Daikin FXSQ32MVE [278/458] Si34 803 troubleshooting by indication on the remote controller

Daikin FXDQ63NBVE [278/458] Si34 803 troubleshooting by indication on the remote controller
Si34-803 Troubleshooting by Indication on the Remote Controller
Troubleshooting 267
The resistors among
U, V, and W are unbalanced or
short-circuited.
NO
YES
Replace the fan motor.
Replace the fan motor.
*1. Measurement of power wire connector.
Remove the X1A connector from the fan PC board (A2P) and
measure the resistance between the U and V, V and W, and W
and U phases of the motor connector (with five conductors) and
check that each phase are balanced (within a permissible
dispersion range of ±20%).
*2. Measurement of signal wire connector.
Remove the X2A connector and measure the resistance between
GND and V
CC, HW, HV, or HU terminals of the motor connector
(with five conductors).
Turn on the power.
Remove the signal connector
from the fan motor and check
the resistance (*2).
Between V
CC
and GND
terminals, and between GND
and H
W
, H
V
, or H
U
terminals
are short-circuited.
YES
NO
The HAP
lamp of the indoor PC
board (A1P) blinks and the HAP
lamp of the fan PC board
(A2P) is off.
YES
NO
Replace the fan motor.
Replace the fan PC
board (A2P).
5 Gray
4 Pink
3 Orange
2 Blue
1 Yellow
GND
Vcc
Hw
H
V
HU
5 Red
4
3 White
2
1 Black
U
V
W
Connector power wire use (X1A) Connector signal wire use (X2A)