool heat mode switching p.237
- Set cool heat separately for each outdoor unit system by cool heat selector p.238
- Set cool heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by indoor unit remote controller p.239
- Multi outdoor units connection p.239
- Set cool heat for more than one outdoor unit system simultaneously in accordance with unified master outdoor unit by cool heat selector p.240
- Multi outdoor units connection p.240
- Supplementation on p.241
- Setting of low noise operation and demand operation p.242
- Setting of low noise operation p.242
- Image of operation in the case of b p.243
- Image of operation in the case of a and b p.243
- Image of operation in the case of a p.243
- Setting of demand operation p.244
- By connecting the external contact input to the demand input of the outdoor unit external control adapter optional the power consumption of unit operation can be saved suppressing the compressor operating condition p.244
- B when the normal demand operation is carried out use of the external control adapter for outdoor unit is not required 1 while in setting mode 2 make setting of the set item no 32 setting of constant demand to on 2 while in setting mode 2 select the set item no 30 setting of demand 1 level and then set the setting condition to targeted mode p.244
- A when the demand operation is carried out by external instructions with the use of the external control adapter for outdoor unit 1 while in setting mode 2 set the setting condition for set item no 12 setting of external low noise demand operation to yes 2 if necessary while in setting mode 2 select the set item no 30 setting of demand 1 level and then set the setting condition to targeted mode p.244
- Field setting si34 803 p.245
- Test operation p.245
- Image of operation in the case of b p.245
- Image of operation in the case of a and b p.245
- Image of operation in the case of a p.245
- Detailed setting procedure of low noise operation and demand control p.246
- Setting of refrigerant recovery mode p.248
- Setting of vacuuming mode p.249
- Check operation function p.249
- Check operation detail p.249
- Troubleshooting by indication on the remote controller 60 p.250
- Symptom based troubleshooting 42 2 troubleshooting by remote controller 45 p.250
- Part 6 troubleshooting p.250
- Troubleshooting op central remote controller 45 p.251
- Troubleshooting op unified on off controller 53 p.252
- Symptom based troubleshooting p.253
- Inspection mode p.256
- Troubleshooting by remote controller p.256
- The inspection test button p.256
- The following modes can be selected by using the inspection test operation button on the remote control p.256
- Test operation mode p.256
- Normal mode p.256
- Local setting mode service mode p.256
- Self diagnosis by wired remote controller p.257
- Explanation p.257
- Self diagnosis by wireless remote controller p.258
- In the case of brc7c type brc7e type brc4c type p.258
- The lower digit of the code changes as shown below when the up and down buttons are pressed p.259
- Troubleshooting by remote controller si34 803 p.261
- Troubleshooting p.261
- Operation of the remote controller s inspection test operation button p.261
- Remote controller service mode p.262
- How to enter the service mode p.262
- Service mode operation method p.262
- Remote controller self diagnosis function p.264
- The system operates for malfunction codes indicated in black squares however be sure to check and repair p.266
- Troubleshooting by remote controller si34 803 p.267
- Troubleshooting p.267
- To enter the monitor mode push the mode bs1 button when in setting mode 1 p.267
- Refer to p 24 for monitor mode p.267
- Push the set bs2 button once to display second digit of malfunction code p.267
- Push the set bs2 button once to display master or slave 1 or slave 2 and malfunction location p.267
- Push the set bs2 button once to display malfunction location p.267
- Push the set bs2 button and set the led display to a setting item p.267
- Push the return bs3 button once to display first digit of malfunction code p.267
- Push the return bs3 button and switches to the initial status of monitor mode p.267
- Push the mode bs1 button and returns to setting mode 1 p.267
- Malfunction code indication by outdoor unit pc board p.267
- Detail description on next page p.267
- Troubleshooting 257 p.268
- Si34 803 troubleshooting by remote controller p.268
- Troubleshooting by remote controller si34 803 p.269
- Troubleshooting p.269
- To enter the monitor mode push the mode bs1 button when in setting mode 1 p.269
- Refer to p 24 for monitor mode p.269
- Push the set bs2 button once to display second digit of malfunction code p.269
- Push the set bs2 button once to display master or slave 1 or slave 2 and malfunction location p.269
- Push the set bs2 button once to display malfunction location p.269
- Push the set bs2 button and set the led display to a setting item p.269
- Push the return bs3 button once to display first digit of malfunction code p.269
- Push the return bs3 button and switches to the initial status of monitor mode p.269
- Push the mode bs1 button and returns to setting mode 1 p.269
- Detail description on next page p.269
- Troubleshooting 259 p.270
- Si34 803 troubleshooting by remote controller p.270
- Method of malfunction detection p.271
- Troubleshooting by indication on the remote controller p.271
- Troubleshooting p.271
- Supposed causes p.271
- Remote controller display p.271
- Malfunction decision conditions p.271
- Indoor unit error of external protection device p.271
- Applicable models p.271
- Indoor unit pc board defect p.272
- Supposed causes p.273
- Remote controller display p.273
- Method of malfunction detection p.273
- Malfunction decision conditions p.273
- Indoor unit malfunction of drain level control system s1l p.273
- Applicable models p.273
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.274
- Troubleshooting 263 p.274
- Troubleshooting p.274
- Si34 803 troubleshooting by indication on the remote controller p.274
- When number of turns can t be detected even when output voltage to the fan is maximum p.275
- Troubleshooting p.275
- Supposed causes p.275
- Remote controller display p.275
- Method of malfunction detection p.275
- Malfunction decision conditions p.275
- Indoor unit fan motor m1f lock overload p.275
- Fan motor lock disconnected or faulty wiring between fan motor and pc board p.275
- Detection by failure of signal for detecting number of turns to come from the fan motor p.275
- Applicable models p.275
- All indoor units except fxmq p p.275
- Malfunction decision conditions p.276
- Applicable models p.276
- Supposed causes p.276
- Remote controller display p.276
- Method of malfunction detection p.276
- Troubleshooting by indication on the remote controller si34 803 p.277
- Troubleshooting p.277
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.277
- Troubleshooting 267 p.278
- Si34 803 troubleshooting by indication on the remote controller p.278
- Indoor unit malfunction of swing flap motor m1s p.279
- Troubleshooting 269 p.280
- Troubleshooting p.280
- Si34 803 troubleshooting by indication on the remote controller p.280
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.280
- Detect malfunction checking the input voltage of fan motor p.281
- Applicable models p.281
- Abnormal power supply voltage p.281
- When the input voltage of fan motor is 150v and below or 386v and above p.281
- Troubleshooting p.281
- The possible causes are power supply voltage malfunction connection defect on signal line wiring defect instantaneous blackout others p.281
- Supposed causes p.281
- Remote controller display p.281
- Method of malfunction detection p.281
- Malfunction decision conditions p.281
- Fxmq40 125p p.281
- Supposed causes p.282
- Remote controller display p.282
- Method of malfunction detection p.282
- Malfunction of moving part of electronic expansion valve defect of indoor unit pc board defect of connecting cable p.282
- Malfunction decision conditions p.282
- Indoor unit malfunction of moving part of electronic expansion valve y1e p.282
- Applicable models p.282
- All indoor unit models p.282
- When the pin input of the electronic expansion valve is not normal while in the initialization of the microcomputer p.282
- Use a microcomputer to check the electronic expansion valve for coil conditions p.282
- Troubleshooting p.282
- Normal p.283
- Continuity no continuity p.283
- 1 coil check method for the moving part of the electronic expansion valve disconnect the electronic expansion valve from the pc board and check the continuity between the connector pins p.283
- Water leakage is detected based on float switch on off operation while the compressor is in non operation p.284
