Si-71A Troubleshooting by Remote Controller Display / LED Display
Troubleshooting 117
6.19 Lack of Gas Malfunction
Remote Controller
Display
83
8383
83
LED Display
A(H1P) —
ýýý
1(H2P) — 2(H3P) —
Applicable Models
R(Y)
Method of
Malfunction
Detection
Lack of gas is detected according to discharge pipe temperature.
Malfunction
Decision
Conditions
Microcomputer decides whether there is a lack of gas and detects malfunction.
Stop due to malfunction does not occur even though a malfunction is determined to have occurred.
Supposed Causes
Lack of refrigerant
Refrigerant piping circuit clogging
Troubleshooting
Is the
amount of
refrigerant correct?
YES
Charge with the proper amount
of refrigerant.
Check the refrigerant piping
circuit for clogging.
NO
(SF021)