Daikin FXSQ32MVE [155/458] Large capacity start up control heating

Daikin FXDQ25PBVE6 [155/458] Large capacity start up control heating
Special Control Si34-803
144 Function
3.2 Large Capacity Start Up Control (Heating)
For startup, oil return operation, or setup after defrosting, start up multiple compressors at a high speed according to the
conditions of indoor units with thermostat ON, thus maximizing the equipment capacity.
Start up STD compressors at intervals of 15 seconds.
INV
STD
0
5
10
20
15
25
Pressure
Pc
Pe
Time
Number of
compressors
3
9
7
4
5
6
8