- Troubleshooting p.284
- Supposed causes p.284
- Remote controller display p.284
- Method of malfunction detection p.284
- Malfunction decision conditions p.284
- Indoor unit drain level above limit p.284
- Humidifier unit optional accessory leaking defect of drain pipe upward slope etc defect of indoor unit pc board p.284
- Fxcq fxfq fxsq fxkq fxmq fxdq fxmq mf fxuq p.284
- Applicable models p.284
- When the float switch changes from on to off while the compressor is in non operation p.284
- Indoor unit malfunction of capacity determination device p.285
- Indoor unit failure of transmission between indoor unit pc board and fan pc board p.286
- Troubleshooting by indication on the remote controller si34 803 p.287
- Troubleshooting p.287
- Determination 01 normal other than 01 transmission defect on indoor pc board p.287
- After confirmation turn off the power take off the short circuit and connect x70a back to original condition p.287
- 1 pull out and insert the connecter once and check it is absolutely connected 2 method to check transmission part of indoor pc board turn off the power and remove the connecter x70a of indoor pc board a1p short circuit x70a after turning on the power check below numbers under local setting remote control confirmation setting position no at the condition of setting switch no 21 on mode no 41 p.287
- Refer to thermistor resistance temperature characteristics table on p 27 p.288
- Method of malfunction detection p.288
- Malfunction detection is carried out by temperature detected by heat exchanger thermistor p.288
- Malfunction decision conditions p.288
- Indoor unit malfunction of thermistor r2t for heat exchanger p.288
- Defect of thermistor r2t for liquid pipe defect of indoor unit pc board p.288
- Applicable models p.288
- All indoor unit models p.288
- When the heat exchanger thermistor becomes disconnected or shorted while the unit is running p.288
- Troubleshooting p.288
- Supposed causes p.288
- Remote controller display p.288
- When the gas pipe thermistor becomes disconnected or shorted while the unit is running p.289
- Troubleshooting p.289
- Supposed causes p.289
- Remote controller display p.289
- Refer to thermistor resistance temperature characteristics table on p 27 p.289
- Method of malfunction detection p.289
- Malfunction detection is carried out by temperature detected by gas pipe thermistor p.289
- Malfunction decision conditions p.289
- Indoor unit malfunction of thermistor r3t for gas pipes p.289
- Defect of indoor unit thermistor r3t for gas pipe defect of indoor unit pc board p.289
- Applicable models p.289
- All indoor unit models p.289
- When the communication data of pc board for fan a2p is determined as incorrect p.290
- Troubleshooting p.290
- The possible causes are malfunction of pc board for fan a2p connection defect of capacity setting adapter setting mistake on site p.290
- Supposed causes p.290
- Remote controller display p.290
- Method of malfunction detection p.290
- Malfunction decision conditions p.290
- Indoor unit failure of combination between indoor unit pc board and fan pc board p.290
- Fxmq40 125p p.290
- Conduct open line detection with pc board for fan a2p using indoor pc board a1p p.290
- Applicable models p.290
- Malfunction decision conditions p.291
- Indoor unit malfunction of thermistor r1t for suction air p.291
- Defect of indoor unit thermistor r1t for air inlet defect of indoor unit pc board p.291
- Applicable models p.291
- Aii indoor unit models p.291
- When the suction air temperature thermistor becomes disconnected or shorted while the unit is running p.291
- Troubleshooting p.291
- Supposed causes p.291
- Remote controller display p.291
- Refer to thermistor resistance temperature characteristics table on p 27 p.291
- Method of malfunction detection p.291
- Malfunction detection is carried out by temperature detected by suction air temperature thermistor p.291
- Troubleshooting p.292
- Supposed causes p.292
- Remote controller display p.292
- Method of malfunction detection p.292
- Malfunction decision conditions p.292
- Indoor unit malfunction of humidity sensor system p.292
- Faulty sensor disconnection p.292
- Even if a malfunction occurs operation still continues malfunction is detected according to the moisture output voltage detected by the moisture sensor p.292
- Applicable models p.292
- When the moisture sensor is disconnected or short circuited p.292
- Indoor unit malfunction of thermostat sensor in remote controller p.293
- Outdoor unit pc board defect p.294
- Supposed causes p.295
- Remote controller display p.295
- Outdoor unit actuation of high pressure switch p.295
- Method of malfunction detection p.295
- Malfunction decision conditions p.295
- Applicable models p.295
- Troubleshooting 285 p.296
- Troubleshooting p.296
- Si34 803 troubleshooting by indication on the remote controller p.296
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.296
- 1 make a comparison between the voltage of the pressure sensor and that read by the pressure gauge as to the voltage of the pressure sensor make measurement of voltage at the connector and then convert it to pressure according to information on page 429 2 make a comparison between the high pressure value checked with the service checker and the voltage of the pressure sensor see 1 3 make measurement of voltage of the pressure sensor p.296
- Outdoor unit actuation of low pressure sensor p.297
- 1 make a comparison between the voltage of the pressure sensor and that read by the pressure gauge as to the voltage of the pressure sensor make measurement of voltage at the connector and then convert it to pressure according to information on page 429 2 make a comparison between the low pressure value checked with the service checker and the voltage of the pressure sensor see 1 3 make measurement of voltage of the pressure sensor p.298
- Troubleshooting 287 p.298
- Troubleshooting p.298
- Si34 803 troubleshooting by indication on the remote controller p.298
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.298
- Supposed causes p.299
- Remote controller display p.299
- Outdoor unit inverter compressor motor lock p.299
- Method of malfunction detection p.299
- Malfunction decision conditions p.299
- Applicable models p.299
- Troubleshooting 289 p.300
- Troubleshooting p.300
- Si34 803 troubleshooting by indication on the remote controller p.300
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.300
- Closed stop value obstacles at the air outlet improper power voltage faulty magnetic switch faulty compressor faulty current sensor a6p a7p p.301
- Applicable models p.301
- Troubleshooting p.301
- Supposed causes p.301
- Rxyq5p a 54p a p.301
- Remote controller display p.301
- Outdoor unit std compressor motor overcurrent lock p.301
- Note 1 abnormal case the current sensor value is 0 during std compressor operation the current sensor value is more than 15 a during std compressor stop p.301
- Method of malfunction detection p.301
- Malfunction is decided when the detected current value exceeds the below mentioned value for 2 seconds 400 v class unit 15 a 200 v class unit 28 a p.301
- Malfunction decision conditions p.301
- Detects the overcurrent with current sensor ct p.301
- Supposed causes p.302
- Remote controller display p.302
- Outdoor unit malfunction of outdoor unit fan motor p.302
- Method of malfunction detection p.302
- Malfunction decision conditions p.302
- Applicable models p.302
- Troubleshooting by indication on the remote controller si34 803 p.303
- Troubleshooting p.303
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.303
- Troubleshooting 293 p.304
- Troubleshooting p.304
- Si34 803 troubleshooting by indication on the remote controller p.304
- Note refer to check 1 and 2 on p 59 p.304
- Outdoor unit malfunction of moving part of electronic expansion valve y1e y2e p.305
- Troubleshooting 295 p.306
- Troubleshooting p.306
- Si34 803 troubleshooting by indication on the remote controller p.306
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.306
- Malfunction decision conditions p.307
- Faulty discharge pipe temperature sensor faulty connection of discharge pipe temperature sensor faulty outdoor unit pc board p.307
- Applicable models p.307
- Abnormality is detected according to the temperature detected by the discharge pipe temperature sensor p.307
- When the discharge pipe temperature rises to an abnormally high level when the discharge pipe temperature rises suddenly p.307
- Troubleshooting p.307
- Supposed causes p.307
- Rxyq5p a 54p a p.307
- Remote controller display p.307
- Refer to thermistor resistance temperature characteristics table on p 28 p.307
- Outdoor unit abnormal discharge pipe temperature p.307
- Method of malfunction detection p.307
