Daikin FXSQ32MVE [348/458] Troubleshooting

Daikin FXDQ63NBVE4 [348/458] Troubleshooting
Si34-803 Troubleshooting by Indication on the Remote Controller
Troubleshooting 337
Troubleshooting
The number of indoor units that can be connected to a single outdoor unit system depends on
the model of outdoor unit.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The total
of indoor units
displaying "UA" and
indoor units connected to the
same refrigerant system is
within connectable
number of
unit
NO
The number of indoor units that
can be connected to a single
outdoor unit system is excess of
allowable range.
Is the outdoor
PC board replaced
to spare parts PC
board ?
YES
The setting after replacing spare
PC board has not been set yet.
Please set as per page 218, 219.
Correct the combination of indoor
units with "UA" displayed.
Normal
(It is assumed that the code is
displayed due to temporary
external cause (e.g. noises).
NO
YES
Replace the outdoor unit main PC
board.
Matches the refrigerant type of
indoor and outdoor unit.
Replace the indoor unit PC board.
NO
YES
Does the
refrigerant type of indoor
and outdoor unit
match?
YES
Replace the outdoor unit main PC
board.
NO
Is it a multi
outdoor unit connection
system?
YES
Change to a correct combination.
NO
Is the
combination of master
unit and slave unit
correct?
NO
Is the
malfunction code "UA"
displayed?
Reset all power supplies for
indoor and outdoor units
connected to one and the
same system.
Is the
malfunction code
"UA" displayed for all
indoor units connected to
one and the same
system?
Is
the type of
refrigerant for the
indoor units with "UA"
displayed corresponding
to that for the
outdoor
units?
NO
YES
NO
YES
YES