Daikin FAQ100BVV1B [143/381] Forced operating mode emergency operation

Daikin FCQ125DV3B [143/381] Forced operating mode emergency operation
ESIEN05-04 Functional concept
Part 2 Functional Description 2–5
3
2
4
5
1
1.3 Forced Operating Mode (Emergency Operation)
Purpose The table below describes the purpose of the forced operating mode.
Starting conditions You can operate the system manually by changing the emergency switch on the indoor and outdoor
PCB from "normal" to "emergency". When the system is operating in "emergency" it can not control
the room temperature.
Both the indoor and outdoor unit must be set to "emergency" while the power is off.
Ending conditions You can end the emergency operation by changing the "emergency" switch back to "normal" while the
power is OFF.
Emergency
operation
Below table explains what will happen when the switch is set to "emergency":
How to set
Emergency
Operation
To set emergency operation, proceed as follows:
If... Then...
Q R/C is defective
Q Indoor PCB is defective
Q Outdoor PCB is defective
Forced operating mode can be used to go to cooling or heat-
ing. In forced operating mode, the compressor is forced to
operate until the defective indoor or outdoor PCB is back
online.
Changing the switch to "emergency" for the… Switches ON the…
Indoor unit
Q Indoor fan(s)
Q Drain pump
Outdoor unit
Q Compressor
Q Outdoor fan(s)
Step Action
1 Turn OFF the power.
2 Switch ON the emergency switch (SS1) on the indoor PCB.
Normal
Emergency