- Remote controller display p.308
- Refrigerant overcharge misalignment of the outside air thermistor misalignment of the heat exchanging deicer thermistor misalignment of the liquid pipe thermistor p.308
- Refer to thermistor resistance temperature characteristics table on p 27 p.308
- Outdoor unit refrigerant overcharged p.308
- Method of malfunction detection p.308
- Malfunction decision conditions p.308
- Excessive charging of refrigerant is detected by using the outside air temperature heat exchanging deicer temperature and liquid pipe temperature during a check run p.308
- Applicable models p.308
- When the amount of refrigerant which is calculated by using the outside air temperature heat exchanging deicer temperature and liquid pipe temperature during a check run exceeds the standard p.308
- Troubleshooting p.308
- Supposed causes p.308
- Rxyq5p a 54p a p.308
- Troubleshooting p.309
- Supposed causes p.309
- Rxyq5p a 54p a p.309
- Remote controller display p.309
- Outdoor unit abnormal outdoor fan motor signal p.309
- Method of malfunction detection p.309
- Malfunction decision conditions p.309
- In case of detection of abnormal signal at starting fan motor p.309
- Detection of abnormal signal from fan motor p.309
- Applicable models p.309
- Abnormal fan motor signal circuit malfunction broken short or disconnection connector of fan motor connection cable fan inverter pc board malfunction p.309
- 1 disconnect connector x2a and measure the following resistance p.309
- When the outside air temperature thermistor has short circuit or open circuit p.310
- Troubleshooting p.310
- Supposed causes p.310
- Rxyq5p a 54p a p.310
- Remote controller display p.310
- Refer to thermistor resistance temperature characteristics table on p 27 p.310
- Outdoor unit malfunction of thermistor r1t for outdoor air p.310
- Method of malfunction detection p.310
- Malfunction is detected from the temperature detected by the outdoor air thermistor p.310
- Malfunction decision conditions p.310
- Defect of thermistor r1t for outdoor air defect of outdoor unit pc board a1p p.310
- Applicable models p.310
- Malfunction is detected according to the current value detected by current sensor p.311
- Malfunction decision conditions p.311
- Faulty current sensor a6p a7p faulty outdoor unit pc board p.311
- Applicable models p.311
- When the current value detected by current sensor becomes 5a or lower or 40a or more during standard compressor operation p.311
- Troubleshooting p.311
- Supposed causes p.311
- Rxyq5p a 54p a p.311
- Remote controller display p.311
- Outdoor unit current sensor malfunction p.311
- Method of malfunction detection p.311
- Remote controller display p.312
- Refer to thermistor resistance temperature characteristics table on p 28 p.312
- Outdoor unit malfunction of discharge pipe thermistor r3 r31 33t p.312
- Note 5 hp class r3t 8 12 hp class r31t r32t 14 16hp class r31t r32t and r33t p.312
- Method of malfunction detection p.312
- Malfunction is detected from the temperature detected by discharge pipe temperature thermistor p.312
- Malfunction decision conditions p.312
- Defect of thermistor r31t r32t or r33t for outdoor unit discharge pipe defect of outdoor unit pc board a1p defect of thermistor connection p.312
- Applicable models p.312
- When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected p.312
- Troubleshooting p.312
- The alarm indicator is displayed when the fan is being used also p.312
- Supposed causes p.312
- Rxyq5p a 54p a p.312
- Troubleshooting p.313
- Supposed causes p.313
- Rxyq5p a 54p a p.313
- Remote controller display p.313
- Refer to thermistor resistance temperature characteristics table on p 27 p.313
- Outdoor unit malfunction of thermistor r2t r7t for suction pipe p.313
- Method of malfunction detection p.313
- Malfunction is detected from the temperature detected by the suction pipe temperature thermistor p.313
- Malfunction decision conditions p.313
- Defect of thermistor r2t r7t for outdoor unit suction pipe defect of outdoor unit pc board a1p defect of thermistor connection p.313
- Applicable models p.313
- When a short circuit or an open circuit in the suction pipe temperature thermistor is detected p.313
- When a short circuit or an open circuit in the heat exchange thermistor is detected p.314
- Troubleshooting p.314
- Supposed causes p.314
- Rxyq5p a 54p a p.314
- Remote controller display p.314
- Refer to thermistor resistance temperature characteristics table on p 27 p.314
- Outdoor unit malfunction of thermistor r4t for outdoor unit heat exchanger p.314
- Method of malfunction detection p.314
- Malfunction is detected from the temperature detected by the heat exchanger thermistor p.314
- Malfunction decision conditions p.314
- Defect of thermistor r4t for outdoor unit coil defect of outdoor unit pc board a1p defect of thermistor connection p.314
- Applicable models p.314
- Malfunction decision conditions p.315
- Faulty liquid pipe thermistor r6t faulty outdoor unit pc board defect of thermistor connection p.315
- Applicable models p.315
- When the liquid pipe thermistor is short circuited or open p.315
- Troubleshooting p.315
- Supposed causes p.315
- Rxyq5p a 54p a p.315
- Remote controller display p.315
- Refer to thermistor resistance temperature characteristics table on p 27 p.315
- Outdoor unit malfunction of liquid pipe thermistor r6t p.315
- Method of malfunction detection p.315
- Malfunction is detected according to the temperature detected by liquid pipe thermistor p.315
- Refer to thermistor resistance temperature characteristics table on p 27 p.316
- Outdoor unit malfunction of subcooling heat exchanger gas pipe thermistor r5t p.316
- Method of malfunction detection p.316
- Malfunction is detected according to the temperature detected by subcooling heat exchanger gas pipe thermistor p.316
- Malfunction decision conditions p.316
- Faulty subcooling heat exchanger gas pipe thermistor r5t faulty outdoor unit pc board p.316
- Applicable models p.316
- When the subcooling heat exchanger gas pipe thermistor is short circuited or open p.316
- Troubleshooting p.316
- Supposed causes p.316
- Rxyq5p a 54p a p.316
- Remote controller display p.316
- Supposed causes p.317
- Rxyq5p a 54p a p.317
- Remote controller display p.317
- Outdoor unit malfunction of high pressure sensor p.317
- Method of malfunction detection p.317
- Malfunction is detected from the pressure detected by the high pressure sensor p.317
- Malfunction decision conditions p.317
- Defect of high pressure sensor system connection of low pressure sensor with wrong connection defect of outdoor unit pc board p.317
- Applicable models p.317
- 2 refer to pressure sensor pressure voltage characteristics table on p 29 p.317
- 1 voltage measurement point p.317
- When the high pressure sensor is short circuit or open circuit p.317
- Troubleshooting p.317
- When the low pressure sensor is short circuit or open circuit p.318
- Troubleshooting p.318
- Supposed causes p.318
- Rxyq5p a 54p a p.318
- Remote controller display p.318
- Outdoor unit malfunction of low pressure sensor p.318
- Method of malfunction detection p.318
- Malfunction is detected from pressure detected by low pressure sensor p.318
- Malfunction decision conditions p.318
- Defect of low pressure sensor system connection of high pressure sensor with wrong connection defect of outdoor unit pc board p.318
- Applicable models p.318
- 2 refer to pressure sensor pressure voltage characteristics table on p 29 p.318
- 1 voltage measurement point p.318
- Actuation of fin thermal actuates above 93 c defect of inverter pc board defect of fin thermistor p.319
- When the temperature of the inverter radiation fin increases above 93 c p.319
- Troubleshooting p.319
- Supposed causes p.319
- Rxyq5p a 54p a p.319
- Remote controller display p.319
- Outdoor unit malfunction of inverter radiating fin temperature rise p.319
- Method of malfunction detection p.319
- Malfunction decision conditions p.319
- Fin temperature is detected by the thermistor of the radiation fin p.319
- Applicable models p.319
- Refer to thermistor resistance temperature characteristics table on p 27 p.320
- Inverter pc board for compressor p.320
- Malfunction decision conditions p.321
- Defect of compressor coil disconnected defective insulation compressor start up malfunction mechanical lock defect of inverter pc board p.321
- Compressor inspection p.321
- Applicable models p.321
- When an excessive current flows in the power transistor instantaneous overcurrent also causes activation p.321
- Troubleshooting p.321
- Supposed causes p.321
- Rxyq5p a 54p a p.321
- Remote controller display p.321
- Outdoor unit inverter compressor abnormal p.321
- Method of malfunction detection p.321
