Daikin FXSQ32MVE [350/458] Malfunction of transmission between centralized controller and indoor unit

Daikin FXSQ32MVE [350/458] Malfunction of transmission between centralized controller and indoor unit
Si34-803 Troubleshooting by Indication on the Remote Controller
Troubleshooting 339
3.55
UE
Malfunction of Transmission Between Centralized
Controller and Indoor Unit
Remote
Controller
Display
UE
Applicable
Models
All models of indoor units Intelligent Touch Controller
Centralized controller
Schedule timer
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized controller is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control and indoor
unit
Connector for setting master controller is disconnected.
(or disconnection of connector for independent / combined use changeover switch.)
Failure of PC board for central remote controller
Defect of indoor unit PC board