Daikin FXSQ32MVE [389/458] Rxyq8ptl

Daikin FXSQ32MVE [389/458] Rxyq8ptl
Wiring Diagrams for Reference Si34-803
378 Appendix
RXYQ8PTL
*
:
*
IS DISCRIMINATION COLOR FOR
COMPONENT LEAD WIRE.
*
:
*
IS CONNECTOR COLOR FOR COMPONENT.
*
:
*
IS CONNECTOR COLOR FOR
PRINTED CIRCUIT BOARD.
POWER SUPPLY
220V 3~60Hz
L1
L3
L2
L3X1M L2L1
RED
BLU
WHT
+
+
+
+
-
-
-
K84R
C1
BLKBLK
L1R
P2
P3
N3
P1
K1M
K2M
R1
V1R
X7A
X6A
X4A
BLU
GRN
RED
A2P
WHT
E1L3AL1A L2A
PS
Z1F
BLK
W
V
RED
Z1C
N=4
BLK
X1A
5
X2A
WHT
M1C
WHT
M1F
U
5
RED
Z2C
MS
3~
MS
3~
V
U
W
R112
V2R
R502F1U
V3R
X501A
X504A
X502A
X28A
N=3
Z3C
X20A
R1T
WHT
X1A
BLU
A1P
RED
X4A
X2A
V1CP
P<
Q1RP
X3A
S1PH
F1U
F2U
X7A X9A
K5R
X8A
Y2S Y3SY1S
K4R
K3R
K7R
E1HC
X11A
H7P H8P
1234
H6P
DS1
OFF
ON
H4PH3P H5P
X37A
HAP
NOTE) 4.
H1P
BS4BS2 BS5BS1 BS3
H2P
PS
R4T
R7TR2TR3T R5T R6T
outdoor (Q1) (Q2)
indoor (F1) (F2)
outdoor (F1) (F2)
X31A
M
S1NPL
X23A
IN-OUT
Y1E
5
Q1
NOTE) 5.
OUT-OUT
R1T
Y2E
BLU
Q2F2
X32A
5
X1M
M
F1
t
˚
S1NPH
X21A
F1
OUT-MULTI
X18A
F2
BLUWHT
X30AX29A11
X66A
S1S
X1M
COOL/HEAT SELECTOR
A3P
HEAT
X1A
C
FAN
COOL
S2S
AB
HEAT
COOL
LAYOUT OF M1C, M1F
TERMINAL OF M1C
W
V
U
EL. COMPO. BOX
X1M
A1P
(FRONT)
X2A
A3P
X1M
X1A
(BACK)
M1F
EL. COMPO. BOX
OUTER SHELL
M1C
COOL/HEAT SELECTOR
(OPTIONAL ACCESSORY)
L2-WHT L3-BLUL1-RED
A1P
A2P
A3P
BS1~5
C1
DS1
E1HC
F1U
F1U, F2U
H1P~8P
HAP
K1M, K2M
K3R
K4R
K5R
K7R
K84R
PRINTED CIRCUIT BOARD (MAIN)
PRINTED CIRCUIT BOARD (INV)
PRINTED CIRCUIT BOARD (ABC I/P)
PUSH BUTTON SWITCH
(MODE, SET, RETURN, TEST, RESET)
CAPACITOR
DIP SWITCH
CRANKCASE HEATER
FUSE (16A, DC450V) (A2P)
FUSE (T, 3.15A, 250V) (A1P)
PILOTLAMP (SERVICE MONITOR-ORANGE)
[H2P] PREPARE,TEST------------FLICKERING
MALFUNCTION DETECTION---LIGHT UP
PILOTLAMP (SERVICE MONITOR-GREEN)
MAGNETIC CONTACTOR (M1C) (A2P)
MAGNETIC RELAY (Y1S)
MAGNETIC RELAY (Y2S)
MAGNETIC RELAY (Y3S)
MAGNETIC RELAY (E1HC)
MAGNETIC RELAY (CURRENT LIMITING)
L1R
M1C
M1F
PS
Q1RP
R1
R112
R502
R1T
R1T
R2T
R3T
R4T
R5T
R6T
R7T
S1NPH
S1NPL
S1PH
V1CP
REACTOR
MOTOR (COMPRESSOR)
MOTOR (FAN)
SWITCHING POWER SUPPLY (A1P,A2P)
PHASE REVERSAL DETECT CIRCUIT
RESISTOR (CURRENT LIMITING)
RESISTOR (CURRENT SENSOR) (A2P)
RESISTOR (CURRENT SENSOR) (A2P)
THERMISTOR (AIR) (A1P)
THERMISTOR (FIN) (A2P)
THERMISTOR (SUCTION)
THERMISTOR (M1C DISCHARGE)
THERMISTOR (HEAT EXC. DEICER)
THERMISTOR (HEAT EXC. OUTLET)
THERMISTOR (LIQ. PIPE)
THERMISTOR (ACCUMULATOR)
PRESSURE SENSOR (HIGH)
PRESSURE SENSOR (LOW)
PRESSURE SWITCH (HIGH)
SAFETY DEVICES INPUT
V1R
V2R, V3R
X1A, X2A
X1M
X1M
X1M
Y1E
Y2E
Y1S
Y2S
Y3S
Z1C~3C
Z1F
COOL/HEAT SELECTOR
S1S
S2S
DIODE BRIDGE (A2P)
POWER MODULE (A2P)
CONNECTOR (M1F)
TERMINAL STRIP (POWER SUPPLY)
TERMINAL STRIP (CONTROL) (A1P)
TERMINAL STRIP (ABC I/P) (A3P)
ELECTRONIC EXPANSION VALVE (MAIN)
ELECTRONIC EXPANSION VALVE (SUBCOOL)
SOLENOID VALVE (HOT GAS)
SOLENOID VALVE (OIL)
SOLENOID VALVE (4 WAY VALVE)
NOISE FILTER (FERRITE CORE)
NOISE FILTER (WITH SURGE ABSORBER)
SELECTOR SWITCH (FAN/COOL · HEAT)
SELECTOR SWITCH (COOL/HEAT)
NOTES)
1. THIS WIRING DIAGRAM IS APPLIED ONLY TO THE OUTDOOR UNIT.
2. : FIELD WIRING.
3. : TERMINAL STRIP : CONNECTOR : TERMINAL : PROTECTIVE EARTH (SCREW)
4. WHEN USING THE OPTIONAL ADAPTOR, REFER TO THE INSTALLATION MANUAL OF THE OPTIONAL ADAPTOR.
5. FOR CONNECTION WIRING TO INDOOR-OUTDOOR TRANSMISSION F1 · F2, OUTDOOR-OUTDOOR
TRANSMISSION F1 · F2, OUTDOOR-MULTI TRANSMISSION Q1 · Q2, REFER TO THE INSTALLATION MANUAL.
6. HOW TO USE BS1~5 AND DS1 SWITCH, REFER TO "SERVICE PRECAUTION" LABEL ON EL. COMPO. BOX COVER.
7. WHEN OPERATING, DON' T SHORTCIRCUIT THE PROTECTION DEVICE (S1PH).
8. COLORS BLK : BLACK RED : RED BLU : BLUE WHT : WHITE PNK : PINK YLW : YELLOW BRN : BROWN
GRY : GRAY GRN : GREEN ORG : ORANGE.
L1R
A2P
3D060627B

Содержание

Скачать