- Malfunction is detected from current flowing in the power transistor p.321
- Troubleshooting 311 p.322
- Troubleshooting p.322
- Si34 803 troubleshooting by indication on the remote controller p.322
- Method of malfunction detection p.323
- Malfunction is detected by current flowing in the power transistor p.323
- Malfunction decision conditions p.323
- Compressor overload compressor coil disconnected defect of inverter pc board faulty compressor p.323
- Applicable models p.323
- When overload in the compressor is detected inverter secondary current 16 a y1 yl and 27 a tl p.323
- Troubleshooting p.323
- Supposed causes p.323
- Rxyq5p a 54p a p.323
- Remote controller display p.323
- Output current check p.323
- Outdoor unit inverter current abnormal p.323
- Troubleshooting 313 p.324
- Troubleshooting p.324
- Si34 803 troubleshooting by indication on the remote controller p.324
- Remote controller display p.325
- Outdoor unit inverter start up error p.325
- Method of malfunction detection p.325
- Malfunction decision conditions p.325
- Defect of compressor failure to open the stop valve pressure differential start faulty compressor connection defect of inverter pc board p.325
- Applicable models p.325
- When the startup control is failed when an overcurrent is passed to the inverter due to the malfunction of a compressor or electrical system p.325
- Troubleshooting p.325
- This malfunction code will be output if overcurrent occurs at the time of startup p.325
- Supposed causes p.325
- Rxyq5p a 54p a p.325
- Troubleshooting 315 p.326
- Troubleshooting p.326
- Si34 803 troubleshooting by indication on the remote controller p.326
- Supposed causes p.327
- Remote controller display p.327
- Outdoor unit malfunction of transmission between inverter and control pc board p.327
- Method of malfunction detection p.327
- Malfunction decision conditions p.327
- Applicable models p.327
- Si34 803 troubleshooting by indication on the remote controller p.328
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.328
- Troubleshooting 317 p.328
- Troubleshooting p.328
- Troubleshooting by indication on the remote controller si34 803 p.329
- Troubleshooting p.329
- When the resistance value of thermistor becomes a value equivalent to open or short circuited status malfunction is not decided while the unit operation is continued p1 will be displayed by pressing the inspection button when the amplitude of the ripple exceeding a certain value is detected for consecutive 4 minutes p.330
- Troubleshooting p.330
- Supposed causes p.330
- Rxyq5p a 54p a p.330
- Remote controller display p.330
- Outdoor unit inverter over ripple protection p.330
- Open phase voltage imbalance between phases defect of main circuit capacitor defect of inverter pc board defect of k2 relay in inverter pc board improper main circuit wiring p.330
- Method of malfunction detection p.330
- Malfunction decision conditions p.330
- Imbalance in supply voltage is detected in pc board imbalance in the power supply voltage causes increased ripple of voltage of the main circuit capacitor in the inverter consequently the increased ripple is detected p.330
- Applicable models p.330
- Applicable models p.331
- When the resistance value of thermistor becomes a value equivalent to open or short circuited status malfunction is not decided while the unit operation is continued p4 will be displayed by pressing the inspection button p.331
- Troubleshooting p.331
- Supposed causes p.331
- Rxyq5p a 54p a p.331
- Resistance of radiation fin thermistor is detected when the compressor is not operating p.331
- Remote controller display p.331
- Outdoor unit malfunction of inverter radiating fin temperature rise sensor p.331
- Method of malfunction detection p.331
- Malfunction decision conditions p.331
- Defect of radiator fin temperature sensor defect of inverter pc board p.331
- Refer to thermistor resistance temperature characteristics table on p 27 p.332
- Inverter pc board for compressor p.332
- Method of malfunction detection p.333
- Malfunction decision conditions p.333
- Faulty or no field setting after replacing main pc board mismatching of type of pc board p.333
- Applicable models p.333
- Whether or not the field setting or the type of the pc board is correct through the communication date is judged p.333
- Troubleshooting p.333
- The faulty or no field setting after replacing pc board or faulty pc board combination is detected through communications with the inverter p.333
- Supposed causes p.333
- Rxyq5p a 54p a p.333
- Remote controller display p.333
- Outdoor unit faulty field setting after replacing main pc board or faulty combination of pc board p.333
- Short of gas malfunction is detected by discharge pipe temperature thermistor p.334
- Rxyq5p a 54p a p.334
- Remote controller display p.334
- Outdoor unit low pressure drop due to refrigerant shortage or electronic expansion valve failure p.334
- Out of gas or refrigerant system clogging incorrect piping defect of pressure sensor defect of outdoor unit pc board a1p defect of thermistor r7t or r4t p.334
- Microcomputer judge and detect if the system is short of refrigerant malfunction is not decided while the unit operation is continued p.334
- Method of malfunction detection p.334
- Malfunction decision conditions p.334
- Applicable models p.334
- 1 refer to thermistor resistance temperature characteristics table on p 27 2 refer to pressure sensor pressure voltage characteristics table on p 29 p.334
- Troubleshooting p.334
- Supposed causes p.334
- When a significant phase difference is made between phases p.335
- Troubleshooting p.335
- The phase of each phase are detected by reverse phase detection circuit and right phase or reverse phase are judged p.335
- Supposed causes p.335
- Rxyq5p a 54p a p.335
- Reverse phase open phase p.335
- Remote controller display p.335
- Power supply reverse phase power supply open phase defect of outdoor pc board a1p p.335
- Method of malfunction detection p.335
- Malfunction decision conditions p.335
- Applicable models p.335
- Malfunction decision conditions p.336
- Applicable models p.336
- Supposed causes p.336
- Remote controller display p.336
- Outdoor unit power supply insufficient or instantaneous failure p.336
- Method of malfunction detection p.336
- Troubleshooting by indication on the remote controller si34 803 p.337
- Troubleshooting p.337
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.337
- Troubleshooting 327 p.338
- Troubleshooting p.338
- Si34 803 troubleshooting by indication on the remote controller p.338
- Method of malfunction detection p.339
- Malfunction is decided when the unit starts operation without check operation p.339
- Malfunction decision conditions p.339
- Check operation is not executed p.339
- Check operation is executed or not p.339
- Applicable models p.339
- Troubleshooting p.339
- Supposed causes p.339
- Rxyq5p a 54p a p.339
- Remote controller display p.339
- Outdoor unit check operation not executed p.339
- Supposed causes p.340
- Remote controller display p.340
- Method of malfunction detection p.340
- Malfunction of transmission between indoor units p.340
- Malfunction decision conditions p.340
- Applicable models p.340
- Troubleshooting by indication on the remote controller si34 803 p.341
- Troubleshooting p.341
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.341
- All models of indoor units p.342
- Applicable models p.342
- Troubleshooting p.342
- Supposed causes p.342
- Remote controller display p.342
- Normal transmission does not continue for specified period p.342
- Method of malfunction detection p.342
- Malfunction of indoor unit remote controller transmission connection of two main remote controllers when using 2 remote controllers defect of indoor unit pc board defect of remote controller pc board malfunction of transmission caused by noise p.342
- Malfunction decision conditions p.342
- Indoor unit malfunction of transmission between remote controller and indoor unit p.342
- In case of controlling with 2 remote controller check the system using microcomputer is signal transmission between indoor unit and remote controller main and sub is normal p.342
- Supposed causes p.343
- Remote controller display p.343
- Method of malfunction detection p.343
- Malfunction decision conditions p.343
- Indoor unit malfunction of transmission between outdoor units p.343
- Applicable models p.343
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.344
- Troubleshooting 333 p.344
- Troubleshooting p.344
- Si34 803 troubleshooting by indication on the remote controller p.344
- Troubleshooting p.345
- Supposed causes p.345
- Remote controller display p.345
- Normal transmission does not continue for specified period p.345
