Daikin FXSQ32MVE [356/458] Troubleshooting op central remote controller

Daikin FXSQ32MVE [356/458] Troubleshooting op central remote controller
Si34-803 Troubleshooting (OP: Central Remote Controller)
Troubleshooting 345
4. Troubleshooting (OP: Central Remote Controller)
4.1
M1
PC Board Defect
Remote
Controller
Display
M1
Applicable
Models
Central remote controller
Schedule timer
Method of
Malfunction
Detection
Detect an abnormality in the DIII-NET polarity circuit.
Malfunction
Decision
Conditions
When + polarity and - polarity are detected at the same time.
Supposed
Causes
Defect of central remote controller PC board
Defect of Schedule timer PC board
Troubleshooting
Replace the central remote controller.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the M1 displayed again?
Replace the central
equipment.
Central equipment: Normal
It is supposed that the
malfunction results from
external factors (e.g. noises)
from other equipment.
With M1 displayed
Turn ON the power supply of
the central equipment
with M1 displayed once again.
Without M1 displayed