Aten KE6900 [179/222] Rs 232 command

Aten KE6900 [179/222] Rs 232 command
Chapter 13. RS-232 Commands
165
RS-232 Command
The RS-232 command allows you to set the RS-232 settings for a device.
The formula for the RS-232 command is as follows:
Command + Address + Number + Baud Rate + Parity + Data Bit +
Stop Bit + Flow Control [Enter]
1. For example, to set device (192.168.0.33) with a baud rate of 38400, parity
of none, data bit of 8, and stop bit of 1, type the following:
baud a192.168.0.33 38400 none 8 1 [Enter]
2. For example, to set the local device with a baud rate of 19200, type the
following:
baud 19200 [Enter]
The following tables show the possible values for the RS-232 command:
Command Description
baud RS-232 command
Address Description
a Address command
Num1 Description
xx Address number
xx: Device ID or IP address
Baud Rate Description
9600 Use 9600 baud rate
19200 Use 19200 baud rate
38400 Use 38400 baud rate
115200 Use 115200 baud rate
Parity Description
None Sets the parity to none
Even Sets the parity to even
Odd Sets the parity to odd
Data Bit Description
5 Sets the data bit to 5
6 Sets the data bit to 6