- Method of malfunction detection p.345
- Malfunction of transmission between main and sub remote controller connection between sub remote controllers defect of remote controller pc board p.345
- Malfunction decision conditions p.345
- Indoor unit malfunction of transmission between main and sub remote controllers p.345
- In case of controlling with 2 remote controller check the system using microcomputer if signal transmission between indoor unit and remote controller main and sub is normal p.345
- Applicable models p.345
- All models of indoor units p.345
- Applicable models p.346
- All models of indoor units p.346
- When the malfunction decision is made on any other indoor unit within the system concerned p.346
- Troubleshooting p.346
- Supposed causes p.346
- Remote controller display p.346
- Method of malfunction detection p.346
- Malfunction of transmission within or outside of other system malfunction of electronic expansion valve in indoor unit of other system defect of pc board of indoor unit in other system improper connection of transmission wiring between indoor and outdoor unit p.346
- Malfunction decision conditions p.346
- Indoor unit malfunction of transmission between indoor and outdoor units in the same system p.346
- Detect the malfunction signal of any other indoor unit within the system concerned p.346
- Supposed causes p.347
- Remote controller display p.347
- Method of malfunction detection p.347
- Malfunction decision conditions p.347
- Improper combination of indoor and outdoor units indoor units and remote controller p.347
- Applicable models p.347
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.348
- Troubleshooting 337 p.348
- Troubleshooting p.348
- The number of indoor units that can be connected to a single outdoor unit system depends on the model of outdoor unit p.348
- Si34 803 troubleshooting by indication on the remote controller p.348
- Address duplication of centralized controller p.349
- Supposed causes p.350
- Remote controller display p.350
- Method of malfunction detection p.350
- Malfunction of transmission between centralized controller and indoor unit p.350
- Malfunction decision conditions p.350
- Applicable models p.350
- Troubleshooting by indication on the remote controller si34 803 p.351
- Troubleshooting p.351
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.351
- Troubleshooting p.352
- Si34 803 troubleshooting by indication on the remote controller p.352
- Troubleshooting 341 p.352
- Troubleshooting p.353
- The malfunction is determined as soon as the abnormality aforementioned is detected through checking the system for any erroneous connection of units on the check operation p.353
- System is not set yet p.353
- Supposed causes p.353
- Remote controller display p.353
- On check operation the number of indoor units in terms of transmission is not corresponding to that of indoor units that have made changes in temperature p.353
- Note wiring check operation may not be successful if carried out after the outdoor unit has been off for more than 12 hours or if it is not carried out after running all connected indoor units in the fan mode for at least an hour p.353
- Method of malfunction detection p.353
- Malfunction decision conditions p.353
- Improper connection of transmission wiring between indoor outdoor units and outdoor outdoor units failure to execute check operation defect of indoor unit pc board stop valve is left in closed p.353
- Applicable models p.353
- All models of indoor units rxyq5p a 54p a p.353
- Malfunction of system refrigerant system address undefined p.354
- Troubleshooting p.355
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.355
- Troubleshooting by indication on the remote controller si34 803 p.355
- Troubleshooting op central remote controller p.356
- Pc board defect p.356
- Malfunction of transmission between optional controllers for centralized control p.357
- Troubleshooting 347 p.358
- Troubleshooting p.358
- Si34 803 troubleshooting op central remote controller p.358
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.358
- Improper combination of optional controllers for centralized control p.359
- Troubleshooting 349 p.360
- Troubleshooting p.360
- Si34 803 troubleshooting op central remote controller p.360
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.360
- Applicable models p.361
- Address duplication of centralized controller p.361
- Address duplication improper setting p.361
- Two or more units of central remote controllers and intelligent touch controllers are connected and all of them are set to master unit central setting or slave unit central setting two units of schedule timers are connected p.361
- Troubleshooting p.361
- Supposed causes p.361
- Remote controller display p.361
- Method of malfunction detection p.361
- Malfunction decision conditions p.361
- Detect the malfunction according to diii net transmission data p.361
- Central remote controller intelligent touch controller schedule timer p.361
- Troubleshooting 351 p.362
- The master unit central setting connector cn1 x1a is mounted at the factory to independently use a single unit of the intelligent touch controller or a single unit of the central remote controller do not dismount the master unit central setting connector i e use the connector with the factory setting unchanged to independently use the schedule timer insert an independent use setting connector no independent use setting connector has been mounted at the factory insert the connector which is attached to the casing of the main unit in the pc board cn1 x1a independent use connector master unit central setting connector to use two or more central equipment in combination make settings according to the table shown below p.362
- Si34 803 troubleshooting op central remote controller p.362
- Master unit central connector setting table p.362
- Master slave unit setting table p.362
- Combination of intelligent touch controller and central remote controller p.362
- Procedures for detecting broken wires in transmission wiring for control p.363
- Applicable models p.364
- Troubleshooting op unified on off controller p.364
- Supposed causes p.364
- Remote controller display p.364
- Operation lamp blinks p.364
- Method of malfunction detection p.364
- Malfunction decision conditions p.364
- Troubleshooting op unified on off controller si34 803 p.365
- Troubleshooting p.365
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.365
- Supposed causes p.366
- Remote controller display p.366
- Method of malfunction detection p.366
- Malfunction decision conditions p.366
- Display under centralized control blinks repeats single blink p.366
- Applicable models p.366
- Caution be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred p.367
- Troubleshooting op unified on off controller si34 803 p.367
- Troubleshooting p.367
- Troubleshooting 357 p.368
- Si34 803 troubleshooting op unified on off controller p.368
- Unified on off controller p.369
- Under centralized control repeats double blink p.369
- Troubleshooting op unified on off controller si34 803 p.369
- Troubleshooting p.369
- Supposed causes p.369
- Remote controller display p.369
- Method of malfunction detection p.369
- Malfunction decision conditions p.369
- Display under centralized control blinks repeats double blink p.369
- Detect the malfunction according to diii net transmission data p.369
- Central control address group no is not set for indoor unit improper control range setting switch improper wiring of transmission wiring p.369
- Applicable models p.369
- When no central control addresses are set to indoor units when no indoor units are connected within the control range p.369
- Troubleshooting 359 p.370
- Si34 803 troubleshooting op unified on off controller p.370
- Check on connector of fan motor power supply cable 1 turn off the power supply measure the resistance between phases of u v w at the motor side connectors three core wire to check that the values are balanced and there is no short circuiting while connector or relay connector is disconnected p.370
- Check no 2 p.370
- Check no 1 p.370
- 1 turn off the power supply 2 measure the resistance between vcc and each phase of u v w and gnd and each phase at the motor side connectors five core wire to check that the values are balanced within the range of 20 while connector or relay connector is disconnected furthermore to use a multiple meter for measurement connect the probe of negative pole to vcc and that of positive pole to gnd p.370
- Troubleshooting op unified on off controller si34 803 p.371
- Troubleshooting p.371
- Referring to the fault tree analysis fta shown below probe the faulty points p.371
- Check 3 check for causes of rise in high pressure p.371
