Daikin FXSQ32MVE [437/458] How to calculate the additional refrigerant to be charged

Daikin FXDQ32PBVTS [437/458] How to calculate the additional refrigerant to be charged
Example of connection (R-410A Type) Si34-803
426 Appendix
a
How to calculate the additional
refrigerant to be charged
Additional refrigerant to be charged : R (kg)
(R should be rounded off in units of 0.1 kg.)
Example for refrigerant branch using REFNET joint and REFNET header for the systems and each pipe length as shown below.
Outdoor system : RXYQ34P~
Total capacity of indoor unit : 116%
a : φ19.1 × 30m
b : φ
φ
15.9 × 10m
c : 9.5 × 10m
d : φ9.5 × 10m
e : φ
φ
9.5 × 10m
f : 9.5 × 10m
g : φ6.4 × 10m
h : φ6.4 × 20m
i : φ12.7 × 10m
j : φ
φ
6.4 × 10m
k : 6.4 × 9m
MODEL NAME
THE AMOUNT OF
REFRIGERANT
RX(Y)Q5P
RX(Y)Q8 ~ 12P
RX(Y)Q14 ~ 22P
RX(Y)Q24 ~ 30P
RX(Y)Q32 ~ 38P
RX(Y)Q40 ~ 48P
RX(Y)Q50 ~ 54P
0kg
0.5kg
1.0kg
1.5kg
2.0kg
2.5kg
3.0kg
TABLE B
MODEL NAME [RX(Y)Q ~ P]
INDOOR CONNECTION
CAPACITY [X]
X 100%
100% < X 120%
120% < X 130%
130% < X 140%
140% < X 150%
150% < X 160%
160% < X 170%
170% < X 180%
180% < X 190%
190% < X 200%
5P~8P 12P~14P
18P~22P 24P~28P 30P~32P 42P~44P 46P~48P 52P~54P10P 16P 34P 36P 38P 40P 50P
0.5kg
0.5kg
0.5kg
0.5kg
1.0kg
1.0kg
1.0kg
1.5kg 2.0kg
2.5kg
2.5kg
3.0kg
3.5kg
0.5kg 1.0kg 1.5kg 2.0kg 2.5kg
0.5kg
0.5kg
1.0kg 1.5kg
1.0kg 2.0kg 4.0kg1.5kg 2.5kg 3.0kg 3.5kg
1.5kg 2.0kg 2.5kg 3.0kg
1.5kg 2.0kg
0.5kg 1.0kg
1.0kg 1.5kg 2.0kg
0kg
0.5kg
TABLE A
R = ( 30 × 0.26 + 10 × 0.18 + 10 × 0.12 + 40 × 0.059 + 49 × 0.022 )+ 2.0 + 0.5
abi
RXYQ34P~ 116%
= 16.738 16.7kg
Round off units of 0.1 kg.
c+d+e+f g+h+i+j+k
Note 1
When the equivalent pipe length between outdoor and indoor
units is 90m or more, the size of main pipes (both gas-side and
liquid-side) must be increased.
Depending on the length of the piping, the capacity may drop, but
even in such case it is able to increase the size of main pipes.
Note 2
Allowable length after the first refrigerant branch kit to indoor units is 40 m or less, however it can be extended up to 90 m if all the following conditions are satisfied. (In case of “ Branch with REFNET joint ” )
Note 3
If the pipe size above the REFNET header is φ34.9 or more, KHRP26M73HP is required.
Diameter of above case
Model
Gas Liquid
RXYQ5 Type
φ19.1
Not Increased
RXYQ8 Type
φ22.2 φ12.7
RXYQ10 Type
φ25.4* φ12.7
RXYQ12 Type
Not Increased
φ15.9
RXYQ14 Type
Not Increased
φ15.9
RXYQ16 Type
φ31.8* φ15.9
*If available on the site, use this size.
Otherwise, it can not be increased.
* If available on the site, use
this size.
Otherwise it can not be
increased.
Required Conditions Example Drawings
1. It is necessary to increase the pipe size between the first branch kit and the final
branch kit. (Reducers must be procured on site)
However, the pipes that are same pipe size with main pipe must not be increased.
4. The difference between
[Outdoor unit to the farthest indoor unit] and [Outdoor unit to the nearest indoor unit]
40 m
2. For calculation of Total extension length, the actual length of above pipes must be
doubled. (except main pipe and the pipes that are not increased)
3. Indoor unit to the nearest branch kit 40 m
8 b+c+d+e+f+g+p 90 m
increase the pipe size of b, c, d, e, f, g
a+b×2+c×2+d×2+e×2+f×2+g×2
+h+i+j+k+l+m+n+p 1000 m
h, i, j....... p 40 m
The farthest indoor unit 8
The nearest indoor unit 1
(a+b+c+d+e+f+g+p)-(a+h) 40 m
Increase the pipe size as follows
φ
9.5 → φ12.7
φ12.7 → φ15.9
φ
φ
15.9 → φ19.1
19.1 → φ22.2
φ
φ
22.2 → φ25.4*
28.6 → φ31.8*
φ34.9 → φ38.1*
RXYQ18 Type
φ31.8* φ19.1
Model
Gas Liquid
RXYQ20 Type
φ31.8* φ19.1
RXYQ22 Type
φ31.8* φ19.1
RXYQ24 Type
Not Increased
φ19.1
RXYQ26 Type
φ38.1* φ22.2
RXYQ28 Type
φ38.1* φ22.2
RXYQ30 Type
φ38.1* φ22.2
RXYQ32 Type
φ38.1* φ22.2
Model
Gas Liquid
RXYQ34 Type
φ38.1* φ22.2
RXYQ36 Type
Not Increased
φ22.2
RXYQ38 Type
Not Increased
φ22.2
RXYQ40 Type
Not Increased
φ22.2
RXYQ42 Type
Not Increased
φ22.2
RXYQ44 Type
Not Increased
φ22.2
RXYQ46 Type
Not Increased
φ22.2
Model
Gas Liquid
RXYQ48 Type
Not Increased
φ22.2
RXYQ50 Type
Not Increased
φ22.2
RXYQ52 Type
Not Increased
φ22.2
RXYQ54 Type
Not Increased
φ22.2
a
ABCDEFG
bcdef
g
hi j kl mn
1234567
8
H1
p
Outdoor unit
REFNET joint (A-G)
Indoor units ( 1 - 8 )
R =
REFRIGERANT
AMOUNT FOR
HEAT PUMP SYSTEM
TABLE A
REFRIGERANT AMOUNT
FOR EXCEEDING CONNECTION
CAPACITY OF INDOOR UNIT
TABLE B
Total length(m) of liquid
piping size at φ22.2
0.37
Total length(m) of liquid
piping size at φ19.1
0.26
Total length(m) of liquid
piping size at φ15.9
0.18
Total length(m) of liquid
piping size at φ12.7
0.12
Total length(m) of liquid
piping size at φ9.5
0.059
Total length(m) of liquid
piping size at φ6.4
0.022
Outdoor unit
Main pipes
Increase
The first refrigerant branch kit
Indoor unit