Procedure of Self-Diagnosis by Remote Controller Si-71A
92 Troubleshooting
4. Procedure of Self-Diagnosis by Remote Controller
4.1 The INSPECTION/TEST Button
Explanation
By turning the remote controller’s inspection /test button ON, you can change the mode as shown in the
figure on the right.
When in the inspection mode, malfunction contents can be cleared by continuing to press the ON/OFF
button for 5 seconds.
(Let you know completion timing by blinking.)
To carry out a test run, follow the procedure below.
1. Open the gas side stop valve all the way
2. Open the liquid side stop valve all the way.
3. Energize the crank case heater for 6 hours.
4. Enter the test run mode.
5. Continue to operate by the operation switch for 3 minutes.
6. Enter the normal mode.
7. Check the functions according to the operation manual.