- Troubleshooting 361 p.372
- Si34 803 troubleshooting op unified on off controller p.372
- Referring to the fault tree analysis fta shown below probe the faulty points p.372
- Check 4 check for causes of drop in low pressure p.372
- Example of connection r 410a type 25 7 thermistor resistance temperature characteristics 27 8 pressure sensor 29 9 method of checking the inverter s power transistors and diode modules 30 p.374
- Wiring diagrams for reference 75 p.374
- Piping installation point 23 p.374
- Piping diagrams 64 p.374
- Part 7 appendix p.374
- Option list 19 p.374
- List of electrical and functional parts 06 p.374
- Rxyq5pay1 p.375
- Piping diagrams p.375
- Outdoor unit p.375
- Rxyq5ptl rxyq5payl p.376
- Rxyq8pay1 p.377
- Rxyq8ptl rxyq8payl p.378
- Rxyq10pa 12pay1 p.379
- Rxyq10p 12ptl rxyq10pa 12payl p.380
- Rxyq14p 16p 18ptl rxyq14pa 16pa 18pay1 rxyq14pa 16pa 18payl p.381
- Electronic expansion valve filter filter p.382
- Φ 15 or less attached piping above φ 19 p.382
- Liquid piping connection port p.382
- Indoor unit p.382
- Heat exchanger p.382
- Gas piping connection port p.382
- Fxcq fxfq fxkq fxsq fxmq fxhq fxaq fxlq fxnq p.382
- Flare connection p.382
- Flare connectio p.382
- Refrigerant pipe connection port diameters p.383
- Liquid side p.383
- Indoor heat exchanger p.383
- Gas side p.383
- Fxmq40p 50p 63p 80p 100p 125pve p.383
- Filter filter p.383
- Electronic expansion valve p.383
- Fxmq125mf 200mf 250mfv1 p.384
- Refrigerant pipe connection port diameters p.384
- Indoor unit p.385
- Fxuq bevq p.385
- Connection unit p.385
- Wiring diagrams for reference p.386
- Si34 803 wiring diagrams for reference p.386
- Rxyq5pay1 rxyq5payl p.386
- Outdoor unit p.386
- Appendix 375 p.386
- Wiring diagrams for reference si34 803 p.387
- Rxyq5ptl p.387
- Notes 1 this wiring diagram is applied only to the outdoor unit 2 field wiring 3 terminal strip connector terminal protective earth screw 4 when using the optional adaptor refer to the installation manual of the optional adaptor 5 for connection wiring to indoor outdoor transmission f1 f2 outdoor outdoor transmission f1 f2 refer to the installation manual 6 how to use bs1 5 and ds1 switch refer to service precaution label on el compo box cover 7 when operating don t shortcircuit the protection device s1ph 8 colors blk black red red blu blue wht white pnk pink ylw yellow brn brown gry gray grn green org orange p.387
- D060626b p.387
- Appendix p.387
- Notes 1 this wiring diagram is applied only to the outdoor unit 2 field wiring 3 terminal strip connector terminal protective earth screw 4 when using the optional adaptor refer to the installation manual of the optional adaptor 5 for connection wiring to indoor outdoor transmission f1 f2 outdoor outdoor transmission f1 f2 outdoor multi transmission q1 q2 only for rxyq refer to the installation manual 6 how to use bs1 5 and ds1 switch refer to service precaution label on el compo box cover 7 when operating don t shortcircuit the protection device s1ph 8 colors blk black red red blu blue wht white pnk pink ylw yellow brn brown gry gray grn green org orange p.388
- Appendix 377 p.388
- Si34 803 wiring diagrams for reference p.388
- Rxyq8pay1 rxyq8payl p.388
- Wiring diagrams for reference si34 803 p.389
- Rxyq8ptl p.389
- Notes 1 this wiring diagram is applied only to the outdoor unit 2 field wiring 3 terminal strip connector terminal protective earth screw 4 when using the optional adaptor refer to the installation manual of the optional adaptor 5 for connection wiring to indoor outdoor transmission f1 f2 outdoor outdoor transmission f1 f2 outdoor multi transmission q1 q2 refer to the installation manual 6 how to use bs1 5 and ds1 switch refer to service precaution label on el compo box cover 7 when operating don t shortcircuit the protection device s1ph 8 colors blk black red red blu blue wht white pnk pink ylw yellow brn brown gry gray grn green org orange p.389
- D060627b p.389
- Appendix p.389
- Si34 803 wiring diagrams for reference p.390
- Rxyq10pay1 rxyq10payl p.390
- Notes 1 this wiring diagram is applied only to the outdoor unit 2 field wiring 3 terminal strip connector terminal protective earth screw 4 when using the optional adaptor refer to the installation manual of the optional adaptor 5 for connection wiring to indoor outdoor transmission f1 f2 outdoor outdoor transmission f1 f2 outdoor multi transmission q1 q2 only for rxyq refer to the installation manual 6 how to use bs1 5 and ds1 switch refer to service precaution label on el compo box cover 7 when operating don t shortcircuit the protection device s1ph s2ph 8 colors blk black red red blu blue wht white pnk pink ylw yellow brn brown gry gray grn green org orange p.390
- Appendix 379 p.390
- Wiring diagrams for reference si34 803 p.391
- Rxyq10ptl p.391
- Notes 1 this wiring diagram is applied only to the outdoor unit 2 field wiring 3 terminal strip connector terminal protective earth screw 4 when using the optional adaptor refer to the installation manual of the optional adaptor 5 for connection wiring to indoor outdoor transmission f1 f2 outdoor outdoor transmission f1 f2 outdoor multi transmission q1 q2 refer to the installation manual 6 how to use bs1 5 and ds1 switch refer to service precaution label on el compo box cover 7 when operating don t shortcircuit the protection device s1ph 8 colors blk black red red blu blue wht white pnk pink ylw yellow brn brown gry gray grn green org orange p.391
- D060629b p.391
- Appendix p.391
- Si34 803 wiring diagrams for reference p.392
- Rxyq12pay1 rxyq12payl p.392
- Notes 1 this wiring diagram is applied only to the outdoor unit 2 field wiring 3 terminal strip connector terminal protective earth screw 4 when using the optional adaptor refer to the installation manual of the optional adaptor 5 for connection wiring to indoor outdoor transmission f1 f2 outdoor outdoor transmission f1 f2 outdoor multi transmission q1 q2 refer to the installation manual 6 how to use bs1 5 and ds1 switch refer to service precaution label on el compo box cover 7 when operating don t shortcircuit the protection device s1ph s2ph 8 colors blk black red red blu blue wht white pnk pink ylw yellow brn brown gry gray grn green org orange p.392
- Appendix 381 p.392
- Wiring diagrams for reference si34 803 p.393
- Rxyq12ptl p.393
- Notes 1 this wiring diagram is applied only to the outdoor unit 2 field wiring 3 terminal strip connector terminal protective earth screw 4 when using the optional adaptor refer to the installation manual of the optional adaptor 5 for connection wiring to indoor outdoor transmission f1 f2 outdoor outdoor transmission f1 f2 outdoor multi transmission q1 q2 refer to the installation manual 6 how to use bs1 5 and ds1 switch refer to service precaution label on el compo box cover 7 when operating don t shortcircuit the protection device s1ph 8 colors blk black red red blu blue wht white pnk pink ylw yellow brn brown gry gray grn green org orange p.393
- D060630b p.393
- Appendix p.393
- Si34 803 wiring diagrams for reference p.394
- Rxyq14pa 16pa 18pay1 rxyq14pa 16pa 18payl p.394
- Notes 1 this wiring diagram is applied only to the outdoor unit 2 field wiring 3 terminal strip connector terminal protective earth screw 4 when using the optional adaptor refer to the installation manual of the optional adaptor 5 for connection wiring to indoor outdoor transmission f1 f2 outdoor outdoor transmission f1 f2 outdoor muli transmission q1 q2 refer to the installation manual 6 how to use bs1 5 and ds1 switch refer to service precaution label on el compo box cover 7 when operating don t shortcircuit the protection device s1ph s3ph 8 colors blk black red red blu blue wht white pnk pink ylw yellow brn brown gry gray grn green org orange p.394
- D060911a p.394
- Appendix 383 p.394
- Ps x1m terminal strip power supply p.395
- A3p v1r diode bridge a2p k84r p.395
- A2p magnetic relay e3hc v1cp safety devices input k9r p.395
- Wiring diagrams for reference si34 803 p.395
- Printed circuit board main printed circuit board inv printed circuit board abc i p p.395
- V1r reactor power module a5p l1r p.395
- Printed circuit board inv push button switch mode set return test reset capacitor dip switch crankcase heater fuse 16a dc450v a2p a5p fuse t 3 5a 250v a1p p.395
- Thermistor liq pipe r6t k3r thermistor accumulator r7t pressure sensor high cool heat selector s1nph k4r pressure sensor low p.395
- Pilotlamp service monitor green p.395
- Thermistor heat exc outlet r5t p.395
- Phase reversal detect circuit q1rp c1 x1m terminal strip control a1p p.395
- Thermistor heat exc deicer r4t p.395
- Motor fan connector m1f m2f x1a 4a bs1 5 p.395
- Thermistor fin a2p y3s r1t solenoid valve 4 way valve thermistor suction r2t noise filter ferrite core z1c 7c hap thermistor m1c 3c discharge z1f p.395
