Daikin FHYB45FV1 [67/244] Outdoor unit

Daikin FHYB45FV1 [67/244] Outdoor unit
Electric Function Parts Si-71A
56 Explanation of Function Operation
3.2 Outdoor Unit
RY
Figures inside parentheses are for E unit (anti-corrosion specifications).
RY71KY1 RY71KV1 RY100KY1 RY125KY1
M1C Compressor JT95BC-YE JT95BC-V1 JT125BC-YE JT160BC-YE
J1HC Crank Case Heater 33W
S1PH Pressure Switch for Maintaining
High Pressure
ACB-DB82
OFF : 30
+0
-1
(kg/cm²G)
ON : 22
±
1.5 (kg/cm²G)
S2PH Pressure Switch for Maintaining
High Pressure
ACB-CB57
OFF : 24
±
1 (kg/cm²G)
ON : 19
±
1 (kg/cm²G)
S1LP Pressure Switch for Low
Pressure Control
20PS-1164-1
OFF : –23
±
15 (cmHg)
ON : 0.5
±
0.3 (kg/cm²G)
K1M Magnetic Switch HOE-20F-TRA1 HOE-26F-TRA1 HOE-20F-TRA1
F1C Overcurrent Relay 7.5A 22A 10A 13A
M1F Outdoor Unit Fan (Upper) 70W 90W 95W
M2F Outdoor Unit Fan (Lower) 65W
Q1L
Q2L
Outdoor Unit Fan Motor Safety
Thermostat
OFF : 135
±
5°C
ON : Below 120°C
C1R Capacitor for MF1 6
µ
F
C2R Capacitor for MF2 6
µ
F
A1P Outdoor Unit Control PC Board
EC9526 EC9525 EC9530
A2P Outdoor Control PC Board
(Models for the FJ Type Only)
R1T Thermistor (for Outdoor Air) ST9303
R2T Thermistor (for Heat Exchanger) ST8604A
R3T Thermistor (for Discharge Pipe) ST8606
T1R Transformer TR21H16R2
Y1R 4-way Changeover Valve V26-110B V38-110B VH40100
Y1E Electronic Expansion Valve DKV18D93 (Main Unit) EKV24D34
(Main Unit)
EKV26D35
DKV-MOZS130BO (Coil) EKV-MOZS107BO (Coil)
K1S Starting Relay CLK-15J02-P15
C3R,
C4R
M1C Capacitor 46
µ
F+23
µ
F—
C5R Starting Capacitor 50
µ
F—