Omron NYB1E-C13C6 [168/276] Installation

Omron NYB1E-313K2 [168/276] Installation
USB
USB
Industrial PC
Input
24 VDC
Power Supply (S8VK)
AC (L)
AC (N)
24 VDC
0 VDC
UPS (S8BA)
Output
Refer to the UPS S8BA User's Manual (Cat. No. U702) for details.
Refer to 5-4-3 Wire the Power Connector on page 5-36 for wiring details.
4 Supply power to the Power Supply
.
5 Press and hold the UPS power button until On appears on the UPS display.
6 Power ON the Box PC and then wait until the device drivers are successfully installed.
7 Configure the UPS using the
UPS Settings Utility.
Refer to UPS Setting Utility Instruction Manual for S8BA/BU-2RWL for details.
8 Install the Power Attendant Lite Utility.
Refer to NY-series Operating Systems and Software Utilities Manual (Cat. No. W616) for Pow-
er Attendant Lite Utility
details.
9 Configure the UPS using the Power Attendant Lite Utility.
Refer to NY-series Operating Systems and Software Utilities Manual (Cat. No. W616) for Pow-
er Attendant Lite Utility
details.
10 Configure the Box PC to auto-start after power loss within the BIOS settings.
Refer to A-1 BIOS on page A-2 for BIOS details.
11 Simulate a power interruption and confirm a correct shutdown of the Box PC.
Start the Box PC
Start applications
Create a power interruption
Monitor the shutdown sequence and confirm a correct shutdown sequence
The UPS is connected and configured.
The Box PC will shut down properly in case of a power supply interruption and restart automatically
when the power is restored.