Daikin FXSQ32MVE [304/458] Troubleshooting

Daikin FXSQ32MVE [304/458] Troubleshooting
Si34-803 Troubleshooting by Indication on the Remote Controller
Troubleshooting 293
Troubleshooting
Note: Refer to check 1 and 2 on P.359.
Check 1
Check for the fan motor
connector (Power supply cable)
Check 2
Check for the fan motor
connector (Signal cable)
NO
NO
Resistance
of the U, V, and W
phases of the fan motor
has got imbalanced or short
circuits have been established
amoung the U, V,
and W
phases.
YES
Turn ON the power supply.
NO
Has a
short circuit been
established between
the fan motor signal cables
Vcc and GND, and UVW
and GND,
respectively?
YES
The LED
(HAP) on the
compressor inverter PC
board is blinking, but the LED
(HAP) on the fan inverter
PC board is not
blinking.
YES
Replace the outdoor unit fan
motor.
Replace the outdoor unit fan
motor.
Replace the fan inverter PC
board.
Replace the outdoor unit fan
motor.
A