Si-71A Troubleshooting by Remote Controller Display / LED Display
Troubleshooting 103
6.5 Indoor Unit Fan Motor Lock
Remote Controller
Display
$9
$9$9
$9
Applicable Models
FH(Y), FAY, FUY
Method of
Malfunction
Detection
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Decision
Conditions
When number of turns can’t be detected even when output voltage to the fan is maximum
Supposed Causes
Failure of indoor unit fan motor
Broken or disconnected wire
Failure of contact
Failure of indoor unit PC board
Troubleshooting
With
X26A
unplugged
and the power
supply turned on,
is there about 12
VDC between
pins 1 and
3 of
X26A?
YES
YES
Connect correctly.
Indoor unit PC board
replacement
Check indoor unit fan motor
and motor wiring.
Are
X20A and
X26A properly
connected?
NO
(SF007)
NO