- Magnetic relay e2hc current sensor a4p a6p a1p t1a k8r p.395
- Thermistor air a1p y2s r1t solenoid valve oil h1p 8p p.395
- Magnetic relay current limiting p.395
- Switching power supply a1p a2p p.395
- Magnetic contactor m1c a2p magnetic contactor m2c m3c magnetic relay k2m k3m magnetic relay y1s magnetic relay y2s magnetic relay y3s magnetic relay e1hc selector switch cool heat s2s pressure switch high k7r p.395
- Selector switch fan cool heat p.395
- M1c 3c p.395
- S1s s1npl k5r p.395
- L1 red l2 wht l3 blu p.395
- Rxyq14p 16p 18ptl p.395
- F1u f2u p.395
- Resistor current sensor a5p p.395
- Electronic expansion valve main p.395
- Resistor current sensor a2p y1s solenoid valve hotgas r502 p.395
- E1hc 3hc p.395
- Resistor current sensor a2p f1u y2e r112 p.395
- Appendix p.395
- Resistor current limiting ds1 x1m terminal strip abc i p a3p r1 p.395
- A5p motor compressor power module a2p p.395
- Appendix 385 p.396
- Si34 803 wiring diagrams for reference p.396
- Rxyq5pa 8pa 10pa 12pa 14pa 16pa 18pay1 rxyq5pa 8pa 10pa 12pa 14pa 16pa 18payl p.396
- Field wiring p.396
- Wiring diagrams for reference si34 803 p.397
- Rxyq5p 8p 10p 12p 14p 16p 18ptl p.397
- Appendix p.397
- Si34 803 wiring diagrams for reference p.398
- Rxyq20pa 22pa 24pa 26pa 28pa 30pa 32pay1 rxyq20pa 22pa 24pa 26pa 28pa 30pa 32payl p.398
- Appendix 387 p.398
- Wiring diagrams for reference si34 803 p.399
- Rxyq20p 22p 24p 26p 28p 30p 32ptl p.399
- Appendix p.399
- Si34 803 wiring diagrams for reference p.400
- Rxyq34pa 36pa 38pa 40pa 42pa 44pa 46pa 48pa 50pa 52pa 54pay1 rxyq34pa 36pa 38pa 40pa 42pa 44pa 46pa 48pa 50pa 52pa 54payl p.400
- Appendix 389 p.400
- Appendix p.401
- Wiring diagrams for reference si34 803 p.401
- Rxyq34p 36p 38p 40p 42p 44p 46p 48p 50p 52p 54ptl p.401
- Indoor unit p.402
- Fxfq25p 32p 40p 50p 63p 80p 100p 125pve p.402
- When connecting the input wires from outside forced off or on off control operation can be selected by the remote controller see installation manual for more details 5 confirm the method of setting the selector switch ss1 ss2 by installation manual and engineering data etc 6 symbols shows as follows red red blk black wht white ylw yellow grn green org orange brn brown pnk pink gry gray blu blue p.402
- Fuse f 5a 250v p.402
- Thermistor ptc p.402
- Float switch p.402
- Thermistor coil liquid p.402
- Ferrite core p.402
- Thermistor air p.402
- Electronic expansion valve p.402
- Terminal strip p.402
- Diode bridge p.402
- Si34 803 wiring diagrams for reference p.402
- Service monitor green p.402
- D059890 p.402
- Selector switch wireless address set p.402
- Connector for optional parts p.402
- Selector switch main sub p.402
- Capacitor p.402
- S1l v1r p.402
- C1 f1u p.402
- Notes 1 terminal connector field wiring 2 in case using central remote controller connect it to the unit in accordance with the attached installation manual 3 x24a x33a and x35a are connected when the optional accessories are being used p.402
- Appendix 391 p.402
- Noise filter p.402
- A4p a3p p.402
- Magnetic relay p.402
- A1p a2p p.402
- M1s r1t r2t r3t r4t p.402
- Light emitting diode p.402
- Fxcq20m 25m 32m 63mve p.403
- Fxcq40m 50m 80m 125mve p.404
- Fxkq25ma 32ma 40ma 63mave p.405
- Si34 803 wiring diagrams for reference p.406
- Fxdq20pb 25pb 32pb fxdq40nb 50nb 63nbve with drain pump p.406
- Appendix 395 p.406
- Wiring diagrams for reference si34 803 p.407
- Fxdq20pb 25pb 32pb fxdq40nb 50nb 63nbvet without drain pump p.407
- Appendix p.407
- Kpr m1f m1p q1m p.408
- Kcr kfr khr khur p.408
- Indoor unit printed circuit board a1p a2p c1 f1u hap p.408
- Humidistat terminal block e1h wired remote controller thermistor air selector switch main sub adaptor for wiring fuse 5a 250v magnetic relay magnetic relay magnetic relay e1h magnetic relay hu connector for optional parts connector adaptor for wiring connector wiring adaptor for electorical appendices p.408
- Hu k1m s1h x3m p.408
- Fxsq20m 25m 32m 40m 50m 63m 80m 100m 125mve p.408
- D039561b p.408
- Appendix 397 p.408
- X16a x18a p.408
- Terminal board capacitor m1f fuse 5a 250v p.408
- Si34 803 wiring diagrams for reference p.408
- S1l t1r x1m x2m y1e p.408
- R1t ss1 p.408
- Notes 1 terminal block connector terminal 2 field wiring 3 in case using central remote controller connect it to the unit in accordance with the attached instruction manual 4 when connecting the input wires from outside fdrced off or on off control operation can be selected by remote controller in details refer to the installation manual attached the unit 5 in case installing the electric heater execute the additional wiring for heater circuit k1m e1h in this case the main power supply has to be supplied independently 6 in case high or low e s p operation change over the wiring connection from x4a of a2p to x3a or x5a 7 symbols show as follows pnk pink wht white ylw yellow gry gray org orange blu blue blk black red red brn brown grn green 8 use copper conductors only 9 only 80 100 125 type p.408
- Magnetic relay m1f magnetic relay m1p motor indoor fan motor drain pump thermo switch 135 c or 145 c note9 m1f embedded thermistor air thermistor coil float switch transformer 220 240v 22v terminal block power terminal block control electronic expansion valve optional parts electric heater fuse 15a 250v humidifier p.408
- Magnetic relay e1h p.408
- R1t ss1 p.409
- Fuse t 3 5a 250v p.409
- Printed circuit board fan p.409
- Float switch p.409
- Printed circuit board capacitor p.409
- F3u f2u p.409
- Wiring diagrams for reference si34 803 p.409
- Printed circuit board p.409
- Electronic expansion valve p.409
- Wired remote controller p.409
- Power module p.409
- Diode bridge p.409
- V2r x1m p.409
- Notes 1 terminal connector field wiring 2 in case using central remote controller connect it to the unit in accordance with the attached installation manual 3 when connecting the input wires from outside forced off or on off control operation can be selected by remote controller in details refer to the installation manual attached the unit 4 colors blk black red red blu blue wht white pnk pink ylw yellow brn brown gry gray grn green org orange p.409
- Connector for wiring p.409
- Thermistor liquid p.409
- Capacitor p.409
- Thermistor gas p.409
- Noise filter ferrite core p.409
- Appendix p.409
- Thermistor discharge air p.409
- Noise filter p.409
- Thermistor air p.409
- Motor fan p.409
- Terminal strip power supply p.409
- Motor drain pump p.409
- Terminal strip control p.409
- Magnetic relay p.409
- Switching power supply a1p a2p resistor current limiting current sensing device p.409
- Kpr k1r l1r m1f m1p p.409
- Selector switch main sub p.409
- Indoor unit p.409
- Reactor p.409
- Fxmq40p 50p 63p 80p 100p 125pve p.409
- R3t r4t p.409
- Fuse t 6 a 250v fuse t 6 a 250v p.409
- R3 r4 connector optional accessory p.409
- Fuse t 5a 250v p.409
- Fxmq200ma 250mave p.410
- Fxhq32ma 63ma 100mave p.411
- Si34 803 wiring diagrams for reference p.412
- Fxaq20ma 25ma 32mave 40ma 50ma 63mave p.412
- Appendix 401 p.412
- Fxlq20ma 25ma 32ma 40ma 50ma 63mave fxnq20ma 25ma 32ma 40ma 50ma 63mave p.413
- Fxuq71ma 100ma 125mav1 p.414
- Fxmq125mf 200mf 250mfv1 p.415
- Bevq71ma 100ma 125mave p.416
- Rxyq5pay1 8pay1 p.417
- Outdoor unit p.417
- List of electrical and functional parts p.417
- Rxyq10pay1 12pay1 p.418
- Rxyq5 8payl ptl p.420
- Outdoor unit 60hz p.420
- Rxyq10 12payl ptl p.421
- Rxyq14 16 18payl ptl p.422
- Appendix p.423
- List of electrical and functional parts si34 803 p.423
- Indoor unit p.423
- Indoor side p.423
- C off 87 c on p.423
- Si34 803 list of electrical and functional parts p.424
- Only for fxdq20 63n b ve fxdq20 32pbve with drain pump type p.424
- Appendix 413 p.424
- List of electrical and functional parts si34 803 p.425
- Appendix p.425
- Μ f 400v p.426
- St8605 6 φ 8 p.426
- St8602a 6 φ 6 p.426
- Si34 803 list of electrical and functional parts p.426
- K ω 25 c p.426
- Appendix 415 p.426
- Appendix p.427
- List of electrical and functional parts si34 803 p.427
- Si34 803 list of electrical and functional parts p.428
- Thermal protector 130 c off 83 c on p.428
- Appendix 417 p.428
- List of electrical and functional parts si34 803 p.429
- Appendix p.429
- Various pc boards p.430
- Option list of controllers p.430
- Option list p.430
- Operation control system optional accessories p.430
- Note 1 installation box no is necessary for each adaptor marked p.430
- Fxdq nb fxdq pb p.430
- 2 up to 2 adaptors can be fixed for each installation box 3 only one installation box can be installed for each indoor unit 4 up to 2 installation boxes can be installed for each indoor unit 5 installation box no 8 is necessary for second adaptor 6 installation box no 8 is necessary for each adaptor 7 this adaptor is required when connecting with optional controller for centralized control 8 brc2a51 is also available p.430
