Function Details Si-71A
70 Explanation of Function Operation
Solenoid Valve
Control (In the Case
of R(Y)140 K)
Solenoid valve :
ON condition
In range (1) or Discharge pipe temperature (T2) > Outdoor unit heat exchanger temperature (Tc) +30°C
OFF condition
In range (2) or T2 < Tc R 18°C
5.2.16 Fan Start Control in Heating Operation
The starting air flow volume is varied as shown below according to the outside air temperature condition.
Units operate with the starting air flow volume for up to 5 minutes.
When the outside air temperature is 10°C or lower, the air flow volume stays at H for the first 5 seconds
if it is switched from OFF to L.
(Outdoor unit fan startup compensation control)
*LPS is not detected for 3 minutes after startup.
5.2.17 High Pressure Protection Control in Heating Operation
The thermostat turns OFF immediately before HPS activation according to the indoor unit heat
exchanger temperature (Tc) to prevent shutdown due to an abnormality.
Control is provided to maintain Tc at 53°C.
Fan Tap 40~71 100~140
(1 Fan) Upper Fan (MF1) Lower Fan (MF2)
OFF OFF OFF OFF
LL OFF H
HHHH
HH HH HH HH