Daikin FHYB45FV1 [171/244] Removal of drain pump

Daikin FHYC140KVE [171/244] Removal of drain pump
For FUY71/100/125FJ Si-71A
160 Removal Procedure
3.6 Removal of Drain Pump
Procedure
Warning Be sure to turn off all power supplies before disassembling work.
Step Procedure Points
1. Drain pump is located at
piping side.
Cut clamp material of hose,
and disconnect hose from
pump.
Caution
When reconnect drain hose with the
pump, secure hose at joint using
clamping material such as Tielap.
(Clamping material should be normally
included in the stock items.)
2. Remove four screws to
dismount drain pump.
3. Dismount drain pump by
pulling it down.
4. Removing float switch
a.Loosen three mounting
screws to remove drain
pump mounting base.
b.Remove two screws
located at opposite side of
drain pump mounting base
to dismount float switch.