Troubleshooting by Remote Controller Si34-803
254 Troubleshooting
8: ON 7: OFF 9: Blink
Malfunction
code
Operation
lamp
Malfunction contents Page
Referred
Indoor Unit A0 9 Error of external protection device 260
A1 9 PC board defect, E
2
PROM defect 261
A3 9 Malfunction of drain level control system (S1L) 262
A6 9 Fan motor (M1F) lock, overload 264,
265
A7 8 Malfunction of swing flap motor (M1S) 268
A8 9 Abnormal power supply voltage 270
A9 9 Malfunction of moving part of electronic expansion valve (Y1E) 271
AF 8 Drain level above limit 273
AH 8 Malfunction of air filter maintenance
AJ 9 Malfunction of capacity Determination Device 274
C1 9 Failure of transmission (between indoor unit PC board and fan PC board) 275
C4 9 Malfunction of thermistor (R2T) for heat exchange (loose connection,
disconnection, short circuit, failure)
277
C5 9 Malfunction of thermistor (R3T) for gas pipes (loose connection,
disconnection, short circuit, failure)
278
C6 9 Failure of combination (between indoor unit PC board and fan PC board) 279
C9 9 Malfunction of thermistor (R1T) for suction air (loose connection,
disconnection, short circuit, failure)
280
CC 8 Malfunction of humidity sensor system 281
CJ 8 Malfunction of thermostat sensor in remote controller 282
Outdoor Unit E1 9 PC board defect 283
E3 9 Actuation of high pressure switch 284
E4 9 Actuation of low pressure sensor 286
E5 9 Inverter compressor motor lock 288
E6 9 STD compressor motor overcurrent/lock 290
E7 9 Malfunction of outdoor unit fan motor 291
E9 9 Malfunction of moving part of electronic expansion valve (Y1E, Y2E) 294
F3 9 Abnormal discharge pipe temperature 296
F6 9 Refrigerant overcharged 297
H7 9 Abnormal outdoor fan motor signal 298
H9 9 Malfunction of thermistor (R1T) for outdoor air (loose connection,
disconnection, short circuit, failure)
299
J2 9 Current sensor malfunction 300
J3 9 Malfunction of discharge pipe thermistor (R3, R31~33T) (loose connection,
disconnection, short circuit, failure)
301
J5 9 Malfunction of thermistor (R2T,R7T) for suction pipe (loose connection,
disconnection, short circuit, failure)
302
J6 9 Malfunction of thermistor (R4T) for outdoor unit heat exchanger (loose
connection, disconnection, short circuit, failure)
303
J7 9 Malfunction of liquid pipe thermistor (R6T) 304
J9 9 Malfunction of subcooling heat exchanger gas pipe thermistor (R5T) 305
JA 9 Malfunction of high pressure sensor 306
JC 9 Malfunction of low pressure sensor 307
L0 9 Inverter system error
L4 9 Malfunction of inverter radiating fin temperature rise 308
L5 9 Inverter compressor abnormal 310
L8 9 Inverter current abnormal 312