Tecnoclima VX 930 [110/116] 2 3 4 5

Tecnoclima VX 930 [110/116] 2 3 4 5
108108
109109
108
Heating the working department requires 17/18°C room temperature during working hours and an antifreeze temperature (5°),
during an inactive time.
Controlled by a chronothermostat the warm air heaters run automatically.
The air destratifyer, runs automatically controlled by an on-board installed thermostat, only if the air temperature reaches
settled value.
WORKING TIMETABLE:
08.00 - 12.00
13.30 - 17.30
CRONOTHERMOSTAT PROGRAM:
ON 06.00 - 12.00
OFF 12.00 - 13.30
ON 13.30 - 16.30
OFF 16.30 - 06.00
Schedule (hour)
Temperature (°C)
1 2 3 4 5
7 18,6 19,5 18,6 18,2 18,2
6 18,2 18,9 18,5 18,1 17,9
5 18,0 18,9 18,0 18,3 17,7
4 17,8 18,8 17,6 18,2 17,5
3 17,7 18,5 17,3 17,7 17,3
2 17,6 18,3 17,2 17,2 17,1
1 17,5 18,1 17,0 16,9 16,8
ΔT
1,1 °C 1,4 °C 1,6 °C 1,3 °C 1,4 °C
0,18 °C/m 0,15 °C/m 0,15 °C/m 0,21 °C/m 0,23 °C/m
0,18 °C/m
MEASURING
LEVEL
(meters)
SPAN QUANTITY
ΔT
MEDIUM
(°C/m)
1 2 3 4 5
7 20,3 20,7 19,6 19,1 18,8
6 20,0 20,5 19,3 18,9 18,7
5 19,8 20,2 19,1 18,5 18,5
4 19,6 20,0 18,7 18,3 18,4
3 19,4 19,5 18,3 18,1 17,8
2 18,8 19,1 18,0 17,8 17,2
1 18,5 18,8 17,8 17,1 16,5
ΔT
1,8 °C 1,9 °C 1,8 °C 2,0 °C 2,3 °C
0,30 °C/m 0,31 °C/m 0,30 °C/m 0,33 °C/m 0,38 °C/m
0,32 °C/m
MEASURING
LEVEL
(meters)
SPAN QUANTITY
ΔT
MEDIUM
(°C/m)
THE AIR TEMPERATURE
WITH RUNNING
DESTRATIFYER (ON):
THE AIR TEMPERATURE
WITHOUT RUNNING
DESTRATIFYER (OFF):
SPAN 1 SPAN 2 SPAN 3 SPAN 4 SPAN 5
WAREHOUSE
TUNNEL
HEATING CYCLE
ROOM AIR TEMPERATURE
Temperature course inside and outside the industrial building, checked during the testing day