Daikin FHYB45FV1 [38/244] Fan speed off when thermostat is off

Daikin FHK60FJV1 [38/244] Fan speed off when thermostat is off
Si-71A Method of Field Set (Reset after Maintenance Inspection/Repair)
Explanation of Field Set 27
Multiple Settings
A/b
When the indoor is being operating by outside control (central remote controller, etc.), it sometimes does
not respond to ON/OFF and temperature setting commands from this remote controller. Check what setting
the customer wants and make the multiple setting as shown below.
After Setting
Stick the Unit No. label at decoration panel air discharge outlet as well as on the back of the wireless
remote controller.
<In case of FUY>
PRECAUTIONS
Set the Unit No. of the receiver and the wireless remote controller to be equal. If the setting differs, the
signal from the remote controller cannot be transmitted.
1. Do not use any settings not listed in the table.
2. For group control with a wireless remote controller, initial settings for all the indoor units of the group are
equal. (For group control, refer to the installation manual attached to the indoor unit for group control.)
1.5.6 Fan Speed OFF When Thermostat is OFF
When the cool/heat thermostat is OFF, you can stop the indoor unit fan by switching the setting to “Fan
OFF.”
Used as a countermeasure against odor for barber shops and restaurants.
Setting Table
Remote Controller Indoor Unit
Multiple Setting Remote Controller Display Controlled by other Air
Conditioners and Devices
For other than on Left
A: Standard All items Displayed. Commands other than ON/
OFF and Temperature
Setting Accepted. (1 LONG
BEEP or 3 SHORT BEEPS
Emitted)
b: Multi System Operations Remain
Displayed Shortly after
Execution.
All Commands Accepted (2 SHORT BEEPS)
Mode No. First Code No. Second Code No. Setting
11(21) 2 01
02 Fan OFF

Содержание