Daikin FXSQ32MVE [235/458] 8 8 7 7 8

Daikin FXDQ32NAVE [235/458] 8 8 7 7 8
Field Setting Si34-803
224 Test Operation
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
*1: Number of connected indoor units
Used to make setting of the number of indoor units connected to an outdoor
unit.
*2: Number of connected BS units
Used to make setting of the number of BS units connected to an outdoor
unit.
*3: Number of outdoor units
Used to make setting of the number of outdoor units connected to DIII-NET
that is one of the communication lines.
*4: Number of BS units
Used to make setting of the number of BS units connected to DIII-NET that is
one of the communication lines.
*5: Number of terminal units
Used to make setting of the number of indoor units connected to DIII-NET
that is one of the communication lines.
(Only available for VRV indoor units)
No.
Setting item
LED display
Data display
H1P H2P H3P H4P H5P H6P H7P
0 Various settings
9777777
Lower 4 digits
1 C/H unified address
9777778
Lower 6 digits
2 Low noise/demand address
9777787
3 Not used
9777788
4 Airnet address
9777877
5
Number of connected indoor units
*1
9777878
6
Number of connected BS units *2
9777887
7
Number of connected zone units
(Fixed to "0")
9777888
8 Number of outdoor units *3
9778777
9
Number of BS units *4
9778778
Lower 4 digits:
upper
10
Number of BS units *4
9778787
Lower 4 digits:
lower
11 Number of zone units
9778788
Lower 6 digits
12 Number of terminal units *5
9778877
Lower 4 digits:
upper
13 Number of terminal units *5
9778878
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
9778887
Malfunction
code table
Refer page
256.
15
Contents of malfunction
(1 cycle before)
9778888
16
Contents of malfunction
(2 cycle before)
9787777
20 Contents of retry (the latest)
9787877
21 Contents of retry (1 cycle before)
9787878
22 Contents of retry (2 cycle before)
9787887
25
Number of multi connection
outdoor units
9788778
Lower 6 digits
c. Monitor mode
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
Push the MODE (BS1) button and
returns to “Setting mode 1”.