Daikin FHYB45FV1 [108/244] Procedure of self diagnosis by led

Daikin FHYB45FV1 [108/244] Procedure of self diagnosis by led
Si-71A Procedure of Self-Diagnosis by LED
Troubleshooting 97
5. Procedure of Self-Diagnosis by LED
5.1 Troubleshooting by LED on The Indoor Unit’s
Foreword
Troubleshooting can be carried out by service monitor LED (green). (Blinks when normal)
ò
: LED on
ó
: LED off
ñ
: LED blinks — : No connection with troubleshooting
Note:
1. If LED-B is off, the transmission wiring between indoor and outdoor unit may be incorrect or
disconnected. Before performing the previously described troubleshooting, check the transmission
wiring.
2. Troubleshoot by turning off the power supply for a minimum of 5 seconds, turning it back on, and then
rechecking the LED display.
5.2 Troubleshooting by LED on The Outdoor Unit’s PC Board
With the power supply turned “ON,” the troubleshooting listed below by the outdoor unit’s maintenance
monitor LED.
ò
: LED on
ó
: LED off
ñ
: LED blinks — : No connection with troubleshooting
Green LED : Normal when ON, No LED: Normal when OFF
Note:
1. Check troubleshoot by turning off the power supply for a minimum of 5 seconds, turning it back on, and
then rechecking the LED display.
2. Turn off the power supply for a minimum of 5 seconds, and when turning it back on after disconnecting
transmission wiring No. 2, if the outdoor unit’s LED-A blinks, the indoor unit’s PC board is defective.
3. Previous malfunction data is displayed on the malfunction detection monitor. After inspecting, turn off
the power supply once.
4. Switch 2 of the 3 power supply cables and recheck.
General
Precautions When
Performing
Maintenance
1. When disconnecting the fasten terminal from the PC board, hold down the PC board with your finger
and do not apply excessive force. Also, do not hold the neck of the fasten terminal and pull the lead
wire.
2. Do not use a mega tester on the secondary side (transformer secondary side) of the electronic circuitry.
3. Even when not energized, beware of static electricity when touching parts or pattern. (If handling PC
board when dry [winter], be sure to discharge the electrostatic charge by grounding. Do not touch any
other grounded metal parts with your fingers.)
Microcomputer
Normal Monitor
Transmission Normal
Monitor
Contents/Processing
H1P (LED-A) H2P (LED-B)
ññ
Normal
Outdoor unit
ñò
Failure of indoor unit PC board ass’y
ó
If outdoor unit’s LED-A blinks, failure of indoor unit PC board
ass’y (Note 1)
ò
Failure of indoor unit PC board ass’y (Note 2)
ó
Malfunction of power supply or failure of PC board ass’y
(Note 2)
Microcomputer
Normal Monitor
LED-A (Green)
Malfunction Detection
Monitor (Note 3)
Contents/Processing
LED1
(red)
LED2
(red)
ñóó
Normal
to outdoor unit
ñòó
Actuation of safety device
óò
Main power supply reverse phase connection of lack of phase
(Notes 4)
òò
Malfunction of sensor system
ò
Failure of outdoor unit PC board (Notes 1)
ó
Malfunction of power supply or failure of outdoor unit PC board
(Note 1, 2)

Содержание