Daikin FHYB45FV1 [54/244] Emergency operation

Daikin FHYC100KVE [54/244] Emergency operation
Si-71A Existence of DIP Switch, Jumper and BS
Explanation of Field Set 43
3.2 Emergency Operation
Emergency
Operation of Indoor
Units
You can operate the system manually by changing the setting of the emergency switch (SS1) on the indoor
unit’s PC board from “Normal” to “Emergency.” When switched however the equipment cannot regulate
temperature. The table below contains a list by model of actuators for manually operating indoor units in
time of emergency.
Method of switching in time of emergency
Note:
1. Do not operate from remote controller during emergency operation.
2. Operate the switch only when the power supply is turned OFF.
Emergency
Operation of
Outdoor Units
Turn off the power supply and set the emergency switch to “Heat” for heating or “Cool” for cooling.
Operation will be started manually when you turn the power back on. (“Heat” cannot be set for a cooling
only air-conditioner.)
Concerning
Emergency
Operation
If a safety device should be actuated during emergency operation, all actuators are turned OFF. If you
reset after waiting for 3 minutes, operation will start again. Emergency operation cannot be carried out if the
PC board itself is defective.
Note:
For emergency operation, be sure to set emergency operation for both the indoor and outdoor units. Do not
attempt to operate the equipment from the remote controller during emergency operation. Emergency
operation is computer-controlled, and therefore cannot be carried out if the microcomputer is not operating
properly.
The table below contains a list of actuators for manually operating the equipment in time of emergency.
During emergency heating operation, defrosting is carried out for 3 minutes every hour. (4-way valve and
outdoor unit fan are turned OFF.)
Model Fan Drain Raising
FH(Y)C
{{
FH(Y)
{{
FUY
{{
FVY~F, FVY~L
{
FH(Y)B
{{
FH(Y)K
{{
FAY
{{
Actuator Cooling Heating
Compressor ON ON
4-WAY VALVE OFF ON
Outdoor Unit Fan H Fan Speed H Fan Speed
Electronic Expansion Valve 200 Pulses 200 Pulses
Indoor Unit Fan H Fan Speed H Fan Speed
Drain Pump ON ON