Daikin FXSQ32MVE [421/458] Rxyq10 12payl ptl

Daikin RXYQ8P9W1B [421/458] Rxyq10 12payl ptl
List of Electrical and Functional Parts Si34-803
410 Appendix
3.2.2 RXYQ10 / 12PAYL, PTL
Item Name Symbol
Model
RXYQ10PAYL RXYQ12PAYL
Compressor
Inverter
Type
M1C
JT1GCVDKYR@SB
OC protection
device
14.7A
STD 1
Type
M2C
JT170G-KYH@T
OC protection
device
15.0A
STD 2
Type
M3C
OC protection
device
Fan motor
OC protection
device
M1F 3A 1.15A
M2F 1.15A
Item Name Symbol
Model
RXYQ10PTL RXYQ12PTL
Compressor
Inverter
Type
M1C
JT100GCVDK@SB
OC protection
device
26.5A
STD 1
Type
M2C
JT170G-K
OC protection
device
28.8A
STD 2
Type
M3C
OC protection
device
Fan motor
OC protection
device
M1F 5.5A 2.3A
M2F 2.3A
Electronic expansion valve (Main) Y1E Fully closed: 0pls Fully open: 480pls
Electronic expansion valve (Subcool) Y2E Fully closed: 0pls Fully open: 480pls
Pressure
protection
High pressure
switch
For M1C S1PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M2C S2PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M3C S3PH
Low pressure sensor SLNPL OFF: 0.07MPa
Temperature
protection
Discharge gas temperature
protection
(Discharge pipe thermistor)
R3T OFF: 135°C
Inverter fin temperature
protection
(Radiator fin thermistor)
R1T OFF: 93°C
Others Fuse
For main PC
board
A1P 250V, 15A
A2P 250V, 3A (PTL : 250V, 15A)
For Noise filter
PC board
F1U
250V AC 6.3A Class B
(No fuse for TL model)
+0
0.12
+0
0.12

Содержание

Скачать