Daikin FAQ100BVV1B [210/381] Malfunction of transmission between indoor and outdoor unit u4 or uf

Daikin FCQ71DV3B [210/381] Malfunction of transmission between indoor and outdoor unit u4 or uf
Error Codes: System Malfunctions ESIEN05-04
4–4 Part 3 Troubleshooting
3
1
3
4
5
1.2 Malfunction of Transmission between Indoor and Outdoor Unit (
U4
or
UF
)
Error code U4 or UF
Error generation The error is generated when the microprocessor detects that the transmission between the indoor and
the outdoor unit is not normal over a certain amount of time.
Causes The possible causes are:
Q Wiring indoor-outdoor transmission wire is incorrect
Q Malfunctioning indoor unit PCB
Q Malfunctioning outdoor unit PCB
Q Outside cause (noise...).
Troubleshooting 1 Diagnosis of incorrect or broken/disconnected wiring. If the LEDs on the indoor unit PC board are off,
it indicates that the transmission wiring between indoor and outdoor units may be incorrect or
broken/disconnected.
Caution Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Turn the power supply off
once and then back on.
Check of
indoor unit
microcomputer
normal
HAP
Check of
indoor unit
transmission
malfunction
HBP
Failure of indoor unit PCB or
malfunction of power supply
system.
Resets normally.
Could be outside cause (noise...).
Failure of indoor unit PCB.
Wire correctly.
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO (OFF)
NO (ON or OFF)
To outdoor unit
(next page)
Is HAP flashing?
Is HAP flashing?
Is
indoor-outdoor
transmission wire
connected
correctly?
Does
outdoor unit
microcomputer
normal H1P
flash?
Is H2P on?
Is H1P flashing?