- 2 interface for use in lonwork p.431
- Unification adaptor for computerized control dcs302a52 p.431
- Dms502b51 p.431
- 1 optional diii board dam411b51 p.431
- Temperature setting units dpf201a53 p.431
- Contact analog signal p.431
- 1 interface for use in bacne p.431
- Temperature measurement units dpf201a52 p.431
- Communication line p.431
- System configuration p.431
- Building management system p.431
- Parallel interface basic unit dpf201a51 p.431
- Basic hardware number of units to be connected p.431
- P p d dam002a51 p.431
- Basic hardware intelligent touch controller dcs601c51 p.431
- Option software p.431
- Appendix p.431
- Option list si34 803 p.431
- 6 dio unit dec102a51 p.431
- Option p.431
- 5 di unit dec101a51 p.431
- Note 1 installation box for adaptor must be obtained locally 2 for residential use only cannot be used with other centralized control equipment p.431
- 4 optional diii ai unit dam101a51 p.431
- Note 1 bacne p.431
- 4 electrical box with earth terminal 4 blocks kjb411a p.431
- Is a registered trademark of american society of heating refrigerating and air conditioning engineers ashrae 2 lonwork p.431
- 3 web dcs004a51 p.431
- Is a registered trade mark of echelon corporation 3 installation box for adaptor must be procured on site p.431
- 3 eco dam003a51 p.431
- Intelligent manager iii p.431
- 2 web dam004a51 p.431
- Hardware diii net plus adaptor dcs601a52 p.431
- 2 software p p d dcs002c51 p.431
- Units dam602b52 p.431
- Dms504b51 p.431
- 2 optional di board dam412b51 p.431
- Units dam602b51 512 units dam602b51x2 768 units dam602b51x3 1024 units dam602b51x4 2 1 p.431
- Si34 803 option list p.432
- Rxyq5 18pay1 payl ptl p.432
- Rxyq38 54pay1 payl ptl p.432
- Rxyq20 36pay1 payl ptl p.432
- Option lists outdoor unit p.432
- Note order products p.432
- Appendix 421 p.432
- Rxyq32 50pahy1 pahyl phtl p.433
- Rxyq24 30pahy1 pahyl phtl p.433
- Rxyq16 18pahy1 pahyl phtl p.433
- Option list si34 803 p.433
- Note order products p.433
- Appendix p.433
- Appendix 423 p.434
- When the piping length between the multi connection kits or between multi connection kit and outdoor unit is 2m or more prepare a vertical projection part 200mm or more as shown below only on the gas pipe line location less than 2m from multi connection kit p.434
- The projection part between multi connection piping kits p.434
- Since there is a possibility that oil may be collected on a stop machine side install piping between outdoor units to go to level or go up to an outdoor unit and to make a slope p.434
- Si34 803 piping installation point p.434
- Piping installation point p.434
- In the case of 2m or more p.434
- In the case of 2m or less p.434
- The example of a wrong pattern p.435
- Refrigerant branch kit selection p.436
- Pipe size selection p.436
- Example refrigerant branch using refnet joint and refnet header p.436
- Example refrigerant branch using refnet joint p.436
- Example refrigerant branch using refnet header p.436
- Example of connection r 410a type p.436
- Example of connection p.436
- Appendix 425 p.436
- Si34 803 example of connection r 410a type p.436
- Note 3 p.437
- Note 2 p.437
- Note 1 p.437
- How to calculate the additional refrigerant to be charged p.437
- Diameter of above case p.437
- Thermistor resistance temperature characteristics p.438
- Si34 803 thermistor resistance temperature characteristics p.438
- Outdoor unit for outdoor air r1t for coil r2t for suction pipe r4t for receiver gas pipe r5t for receiver outlet liquid pipe r6t p.438
- Outdoor unit for fin thermistor r1t p.438
- Indoor unit for air suction r1t for liquid pipe r2t for gas pipe r3t p.438
- Appendix 427 p.438
- Thermistor resistance temperature characteristics si34 803 p.439
- Outdoor unit thermistors for discharge pipe r3t r3 p.439
- Appendix p.439
- Pressure sensor p.440
- Method of checking the inverter s power transistors and diode modules p.441
- When using the digital type of multiple tester make measurement in diode check mode p.442
- When using the analog type of multiple tester make measurement in resistance measurement mode in the x1k ω range p.442
- Power module checking p.442
- Diode module checking p.442
- Precautions for new refrigerant r 410a 34 p.444
- Precautions for new refrigerant r 410a p.444
- Part 8 precautions for new refrigerant r 410a p.444
- Part 8 p.444
- Precautions for new refrigerant r 410a p.445
- Outline p.445
- Characteristics of new refrigerant r 410a 1 performance almost the same performance as r 22 and r 407c 2 pressure working pressure is approx 1 times more than r 22 and r 407c 3 refrigerant composition few problems in composition control since it is a quasi azeotropic mixture refrigerant p.445
- About refrigerant r 410a p.445
- 1 non azeotropic mixture refrigerant mixture of two or more refrigerants having different boiling points 2 quasi azeotropic mixture refrigerant mixture of two or more refrigerants having similar boiling points 3 the design pressure is different at each product please refer to the installation manual for each product reference 1 mpa 10 9716 kgf c p.445
- Si34 803 precautions for new refrigerant r 410a p.446
- Precautions for new refrigerant r 410a 435 p.446
- Thermodynamic characteristic of r 410a p.446
- Refrigerant cylinders p.447
- Φ 6 φ 9 φ 12 φ 15 φ 19 φ 22 φ 25 φ 28 φ 31 φ 38 φ 44 p.448
- Ve up r 407c p.448
- Tool compatibility p.448
- Thickness t mm 0 0 0 1 1 1 1 1 1 1 1 p.448
- Service tools p.448
- R 410a is used under higher working pressure compared to previous refrigerants r 22 r 407c furthermore the refrigerating machine oil has been changed from suniso oil to ether oil and if oil mixing is occurred sludge results in the refrigerants and causes other problems therefore gauge manifolds and charge hoses that are used with a previous refrigerant r 22 r 407c can not be used for products that use new refrigerants be sure to use dedicated tools and devices p.448
- R 410a p.448
- Pipe size p.448
- O soft annealed h hard drawn p.448
- O o o o o 1 2h 1 2h 1 2h 1 2h 1 2h 1 2h p.448
- O o o o 1 2h 1 2h 1 2h 1 2h 1 2h 1 2h 1 2h p.448
- Material p.448
- Copper tube material and thickness p.448
- As for the charge mouthpiece and packing 1 2unf20 is necessary for mouthpiece size of charge hose p.448
- Unit mm p.449
- Specifications 2 dimension a p.449
- Flaring tool p.449
- Differences 2 change of dimension a p.449
- Conventional flaring tools can be used when the work process is changed change of work process previously a pipe extension margin of 0 to 0 mm was provided for flaring for r 410a air conditioners perform pipe flaring with a pipe extension margin of 1 to 1 mm for clutch type only conventional tool with pipe extension margin adjustment can be used p.449
- Can not be used p.452
- Drawings flow charts p.456
- Use only those parts and accessories supplied or specified by daikin ask a qualified installer or contractor to install those parts and accessories use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage electrical shock fire or explosion p.458
- Read the user s manual carefully before using this product the user s manual provides important safety instructions and warnings be sure to follow these instructions and warnings p.458
- Printed in japan 06 2008 ak si34 803 p.458
- If you have any enquiries please contact your local importer distributor and or retailer p.458
- Http www daikin com global_ac p.458
- Daikin industries ltd s products are manufactured for export to numerous countries throughout the world daikin industries ltd does not have control over which products are exported to and used in a particular country prior to purchase please therefore confirm with your local authorised importer distributor and or retailer whether this product conforms to the applicable standards and is suitable for use in the region where the product will be used this statement does not purport to exclude restrict or modify the application of any local legislation p.458
- Cautions on product corrosion p.458
- Ask a qualified installer or contractor to install this product do not try to install the product yourself improper installation can result in water or refrigerant leakage electrical shock fire or explosion p.458
Похожие устройства
-
Daikin RXYQ54PYLСервис мануал -
Daikin RXYQ52PYLСервис мануал -
Daikin RXYQ50PYLСервис мануал -
Daikin RXYQ48PYLСервис мануал -
Daikin RXYQ46PYLСервис мануал -
Daikin RXYQ44PYLСервис мануал -
Daikin RXYQ42PYLСервис мануал -
Daikin RXYQ40PYLСервис мануал -
Daikin RXYQ38PYLСервис мануал -
Daikin RXYQ36PYLСервис мануал -
Daikin RXYQ34PYLСервис мануал -
Daikin RXYQ32PYLСервис мануал



















