Daikin FXSQ32MVE [211/458] Setting contents and code no vrv indoor unit

Daikin FXSQ32MVE [211/458] Setting contents and code no vrv indoor unit
Field Setting Si34-803
200 Test Operation
3.1.4 Setting Contents and Code No. – VRV Indoor unit
Notes : 1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so
they cannot be set individually. Setting changes also cannot be checked.
3. Marked are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. “88” may be displayed to indicate the remote controller is resetting when returning to the
normal mode.
6. If the setting mode to “Equipped”, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
7. The FXMQ50·63·80·100·125PVE cannot be set to 30Pa.
The FXMQ40PVE cannot be set to 180 or 200Pa.
VRV
system
indoor
unit
settings
Mode
No.
Note 2
Setting
Switch
No.
Setting Contents
Second Code No.(Note 3)
Details
No.
01 02 03 04
10
(20)
0
Filter contamination
heavy/light (Setting for
display time to clean air
filter)
(Sets display time to clean
air filter to half when there
is heavy filter
contamination.)
Super
long life
filter
Light
Approx.
10,000
hrs.
Heavy
Approx.
5,000
hrs.
——
(1)Long life
filter
Approx.
2,500
hrs.
Approx.
1,250
hrs.
Standard
filter
Approx.
200 hrs.
Approx.
100 hrs.
1 Long life filter type Long life filter
Super long life
filter
——(2)
2
Thermostat sensor in remote
controller
Use No use (3)
3
Display time to clean air filter calculation
(Set when filter sign is not to be displayed.)
Display No display (4)
11
(21)
7 Airflow adjustment OFF
Completion of
airflow
adjustment
Start of airflow
adjustment
—(5)
12
(22)
0
Optional accessories output selection (field
selection of output for adaptor for wiring)
Indoor unit turned
ON by thermostat
Operation
output
Malfunction
output
(6)
1
ON/OFF input from outside (Set when ON/
OFF is to be controlled from outside.)
Forced OFF ON/OFF control
External protection
device input
—(7)
2
Thermostat differential changeover
(Set when remote sensor is to be used.)
1°C 0.5°C (8)
3 OFF by thermostat fan speed LL Set fan speed (9)
4
Automatic mode differential
(automatic temperature differential
setting for VRV system heat
recovery series cool/heat)
01:0 02:1 03:2 04:3 05:4 06:5 07:6 08:7 (10)
5 Power failure automatic reset Not equipped Equipped (11)
6
Airflow When Cooling Thermostat is OFF
LL air flow Preset air flow (12)
13
(23)
0
High air outlet velocity
(Set when installed in place with
ceiling higher than 2.7 m.)
N H S (13)
1
Selection of air flow direction (Set when
a blocking pad kit has been installed.)
F (4 directions) T (3 directions) W (2 directions) (14)
3
Air flow direction adjustment (Set at
installation of decoration panel.)
Equipped Not equipped (15)
4 Field set air flow position setting Draft prevention Standard
Ceiling Soiling
prevention
(16)
5
Setting of the Static Pressure
Selection
Standard
High static
pressure
(17)
6 External Static Pressure Settings
01:30 02:50 03:60 04:70 05:80 06:90 07:100 08:110
(18)
09:120 10:130 11:140 12:150 13:160 14:180 15:200 *7
15
(25)
1 Thermostat OFF excess humidity Not equipped Equipped (19)
2
Direct duct connection
(when the indoor unit and heat
reclaim ventilation unit are
connected by duct directly.) Note 6
Not equipped Equipped (20)
3
Drain pump humidifier interlock selection
Not equipped Equipped (21)
5
Field set selection for individual
ventilation setting by remote controller
Not equipped Equipped (22)